When replacing a fire alarm control unit (panel) in an existing building due to obsolescence or the addition of ADA required notification appliance, is the new fire alarm panel required to be only code compliant and listed compatible with the other existing components such as smoke detectors, heat detectors, pull stations, etc or is the complete fire alarm and detection system for the entire building required to be made code compliant as for new buildings?
Interpretation:
No fire alarm system will sustain itself over the full life expectancy of a building. Eventually the fire alarm control panel or system in that building will need to be replaced. In an existing building, the replacement of the fire alarm system due to obsolescence, catastrophic failure, voluntary or the addition of ADA required notification appliances is not intended to retroactively require a complete fire alarm system upgrade or compliance with current code requirements not in place at the time when the fire alarm system was originally installed.
The replacement of a fire alarm panel, necessary to support construction improvements within a portion of a building, shall also not retroactively require a complete fire alarm system upgrade.
Where the existing fire alarm panel is replaced with a control unit of a different manufacture or utilizing devices of a different technology, the existing initiating devices and conductors may be replaced on a one-for-one basis in the existing locations, provided those devices had been installed in accordance with their listings and location(s) at the time of installation, for compatibility with the new fire alarm control unit.
Creating a situation of multiple fire alarm control panels should be avoided, however, it is not the intent of the code or standards to prohibit the addition of notification appliance circuit panels (NAC) or power supply expander panels.
The AHJ (authority having jurisdiction) shall be consulted prior to the replacement or modification of any fire alarm control equipment. When consulting with the AHJ make sure to provide complete documentation in accordance with NFPA 72, State codes and local codes.