The FPD‑7024 Addressable Fire Alarm Panel (FACP) can be used in commercial and public building applications such as schools, universities, manufacturing plants, and health care facilities. They are listed by UL for central station, local, auxiliary, and remote station systems.- Four IDC initiating zones (expandable to 8); up to 20 two-wire smoke detectors per zone
- Built in DACT
- Two notification applicance circuits (NACs) on board with a shared integral regulated 24 VFWR, 4 amp NAC power supply
- Easliy converts to an addressable control panel with the addition of the D7039 multiplex Expansion Module
- Programmable through front panel interface, remote FMR-7033 LCD fire alarm annunciator, remote programming software (RPS) or the DX4010V2 or DX4020
The FPD‑7024 addressable fire alarm panel supports four on‑board initiating zones that can be expanded to eight using the FPC-7034. Each initiating zone supports two‑wire and four‑wire detectors configurable as Class A , Style D or Class B, Style B loops. Each zone can support up to 20 two‑wire detectors, or any number of four‑wire detectors depending on available power. Each addressable fire alarm system has a built‑in digital fire alarm communicator transmitter (DACT).Enhance the FPD‑7024 conventional system features by adding a D7039 Multiplex Expansion Module. Adding a D7039 Multiplex Expansion Module to the FPD‑7024 fire alarm panel turns the conventional FACP into an addressable FACP. The D7039 adds up to 247 addressable points to the base system and adds an additional 400 events to the history buffer for a total of 499 events. The D7039 also increases the number of programmable relay outputs from 19 to 59 and expands system users to 100.
Central Station Reporting
The FPD-7024 FACPs send reports to two telephone numbers (or IP addresses with a DX4020 Network Interface Module installed) with full single, double, and backup reporting. They communicate in BFSK, SIA, Contact ID, Modem IIIa2, and 4/2 and 3/1 Tone Bursts.
Dirty Smoke Detector Monitoring
All on‑board zones and FPC‑7034 zones are continuously monitored for smoke detectors signaling a dirty condition using the Bosch Chamber Check feature and CleanMe protocol. If a detector's smoke chamber is dirty, the detector sends a CleanMe signal on the two‑wire loop or a dirty detector signal on the addressable loop. The control panel annunciates that there is a dirty detector on the loop or the address. The Chamber Check feature signals a dirty smoke chamber using the LED on the detector head.
Accessories
The FPD‑7024 enclosure has space for additional accessory modules and two D1218 (18 Ah) batteries or two D126 (7 Ah) batteries.
Notification Appliance Circuits (NACs)
Two Class A, Style Z or Class B, Style Y NACs provide up to 4 A of regulated 24 VFWR power to operate horns, strobes, bells, and other notification appliances. Each NAC can be programmed to provide Temporal Code 3, California March, steady, pulsed, and synchronized output for either Wheelock or System Sensor notification appliances.
User Interface
A viewing port in the locked control panel enclosure door shows the system status light‑emitting diodes (LEDs) and liquid‑crystal display (LCD) while maintaining system keypad security. Unlocking the enclosure door provides access to the system controls for silencing off‑normal conditions, zone bypassing, detector resetting, testing, other fire functions, and programming. These functions are also available on all FMR‑7033 LCD fire alarm annunciator keypads connected to the system.
Organized Event Display
Sorts alarm, trouble, and supervisory events into categories and allows scrolling through specific events.
History Buffer
The system stores events in a 99‑event history buffer.
Click here for additional information on the BOSCH FPA-1000. Bosch's larger addressable fire alarm system.