You may ask yourself, "What's wrong with this?".
The answer is simple. As stated above the the fire alarm batteries must be replaced with 4 - 5 years from date of manufacture. If you write the installation date on the batteries then you are not noting accurate information. The reason for this is that there is no telling how long those fire alarm batteries sat in your warehouse or even the manufacturer's warehouse. However, most battery companies are stamping the fire alarm batteries with the month and year of manufacture. This is the date that you want to mark down.For your reference I have included the NFPA 72 code sections below:
Table 14.4.2.2 #5 (b) Fire alarm batteries shall be replaced in accordance with the recommendations of the alarm equipment manufacturer or when the recharged battery voltage or current falls below the manufacturer's recommendations.
10.5.9.1.2 When the fire alarm batteries are not marked with the month/year by the manufactuer, the installer sahall obtain the date code and mark the batteries with month/year of battery manufacture.