Monday, December 19, 2016

Fire Damper vs Smoke Damper | Fire/Smoke Damper Requirements Explained

Fire Alarms Online • Code & Field Guide
Fire dampers, smoke dampers and combination fire/smoke dampers are often confused because they may occupy the same ductwork but perform different life-safety functions. This guide explains what each damper does, where it may be required, how it is activated and where the fire alarm system fits into the picture.

Fire Damper vs Smoke Damper: What Is the Difference?

The simplest way to understand the difference is to look at what each damper is intended to stop.

  • Fire Damper: Protects an opening in certain fire-resistance-rated assemblies by restricting the passage of flame.
  • Smoke Damper: Restricts the movement of smoke through an air distribution or smoke-control system.
  • Combination Fire/Smoke Damper: Performs both functions where both fire-damper and smoke-damper protection are required.
Important: A fire-resistance-rated wall does not automatically mean that every duct penetration requires a fire damper, and a smoke damper does not automatically mean that a dedicated duct smoke detector must be installed next to it. The applicable building/mechanical code, construction type, listed assembly, exceptions, smoke-control design and approved sequence of operations all matter.

Quick Comparison: Fire Damper vs Smoke Damper vs Combination Damper

Damper Type Primary Function Typical Actuation Primary Listing
Fire Damper Restricts passage of flame through protected assemblies Heat-responsive device such as a fusible link or listed thermal release arrangement UL 555
Smoke Damper Restricts passage of smoke Listed smoke detection/control arrangement or smoke-control sequence UL 555S
Combination Fire/Smoke Damper Restricts both flame and smoke Heat-responsive protection plus smoke-control/detection functions as required UL 555 + UL 555S

What Is a Fire Damper?

A fire damper is an opening protective installed in an HVAC duct or air-transfer opening where required to maintain the protection provided by a fire-resistance-rated assembly.

Its job is primarily about fire and flame. When the damper's listed heat-responsive mechanism operates, the blades close to protect the opening through the rated construction.

Under the International Mechanical Code framework, fire dampers are required to comply with UL 555. The required fire-protection rating depends on the rating of the assembly being penetrated.

Does Every Rated Wall Require a Fire Damper?

No. This is one of the most important points in this entire article.

The requirement depends on what type of rated assembly is being penetrated and whether a code exception applies. Fire walls, fire barriers, fire partitions, shafts, rated exterior walls and horizontal assemblies do not all have identical requirements.

For example, the International Mechanical Code contains specific exceptions where certain duct penetrations through fire partitions may be permitted without a fire damper when prescribed construction and sprinkler conditions are satisfied.

That is why a designer should never use the shortcut:

"Rated wall = fire damper."

Instead, identify the actual assembly on the architectural life-safety plans and then apply the appropriate adopted building and mechanical code provisions.

Static vs Dynamic Fire Dampers

Fire dampers are also classified for the operating condition of the HVAC system.

  • Static fire dampers are intended for systems that automatically shut down during a fire event.
  • Dynamic fire dampers are designed and listed to close against airflow while the HVAC system is operating.

This distinction is extremely important. A static damper should not simply be substituted into an application where the fan is intended to remain operating during the fire condition.

What Is a Smoke Damper?

A smoke damper is designed to restrict the movement of smoke through ductwork, air-transfer openings and smoke barriers where required by the adopted code and system design.

Smoke dampers are generally motor-operated rather than relying solely on a fusible link. They are listed under UL 555S and are evaluated for smoke leakage and operation under specified temperature and airflow conditions.

The current IMC framework requires smoke dampers to have an appropriate leakage classification and elevated-temperature rating.

Where Are Smoke Dampers Required?

Common applications include certain penetrations of:

  • Smoke barriers
  • Corridor enclosures requiring smoke and draft control
  • Shaft enclosures
  • Fire walls or fire barriers serving as horizontal exits
  • Air-transfer openings through smoke partitions
  • Other locations specifically required by the adopted building or mechanical code

Just as with fire dampers, exceptions exist. The construction, sprinkler protection, duct configuration and smoke-control design can affect whether a damper is required.

What Is a Combination Fire/Smoke Damper?

A combination fire/smoke damper, often abbreviated FSD, provides both fire-damper and smoke-damper functions in a single listed assembly.

These dampers are used where the construction requires protection against both flame and smoke movement. Because they perform both functions, combination fire/smoke dampers must meet the applicable requirements of both UL 555 and UL 555S.

Combination fire smoke damper used in HVAC ductwork
Example of a combination fire/smoke damper used within HVAC ductwork.

Fire Barrier vs Smoke Barrier: Why It Matters

One reason damper requirements become confusing is that the terms fire barrier and smoke barrier are not interchangeable.

A fire barrier is a fire-resistance-rated construction assembly intended to restrict the spread of fire. A smoke barrier is a continuous membrane designed and constructed to restrict the movement of smoke.

Some assemblies may require protection against fire, some against smoke, and some situations require both. That distinction is one of the reasons combination fire/smoke dampers exist.

Does a Smoke Damper Always Need a Duct Smoke Detector?

No. This is another common misunderstanding.

The International Mechanical Code provides several recognized smoke-damper actuation arrangements depending on the application. Depending on where the damper is installed, actuation may involve:

  • A listed smoke detector installed in the duct near the damper
  • A spot-type detector associated with a smoke-barrier opening
  • A spot-type detector near an air-transfer opening
  • A corridor smoke-detection system
  • A total-coverage smoke-detection system serving the area
  • An engineered smoke-control system sequence

Therefore, the statement "every smoke damper gets a duct detector" is not correct.

Fire Alarm Designer's Note: Before adding a duct detector to every smoke damper on the mechanical drawings, identify the code-required actuation method and review the approved sequence of operations. Unnecessary detectors add cost, testing requirements and future maintenance without necessarily improving the system.

How Close Does a Smoke Detector Need to Be to a Smoke Damper?

Where the adopted code requires a smoke detector installed within the duct for local smoke-damper actuation, the model-code arrangement generally places that detector within 5 feet of the damper, with no air outlet or inlet between the detector and damper. The detector must also be listed for the anticipated air velocity, temperature and humidity at its installation location.

That requirement is application-specific. Do not take the 5-foot criterion and apply it indiscriminately to every damper in a building.

We cover this issue in much greater detail in our companion article: Smoke Detectors for HVAC Shutdown: In-Duct Smoke Detectors vs Duct Detectors.

What Happens When the HVAC Fan Shuts Down?

This is where damper control becomes especially interesting for fire alarm designers.

Sampling-tube duct detectors rely on airflow within their listed operating range. If a fan shuts down, the detector may no longer have the airflow required for its listed operation.

The mechanical code specifically addresses this condition for local smoke-damper detection. Outside of mechanical smoke-control systems, the design must account for damper closure when fan shutdown causes a local detector to lose the minimum velocity it requires for operation.

This is one reason designers should understand the difference between a traditional sampling-tube duct detector and other listed detection arrangements rather than simply copying the same detector detail onto every damper.

Does the Fire Alarm System Control the Damper?

Sometimes, but not always in exactly the same way.

The fire alarm system may provide an emergency-control signal through a listed relay or control module that causes the damper actuator or associated control circuit to move to its required position.

Other installations may incorporate local detection and controls, building automation interfaces, smoke-control equipment or a combination of systems.

The fire alarm contractor should never assume ownership of the entire damper assembly simply because a fire alarm relay appears on the sequence of operations.

Typical Trade Responsibilities

Although responsibilities vary by project, the work is commonly divided among several trades:

  • Mechanical contractor: damper, ductwork and often actuator installation
  • Electrical contractor: line-voltage or control power as specified
  • Fire alarm contractor: initiating devices, control modules, monitoring modules and programming where shown
  • Controls/BAS contractor: HVAC control interfaces where applicable
  • Smoke-control designer/engineer: required system sequence and performance criteria for engineered smoke-control systems

The approved drawings, specifications, equipment listings, sequence of operations and responsibility matrix should determine the actual scope.

Fire/Smoke Dampers in Engineered Smoke Control Systems

A damper that is part of an engineered smoke-control system is a different animal from a simple local damper intended only to close when smoke is detected.

Mechanical smoke-control systems may intentionally command some dampers open while commanding others closed to establish pressure relationships, exhaust smoke or provide makeup air.

That is why blindly programming every smoke damper to close on any alarm can defeat the intended smoke-control strategy.

The IMC specifically recognizes this issue. Where a fire damper would interfere with a required smoke-control system, approved alternative protection is required, and systems that serve both normal ventilation and smoke control must have their smoke-control performance addressed by the required rational analysis.

For a complete explanation of smoke-control sequences, positive status, damper monitoring, firefighters' controls and commissioning, read: Smoke Control Systems Explained for Fire Alarm Professionals.

What Is Positive Status for a Smoke-Control Damper?

In a mechanical smoke-control system, simply sending a command to a damper is not necessarily the end of the story.

The system may be required to verify that smoke-control equipment actually reached its commanded operating condition. For dampers, this is commonly accomplished using actuator auxiliary/end switches or other approved position-verification methods connected to monitoring inputs.

Think of the difference this way:

  • Control: "I told the damper to close."
  • Verification: "The damper actually reached the required position."

That distinction becomes extremely important when working with engineered smoke-control systems.

What Is UUKL Smoke Control?

When fire alarm equipment is being used as part of an engineered smoke-control system, the equipment listing and approved system configuration become especially important.

Fire Alarms Online has a separate introduction to this subject here: UUKL Smoke Control for Fire Alarm Systems.

Do not treat a normal HVAC shutdown sequence and an engineered smoke-control sequence as interchangeable. Smoke-control systems can involve dedicated controls, verification, firefighter override functions, equipment status and a detailed engineered sequence.

Fire Damper and Smoke Damper Ratings

Fire Damper Ratings

Under the current model mechanical-code framework, fire-damper ratings are coordinated with the fire-resistance rating of the assembly being penetrated. Typical minimum ratings include:

  • 1-1/2-hour damper: for assemblies rated less than 3 hours
  • 3-hour damper: for assemblies rated 3 hours or greater

Always verify the specific listed assembly and adopted code before selecting equipment.

Smoke Damper Ratings

Smoke dampers are evaluated differently. The model mechanical code requires smoke dampers to meet specified leakage and elevated-temperature ratings. Current IMC provisions recognize Class I or Class II leakage ratings and require an elevated-temperature rating of at least 250°F.

A combination fire/smoke damper must satisfy the applicable fire-protection rating requirements and smoke-damper requirements.

Access to Fire and Smoke Dampers

A damper that cannot be inspected or maintained becomes a major problem later in the life of the building.

The model mechanical code requires an approved means of access to fire and smoke dampers that is large enough to permit inspection and maintenance of the damper and its operating components.

Access locations must also be identified so maintenance and inspection personnel can find the damper.

Field Tip: During a job walk, look beyond the damper itself. Check whether the actuator, detector, end switch, fusible link and access opening will actually be reachable after ceilings and architectural finishes are installed. A beautiful installation hidden above inaccessible construction is tomorrow's service nightmare.

How Often Are Fire and Smoke Dampers Tested?

Fire and smoke dampers are not "install it and forget it" equipment.

Inspection and testing requirements are coordinated through standards including NFPA 80 for fire dampers and NFPA 105 for smoke dampers. Combination fire/smoke dampers involve both fire- and smoke-protection functions.

The applicable adopted editions, occupancy, damper type and approved inspection program should always be verified when establishing the required test interval and procedure.

During functional testing, the team should verify more than whether the blades move. Depending on the system, testing may involve:

  • Damper movement to the required position
  • Fire alarm initiating-device operation
  • Control relay/module operation
  • Actuator operation
  • HVAC fan response
  • Damper position/end-switch feedback
  • Fire alarm annunciation
  • Smoke-control panel indication
  • Manual firefighter override functions
  • Restoration to normal operation

Common Fire Alarm Design Mistakes With Dampers

  • Assuming every rated wall needs a fire damper. Check the actual assembly and applicable exceptions.
  • Putting a duct detector at every smoke damper. The required actuation method depends on the application.
  • Ignoring detector airflow requirements. Sampling-type duct detectors must operate within their listing.
  • Closing every damper on every alarm. This can conflict with an engineered smoke-control sequence.
  • Ignoring positive-status requirements. Mechanical smoke-control systems may require verification that equipment reached the intended position.
  • Confusing HVAC shutdown with smoke control. They are related concepts but are not the same system function.
  • Ignoring access. Dampers and associated devices must remain accessible for inspection and maintenance.
  • Designing from the fire alarm plans alone. Damper requirements frequently originate on architectural life-safety and mechanical drawings.

What Should a Fire Alarm Estimator Look for on the Plans?

When bidding a project, review more than the fire alarm drawings. Check the mechanical plans, life-safety plans, smoke-control drawings and sequence of operations for:

  • FD = Fire Damper
  • SD = Smoke Damper
  • FSD = Fire/Smoke Damper
  • Motorized smoke/fire dampers
  • Smoke detectors associated with dampers
  • Fire alarm control relays/modules
  • Damper end switches or position contacts
  • Fan shutdown interfaces
  • BAS interfaces
  • Smoke-control zones
  • Firefighter smoke-control panel points
  • Power-supervision requirements
  • Special inspection and commissioning requirements

Missing these interfaces during estimating can turn a seemingly simple fire alarm project into a pile of unplanned modules, relays, wiring and programming.

Frequently Asked Questions

What is the main difference between a fire damper and a smoke damper?

A fire damper is primarily intended to protect an opening against the passage of flame, while a smoke damper is intended to restrict the movement of smoke. A combination fire/smoke damper performs both functions.

Are fire dampers controlled by smoke detectors?

A conventional fire damper is primarily actuated by a heat-responsive device. A combination fire/smoke damper also incorporates the required smoke-control function and can therefore have both thermal and smoke-related actuation requirements.

Does every smoke damper need a duct detector?

No. The model codes recognize several smoke-damper actuation methods depending on the damper location and system design. Local duct detection is only one possible method.

What is an FSD?

FSD commonly means fire/smoke damper. It is a listed combination damper designed to provide both fire-damper and smoke-damper protection.

What standard covers fire dampers?

Fire dampers are listed under UL 555.

What standard covers smoke dampers?

Smoke dampers are listed under UL 555S.

Can a smoke-control damper remain open during a fire?

Yes, depending on the engineered smoke-control sequence. Some dampers may need to open while others close to establish pressure relationships, exhaust smoke or provide makeup air. Always follow the approved rational analysis and sequence of operations.

Does the fire alarm contractor normally furnish the damper?

Typically the damper and actuator are part of the mechanical scope, while the fire alarm contractor provides specified detection, control and monitoring interfaces. Actual responsibility must be determined from the project documents.

Related Fire Alarm & Smoke Control Guides

If you work with fire/smoke dampers, these Fire Alarms Online guides are worth keeping together:

Author's Note: Fire and smoke damper requirements are heavily dependent on the adopted building and mechanical codes, the specific rated assembly, equipment listings and the approved smoke-control sequence. California projects may also be subject to California Building Code and California Mechanical Code amendments. Always verify the code edition adopted by the project jurisdiction and coordinate the final design with the mechanical engineer, fire protection engineer and Authority Having Jurisdiction.

Bottom Line: Fire dampers protect against fire. Smoke dampers restrict smoke. Combination fire/smoke dampers do both. But determining when a damper is required and how it must operate requires more than looking for a rated wall. Follow the adopted code, listed assembly, mechanical design and approved sequence of operations.

1 comment:

  1. Kyle, thanks for posting this article. The question I was researching when I came upon this is...Are stand-alone smoke dampers or Fire/smoke dampers required to be connected to the building fire alarm system?

    ReplyDelete