| 22.5° | 22.5° | 30° | 30° | |
| OFFSET | DISTANCE BETWEEN BENDS | SHRINK | DISTANCE BETWEEN BENDS | SHRINK |
| 2" | 5-1/4" | 3/8" | ||
| 3" | 7-3/4" | 9/16" | 6" | 3/4" |
| 4" | 10-1/2" | 3/4" | 8" | 1" |
| 5" | 13" | 15/16" | 10" | 1-1/4" |
| 6" | 15-1/2" | 1-1/8" | 12" | 1-1/2" |
| 7" | 18-1/4" | 1-5/16" | 14" | 1-3/4" |
| 8" | 20-3/4" | 1-1/2" | 16" | 2" |
| 9" | 23-1/2" | 1-3/4" | 18" | 2-1/4" |
| 10" | 26" | 1-7/8" | 20" | 2-1/2" |
| 45° | 45° | 60° | 60° | |
| OFFSET | DISTANCE BETWEEN BENDS | SHRINK | DISTANCE BETWEEN BENDS | SHRINK |
| 2" | ||||
| 3" | ||||
| 4" | ||||
| 5" | 7" | 1-7/8" | ||
| 6" | 8-1/2" | 2-1/4" | 7-1-4" | 3" |
| 7" | 9-3/4" | 2-5/8" | 8-3/8" | 3-1/2" |
| 8" | 11-1/4" | 3" | 9-5/8" | 4" |
| 9" | 12-1/2" | 3-3/8" | 10-7/8" | 4-1/2" |
| 10" | 14" | 3-3/4" | 12" | 5" |
- HOME
- NICET Fire Alarm Practice Exam (Levels I–IV)
- Bluebeam for Fire Alarm Design
- Occupancy FA Requirements
- California Fire Life Safety Exam Prep | Blue Card Boot Camp
- NFPA 72, IFC, and IBC Code Adoption Guide by State
- 520 HZ Low Frequency Audible Tone
- Frequently Asked Questions | Downloads, Tools & NICET Resources
- About Us
- Conduit Bending
Thursday, February 27, 2014
Conduit Bender Offset Reference Table
This is a chart to help you better understand the the shrink amount and the distance between conduit bends when performing a saddle with EMT, Rigid electrical conduit or any other type of electrical conduit. You will want to use the arrow mark on the conduit bender and refer to the degree markers along the side of the conduit bender head. Make sure the electrical conduit is always in line with the pipe bender to insure nice straight bends.