Wednesday, April 23, 2014

Dedicated Function Fire Alarm Systems | Sprinkler & Duct Detector Monitoring

Fire Alarms Online • Dedicated Function Fire Alarm Systems
Not every building that requires fire alarm monitoring requires a complete building fire alarm system. This guide explains dedicated function fire alarm systems, sprinkler monitoring, duct smoke detector interfaces and the important differences between alarm, supervisory and emergency control functions.

What Is a Dedicated Function Fire Alarm System?

A dedicated function fire alarm system is a protected-premises fire alarm system installed to perform one or more specific fire protection or emergency control functions rather than serving the general fire alarm needs of the entire building.

This distinction becomes extremely important when a building does not otherwise require a complete building fire alarm system but still contains equipment or systems that must be monitored or controlled.

Common examples can involve:

  • Automatic sprinkler waterflow monitoring
  • Sprinkler supervisory monitoring
  • Elevator recall and associated supervision
  • HVAC-related smoke detection and control functions
  • Other specific functions permitted by the applicable codes and approved system design
Key Concept: A dedicated function fire alarm system is still a fire alarm system. The difference is its scope and purpose. It performs specifically required functions without automatically becoming a complete building fire alarm system.

Building Fire Alarm System vs Dedicated Function Fire Alarm System

NFPA 72 distinguishes between a system serving the general fire alarm needs of a building and one installed specifically to perform particular functions.

System Primary Purpose
Building Fire Alarm System Serves the general fire alarm needs of the building and can include occupant notification, automatic detection, manual initiation, sprinkler monitoring, emergency control functions and other required features.
Dedicated Function Fire Alarm System Installed to perform specifically required fire protection, monitoring or emergency control functions where a complete building fire alarm system is not otherwise required.

For projects designed under NFPA 72, 2022, the definitions and protected-premises requirements in Chapters 3 and 23 establish this distinction.

Edition Note: Section numbering can change between NFPA 72 editions. Always verify the edition adopted by the project jurisdiction before applying a specific section number.

What Does a Building Fire Alarm System Do?

A building fire alarm system can incorporate numerous functions depending on the occupancy, applicable building/fire code and approved design.

These can include:

  • Manual fire alarm initiation
  • Automatic fire detection
  • Sprinkler waterflow monitoring
  • Fire suppression system supervision
  • Occupant notification
  • Emergency voice/alarm communications
  • Emergency control functions
  • Off-premises signal transmission
  • Other required fire alarm and signaling functions

A dedicated function system, by comparison, does not automatically need every feature associated with a complete building fire alarm system merely because it performs one required fire protection function.

When Can a Dedicated Function Fire Alarm System Be Used?

NFPA 72 recognizes dedicated function systems for facilities where a building fire alarm system is not otherwise provided and specific fire alarm, monitoring or emergency control functions still need to be performed.

In practical terms, this situation often appears when the adopted building or fire code does not require a complete building fire alarm system for the occupancy, but another provision requires monitoring or control of a particular fire protection system.

One of the most common examples is automatic sprinkler monitoring.

Example: Sprinkler Monitoring Without a Required Building Fire Alarm System

Consider a business occupancy that does not meet the applicable adopted code thresholds requiring a complete building fire alarm system.

Now assume the building is protected by an automatic sprinkler system that is required by the governing code to have its waterflow and supervisory conditions electrically monitored.

The absence of a requirement for a complete building fire alarm system does not automatically eliminate the sprinkler-monitoring requirement.

A dedicated function fire alarm system can therefore be used to perform the required sprinkler monitoring without unnecessarily converting the installation into a complete building fire alarm system.

Example dedicated function sprinkler monitoring fire alarm control panel
Example of a fire alarm control unit that can be used in appropriate dedicated-function applications when installed and configured as part of an approved system.

Sprinkler Waterflow and Supervisory Monitoring

A sprinkler monitoring system can receive several different types of sprinkler signals.

The two most important for fire alarm technicians are:

Condition Typical Fire Alarm Signal
Sprinkler Waterflow Alarm
Sprinkler Control Valve / Tamper Supervisory

These two conditions should not be combined simply because both originate at the sprinkler riser.

A waterflow device indicates the applicable sprinkler waterflow condition. A valve supervisory switch indicates that a monitored sprinkler control valve has moved from its normal position.

For the complete explanation, see: Fire Sprinkler Waterflow, Tamper, OS&Y & Backflow Guide →

What Should the Dedicated Function Panel Be Identified As?

Where NFPA 72 requires a dedicated function control unit specifically for sprinkler waterflow and supervisory monitoring, the system identification is important.

Under the applicable NFPA 72 requirements, the control unit and record documentation are identified according to the dedicated function being performed, such as:

SPRINKLER WATERFLOW AND SUPERVISORY SYSTEM

This immediately tells technicians, inspectors and emergency personnel that they are looking at a dedicated sprinkler-monitoring system rather than a complete building fire alarm system.

Does a Dedicated Function System Need Everything a Building Fire Alarm System Has?

No.

That is one of the central reasons the dedicated-function concept exists.

Where permitted by the applicable codes, a dedicated function system is not automatically required to include unrelated features simply because those features might be found on a complete building fire alarm system.

For example, the presence of a dedicated sprinkler-monitoring control unit does not by itself mean the building suddenly requires:

  • Manual fire alarm boxes throughout the building
  • Smoke detection throughout the building
  • Horn/strobe occupant notification throughout the building
  • Emergency voice/alarm communications
  • Every other feature associated with a complete building fire alarm system

Those requirements must come from the applicable building, fire, life-safety or other governing code and the approved design.

What About Duct Smoke Detectors?

This is where the subject becomes more interesting.

A duct smoke detector is typically installed to perform an HVAC-related smoke detection and emergency control function, such as initiating shutdown of air-moving equipment or another required HVAC response.

The requirements for the detector itself generally originate with the applicable mechanical, building or fire code. NFPA 72 then addresses how fire alarm system detection and emergency control interfaces are installed, supervised and monitored when they are connected to the fire alarm system.

Does a Duct Smoke Detector Automatically Initiate a Building Fire Alarm?

No.

A duct smoke detector is not automatically equivalent to an area smoke detector used for open-area fire detection.

Its primary purpose is associated with detecting smoke in an air-distribution system and initiating the required HVAC response.

The exact signal produced at the fire alarm system depends on the applicable code, system configuration and approved sequence of operations.

What If the Building Already Has a Building Fire Alarm System?

Where a building fire alarm system is installed and the applicable requirements call for the duct smoke detector to be monitored by that system, the duct detector is connected and monitored in accordance with the applicable NFPA 72 requirements.

The fire alarm system can then supervise the detector/interface and perform the required HVAC emergency control sequence.

Duct Smoke Detector → Fire Alarm System → Required HVAC Emergency Control Function

Depending on the approved sequence, the system can also provide the required annunciation and other associated functions.

What If There Is No Building Fire Alarm System?

This is where the original version of this article needs an important clarification.

The absence of a complete building fire alarm system does not automatically mean that every duct smoke detector must be completely standalone and can never be connected to a dedicated function fire alarm control unit.

The correct arrangement depends on:

  • The adopted mechanical, building and fire codes
  • The purpose of the duct detector
  • The required HVAC emergency control function
  • Whether monitoring is required
  • The capabilities and listing of the control equipment
  • The approved sequence of operations
  • Requirements of the authority having jurisdiction
Important: Do not use the existence or absence of a building fire alarm system as the only test for determining how a duct smoke detector must be connected. Start with the code requiring the duct detector and determine exactly what detection, control, annunciation and monitoring functions are required.

Can a Dedicated Function System Perform More Than One Function?

The term dedicated function can sometimes lead people to assume that a control unit must perform exactly one individual task.

That is not necessarily the correct way to understand the concept.

The important distinction is that the system serves specifically required functions rather than the general fire alarm needs of the entire building.

The functions actually assigned to a dedicated function control unit must be permitted by the applicable codes and supported by the equipment listing and approved system design.

Duct Smoke Detector vs Sprinkler Waterflow

These devices can both be connected to fire alarm equipment, but they perform very different jobs.

Device Primary Function
Duct Smoke Detector Detects smoke associated with the air-distribution system and initiates required HVAC-related emergency control functions.
Sprinkler Waterflow Device Detects the required sprinkler waterflow condition and initiates an alarm signal.
Sprinkler Valve Supervisory Switch Monitors abnormal position of a sprinkler control valve and initiates a supervisory signal.

Dedicated Function Systems and Elevator Recall

Sprinkler monitoring is not the only place technicians encounter dedicated function fire alarm equipment.

Elevator recall is another important example.

Where a complete building fire alarm system is not otherwise required, the applicable codes can permit specifically required elevator recall initiating devices and associated functions to be connected to dedicated function fire alarm control equipment.

This reinforces the larger concept: requiring a particular life-safety or emergency control function does not automatically mean the building requires every feature of a complete building fire alarm system.

Does the FACU Need Smoke Detection Above It?

Dedicated function control units are also important when determining the smoke-detection requirements associated with fire alarm control equipment.

NFPA 72 contains requirements for protection of fire alarm control equipment, along with conditions and exceptions that depend on the type of system, location and surrounding protection.

We cover that subject separately here: Is a Smoke Detector Required Above a Fire Alarm Control Panel? →

Common Dedicated Function Fire Alarm System Mistakes

  • Assuming every building containing fire alarm equipment has a complete building fire alarm system.
  • Assuming a dedicated function system must include every feature of a building fire alarm system.
  • Programming sprinkler waterflow as supervisory.
  • Programming sprinkler valve supervision as a fire alarm.
  • Assuming every duct smoke detector must initiate general occupant notification.
  • Assuming every duct detector must be standalone when no building fire alarm system exists.
  • Failing to identify the dedicated function control unit according to its actual function.
  • Adding unrelated fire alarm functions without determining whether they are required or permitted.
  • Ignoring the mechanical or building code that originally requires the duct smoke detector.
  • Using an outdated code edition without checking the jurisdiction's adopted edition.

How Should You Approach the Design?

Instead of beginning with the question, "What can this fire alarm panel do?", begin with:

What does the adopted code require this building to do?

Then work through the sequence:

  1. Determine whether the occupancy requires a building fire alarm system.
  2. Determine whether sprinkler monitoring is required.
  3. Determine whether duct smoke detection or HVAC emergency control is required.
  4. Determine whether elevator recall or other emergency control functions are required.
  5. Determine the required alarm, supervisory and trouble signals.
  6. Select listed equipment capable of performing those functions.
  7. Document the complete sequence of operations.
  8. Verify the requirements with the adopted code and authority having jurisdiction.
Fire Alarm Designer's Rule: Don't let the panel define the system. Let the code-required functions define the system, then select equipment capable of performing those functions.

Frequently Asked Questions

What is a dedicated function fire alarm system?

It is a protected-premises fire alarm system installed to perform specifically required fire protection, monitoring or emergency control functions rather than serving the general fire alarm needs of the entire building.

Is a sprinkler monitoring panel a fire alarm system?

Yes. A properly designed dedicated sprinkler waterflow and supervisory system is a type of fire alarm system even though it does not necessarily perform all the functions of a complete building fire alarm system.

Does sprinkler waterflow create an alarm?

Yes. The required sprinkler waterflow condition is an alarm function.

Is a sprinkler tamper switch an alarm?

No. A sprinkler control-valve supervisory switch normally produces a supervisory signal when the monitored valve moves from its normal position.

Does installing a sprinkler monitoring panel mean I need horn/strobes throughout the building?

Not automatically. Occupant notification requirements must be determined from the applicable codes and approved system design. A dedicated sprinkler-monitoring system does not by itself create every requirement associated with a complete building fire alarm system.

Does every duct smoke detector have to connect to the building fire alarm system?

The required arrangement depends on the adopted codes, whether a building fire alarm system is installed, the purpose of the duct detector and the required HVAC control and monitoring functions.

If there is no building fire alarm system, must the duct detector always be standalone?

No universal rule should be applied that way. The required arrangement must be determined from the applicable mechanical, building, fire and fire alarm requirements and the approved sequence of operations.

Can a dedicated function panel perform sprinkler monitoring and another required function?

Potentially, where permitted by the applicable requirements and supported by the listing and approved system design. "Dedicated function" does not necessarily mean the control unit can perform only one individual task.

Related Fire Alarm & Sprinkler Guides

Studying for the NICET Fire Alarm Systems Exam?

Dedicated function systems are a great example of why understanding system function matters just as much as memorizing individual code sections.

Fire Alarms Online offers a 550-question NICET Fire Alarm Systems practice collection covering Levels I through IV, along with a free 35-question sample.

NICET Fire Alarm Practice Exams • Levels I–IV

Practice code navigation, sprinkler monitoring, emergency control functions, initiating devices and troubleshooting.

View NICET Practice Exams →

Designing Fire Alarm Systems in Bluebeam?

Dedicated function systems are especially dependent on clear drawings and sequences of operation because the plans need to show exactly which functions the system is intended to perform.

Bluebeam Toolkit for Fire Alarm Professionals

Built for fire alarm layouts, takeoffs, estimating and faster PDF markup workflows.

View the Bluebeam Toolkit →

Bottom Line

A building can require specific fire alarm monitoring or emergency control functions without requiring a complete building fire alarm system.

That is where the dedicated function fire alarm system becomes extremely useful.

For sprinkler monitoring, it can provide the required waterflow alarm and valve supervisory functions without automatically adding every feature associated with a complete building fire alarm system.

For duct smoke detection and other emergency control functions, the designer must look at the specific code requiring the function and determine the required detection, control, monitoring and annunciation sequence rather than relying on a blanket rule.

The simplest way to remember the distinction is this: a building fire alarm system serves the building's general fire alarm needs; a dedicated function fire alarm system serves specifically required functions.

1 comment:

  1. This comment has been removed by a blog administrator.

    ReplyDelete