Hyperterminal Settings for Addressable Fire Alarms

These are the correct Hyperterminal settings for the Gamewell and FCI Fire Control Instruments addressable fire alarm panels.

FCI 7100 Series Addressable Fire Alarm Panel:

Bits per Second: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None

FCI E3 Series Addressable Fire Alarm Panel:

Bits per Second: 115200
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None

Notifier 2020 Series Addressable Fire Alarm Panel:

Bits per Second: 2400
Data Bits: 7
Parity: Even
Stop Bits: 1
Flow Control: None

Gamewell 600 Series Addressable Fire Alarm Panel:
Click here for a video demonstration

Bits per Second: 2400
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: Xon / Xoff

Hyperterminal and the Gamewell 600 Series addressable fire alarm panel.