Thursday, October 22, 2026

Fire Alarm Sequence of Operations Matrix | NFPA 72 Guide

Technical editorial note: Verify the adopted code edition, project conditions, equipment listing, and local AHJ requirements before using this guidance for design or permitting.

What is a fire alarm sequence of operations matrix?

A fire alarm sequence of operations matrix is a cause-and-effect schedule that connects an initiating event to the required system response. The rows represent inputs, such as manual stations, sprinkler waterflow, smoke detectors, or supervisory switches. The columns represent outputs, such as panel indication, occupant notification, off-premises transmission, equipment shutdown, and fire safety control. Each intersection tells the reviewer and commissioning team what must happen when a particular event occurs.

Conceptual fire alarm sequence of operations workflow showing inputs, fire alarm control panel processing, and coordinated outputs
Figure 1. Conceptual cause-and-effect workflow. Actual programming and interfaces depend on the approved project design.

Why a matrix matters

A matrix provides a common reference for the designer, fire alarm contractor, controls contractor, elevator contractor, mechanical contractor, and authority having jurisdiction (AHJ). It can expose missing interfaces before installation and provide a repeatable basis for acceptance testing. San Francisco Fire Department submittal guidance expressly requests a sequence-of-operations matrix; its sample is a useful illustration, not a substitute for project-specific design.

Start with inputs and output groups

Build the input list from actual project equipment and approved system requirements. Separate general alarm inputs from supervisory and trouble conditions. Group outputs into control-unit annunciation, occupant notification, supervising-station transmission, and fire safety controls. Use distinct rows when two detectors have different consequences, even if their symbols look identical on the floor plan.

Illustrative cause-and-effect matrix

The following example is deliberately simplified. It is not a complete or universally code-compliant programming schedule. Actual outputs depend on occupancy, system design, adopted codes, the equipment listing, and AHJ approval.

Input eventPanelNotificationRemote signalOther action
Manual stationFire alarmPer designFire alarmPer approved matrix
Sprinkler waterflowFire alarmPer designFire alarmPer approved matrix
Valve tamperSupervisoryNot assumedSupervisoryPer approved matrix
Duct smoke detectorPer approved functionNot assumedPer approved functionHVAC interface if required

Coordinate across disciplines

For HVAC shutdown, identify the controlled equipment, control interface, responsible trade, and reset behavior. For elevator recall, coordinate detector locations, designated and alternate recall levels, elevator controller interfaces, and applicable elevator codes. For smoke control, distinguish the fire alarm initiating signal from the dedicated smoke-control sequence and status feedback. Never assume a generic “alarm” output adequately describes these functions.

Review the matrix before programming

Compare each input with the device schedule, drawings, riser diagram, and equipment list. Verify every required output has a documented interface and responsible contractor. Confirm alarm, supervisory, and trouble classifications; latching and reset behavior; and any required time delays. Review cause-and-effect dependencies and avoid assigning unsupported logic to listed equipment.

Use the matrix during acceptance testing

Turn each applicable row into a witnessed test step. Record the stimulus, expected response, actual response, responsible party, and pass/fail outcome. Retest affected functions after programming changes. Final records should reflect the installed configuration rather than an earlier design assumption.

Common mistakes

Common failures include combining unlike inputs into one row, leaving elevator or HVAC interfaces undefined, confusing supervisory conditions with general alarm, omitting remote transmission, and failing to revise the matrix after a field change.

Scope note: The tables below are educational examples, not approved design sequences. The adopted codes, approved drawings, equipment listings, manufacturer instructions, and AHJ determine the actual project requirements. Do not infer a universal output from a device type alone.

Illustrated fire alarm input output matrix showing initiating events and corresponding system response columns
Figure 2. Visual reference for reading a fire alarm input/output matrix. Use the detailed HTML matrix below for the complete example.

How to read the complete input/output matrix

Each row represents a distinct input condition; each output column represents an independently testable response. A means an illustrative activation, S a supervisory indication, T a trouble indication, C a conditional response requiring project-specific criteria, and — not indicated in this example. A blank or dash is not permission to omit a required function.

Example only: generic commercial building; interfaces and notification must be confirmed by design
Input/eventFACP statusLocal notificationSupervising stationHVAC actionDoor releaseElevator interfaceSmoke control
Manual fire alarm boxACC—C—C
General-area smoke detectorACCCC—C
Sprinkler waterflow switchACC—C—C
Sprinkler valve tamperS—C————
Duct smoke detectorCCCC——C
Elevator lobby smoke detectorACC—CC—
Elevator machine/control space detectorACC——C—
FACP AC power lossT—C————
SLC open / communication failureT—C————
Smoke control manual overrideC—CC——C

Worked example: sprinkler waterflow versus valve tamper

Assume a sprinkler riser has a listed waterflow switch and valve supervisory switch. Waterflow and valve movement are different event classes. The designer should not group them into a single generic “sprinkler” row. A typical waterflow event is an alarm input; a valve tamper is generally supervisory. Whether audible notification activates, how the signal is transmitted, and which ancillary controls respond depends on the adopted criteria and approved programming.

  1. Assign unique device identifiers, such as WF-1 and TS-1, consistent with the drawings.
  2. Record the event classification, control-unit text, annunciator display, and supervising-station point description.
  3. List each required output separately. Do not mark elevator recall or HVAC shutdown without a specific basis.
  4. Test each input and record both the local and remote response, including restoration and abnormal conditions.

Worked example: elevator lobby detection

A detector associated with elevator recall cannot simply be treated as interchangeable with an ordinary corridor detector. Identify the specific floor, elevator group, designated/alternate recall logic, and the relevant elevator code interface. A fire alarm matrix should reference the elevator contractor's approved interface sequence, not invent the final car movement logic. Document what signal the fire alarm system sends and what observable elevator-system result the integrated test must verify.

Matrix quality-control checklist

  • Each input has an address or zone reference and a distinct event classification.
  • Every interface appears on the floor plans, riser, and matrix under consistent identifiers.
  • Output descriptions name the controlled equipment and the responsible trade.
  • General alarm, supervisory, trouble, disablement, and restoration conditions are not conflated.
  • Test procedures reference a matrix row, observed output, and pass/fail criterion.
  • Conditional entries are resolved before programming and acceptance testing.

Keyword-focused questions

What is the difference between a fire alarm sequence of operations and a cause-and-effect matrix?

The narrative sequence describes intended behavior in words; the matrix maps each input to each output. Many projects benefit from both because the narrative explains conditions that a simple mark in a table cannot express.

Should every smoke detector trigger the same outputs?

No. Location, system function, adopted code, and approved design determine outputs. Elevator, duct, smoke-control, and general-area detection may have distinct sequences.

Frequently asked questions

Does every smoke detector activate every output? No. Response depends on the detector function and approved design. Is a narrative enough? Some jurisdictions accept other formats, but a matrix makes complex systems easier to review and test. Who approves the sequence? The design team coordinates it, and the AHJ reviews applicable submittals; the installing contractor must implement the approved logic.

Related Fire Alarms Online resources

Saturday, February 14, 2026

2025 California Carbon Monoxide Requirements – CBC 915, CFC 915 & NFPA 72 (2022)

The 2025 California Building Standards Code (Title 24) updates include important clarifications and enforcement emphasis for carbon monoxide (CO) alarms and detection systems.

This article breaks down:

  • When CO alarms/detection are required under 2025 CBC Section 915 and 2025 CFC Section 915
  • How the IFC Section 915 model requirements (the backbone of many state fire codes) broaden the “when required” scope beyond just dwelling units
  • Power and interconnection rules
  • Enclosed parking garage CO sensor requirements and how California coordinates to CMC 403.7.2
  • How NFPA 72 (2022) applies for inspection, testing, and maintenance where applicable

When Are Carbon Monoxide Alarms / Detection Required? (Two-Lane Approach)

CO requirements get mis-described a lot because designers mix “dwelling unit alarm rules” with “broader building CO detection rules.” To keep your plans plan-check-proof, think in two lanes:

Lane 1: Dwelling Units & Sleeping Units (CBC 915 focus)

Under 2025 CBC Section 915, CO alarms are commonly required in dwelling units/sleeping units when CO exposure risk sources are present, such as fuel-burning appliances and attached garages communicating with the dwelling unit. (CBC 915 framework.)

Common residential triggers include:

  • Fuel-fired appliances
  • Gas fireplaces
  • Fuel-burning forced-air furnaces
  • Attached garages that communicate with the dwelling unit
Combination smoke and carbon monoxide alarm installed on ceiling per California code requirements
Listed combination smoke and carbon monoxide alarms are permitted when installed in accordance with CBC 915 and CFC 915 requirements.


Lane 2: Broader “Interior Space” Requirements (CFC 915 / IFC 915 scope)

Important: The IFC Section 915 (model code basis for many state fire codes, including California’s structure) is broader than only dwelling-unit triggers. It addresses CO detection requirements for new and existing buildings where interior spaces are exposed to CO sources (direct sources, adjacent spaces with communicating openings, and forced-air-related source conditions). In other words: your project may require CO detection even when it doesn’t look like a classic “residential attached garage” situation.

Plan-review tip: On commercial/mixed-use jobs, describe CO detection requirements as: “Provide CO detection where required by CFC 915 for interior spaces exposed to CO sources, and provide CO alarms where required by CBC 915 for dwelling/sleeping units.”

Required Locations (CBC 915.2 concept + CFC/IFC placement logic)

Dwelling units (CBC approach): When required, CO alarms are typically installed:

  • Outside each separate sleeping area in the immediate vicinity of bedrooms
  • On every occupiable level of the dwelling unit, including basements
  • Additional devices may be required where fuel-burning appliances are located within bedrooms or attached bathrooms (project/AHJ dependent)

Broader interior spaces (CFC/IFC approach): Where CO detection applies to interior spaces exposed to CO sources, design should address:

  • Spaces containing CO-producing equipment (direct source locations)
  • Adjacent spaces with communicating openings where CO could migrate
  • Forced-air pathways that can distribute CO to other areas

Always coordinate exact device placement with manufacturer instructions, the adopted code language, and AHJ expectations.


Power & Interconnection (CFC 915.4 + CBC 915 structure)

Power Source (CFC 915.4.1)

CO alarms shall receive primary power from building wiring where such wiring is served from a commercial source, with battery backup where required.

Interconnection (CFC 915.4.4 / CBC 915 framework)

Where more than one CO alarm is required, alarms must be interconnected so activation of one activates all required alarms within the applicable unit/area. California’s 2025 cycle specifically retains clarifying language around interconnection implementation.

Combination Smoke/CO Devices

Combination smoke/CO alarms are permitted where properly listed/approved and installed per manufacturer instructions and adopted code requirements.


Enclosed Parking Garages – CO Sensors and Ventilation Control (CFC 915.6.1 + CMC 403.7.2)

Enclosed parking garage carbon monoxide sensor controlling exhaust ventilation per CFC 915.6.1
Carbon monoxide sensors installed in enclosed parking garages to control ventilation systems in coordination with CFC 915.6.1 and CMC 403.7.2.


This is where a lot of projects get tripped up.

  • Model code note: The IFC framework ties enclosed garage gas detection to mechanical ventilation code references (model mechanical code structure).
  • California note: In the 2025 cycle, California explicitly coordinates enclosed garage detector maintenance expectations through CFC 915.6.1 with reference to CMC 403.7.2.

Key takeaway: Treat enclosed garage CO sensors primarily as a mechanical ventilation control / IAQ scope unless the AHJ/EOR requires FACU integration. If integrated into the fire alarm system, document supervision, pathway, and point type clearly.


NFPA 72 (2022) – How to Reference It Without Getting Burned

Older references commonly point to NFPA 720 for CO detection. NFPA has stated that NFPA 720 requirements were incorporated into NFPA 72.

Safe spec language:

  • Install per the adopted California codes (CBC/CFC) and manufacturer instructions.
  • Where CO detection/notification equipment is part of a signaling system, perform inspection/testing/maintenance per NFPA 72 (2022) as applicable.

2022 vs 2025 Code Comparison (CBC/CFC CO Requirements)

Topic 2022 Cycle (General) 2025 Cycle (What to watch) Plan-Check Proof Note
Scope / “When Required” Commonly described as dwelling-unit driven in many field guides. Must describe both: dwelling/sleeping units (CBC) AND broader interior-space CO exposure conditions (CFC/IFC framework). Write the “two-lane” note on the cover sheet.
Power Hardwired where served by commercial power; battery backup where required. Same concept; cite CFC 915.4.1 explicitly for reviewer confidence. Call out power method and any remodel constraints.
Interconnection Interconnect multiple required alarms. California emphasizes implementation clarity; cite CFC 915.4.4 for consistency. State “hardwired or listed wireless” and show it on plans.
Enclosed Parking Garages Often treated as mechanical/energy controls work, coordinated across disciplines. CFC 915.6.1 coordinates maintenance expectations to CMC 403.7.2 in California. Add a garage SOO and fail-safe behavior.
NFPA Reference NFPA 720 often cited historically. NFPA states CO requirements are incorporated into NFPA 72; cite NFPA generally unless quoting licensed text. Write “NFPA 72 (2022) where applicable + manufacturer instructions.”

Plan Review Notes (Copy Into Drawings)

CARBON MONOXIDE (CO) – 2025 CBC / 2025 CFC GENERAL NOTES

1. Provide CO alarms and/or CO detection where required by the adopted codes:
   • 2025 CBC Section 915 for dwelling units and sleeping units (life-safety CO alarms).
   • 2025 CFC Section 915 for interior spaces exposed to CO sources (CO detection scope).
   Reference IFC Section 915 as the model basis for broader CFC 915 scope where applicable.

2. Power: CO alarms shall receive primary power from building wiring where served by a commercial source, with required secondary power/battery backup. (CFC 915.4.1)

3. Interconnection: Where multiple CO alarms are required, alarms shall be interconnected so that activation of one activates all required alarms within the applicable unit/area. (CFC 915.4.4 / CBC 915 framework)

4. Combination Smoke/CO Alarms: Combination devices shall be listed/approved and installed in accordance with adopted code requirements and manufacturer instructions.

5. Enclosed parking garages (where applicable):
   CO/NO2 detectors used for ventilation control shall be coordinated with mechanical design.
   In California, detector maintenance expectations coordinate through CFC 915.6.1 with CMC 403.7.2.

6. Inspection, testing, and maintenance:
   Perform per adopted code requirements, manufacturer instructions, and NFPA 72 (2022) where applicable.
   Note: NFPA states NFPA 720 requirements were incorporated into NFPA 72.

Garage CO Sensor Sequence of Operations (Typical)

ENCLOSED PARKING GARAGE – CO SENSOR CONTROL (TYPICAL)

GENERAL
- Provide CO (and where applicable NO2) sensors for ventilation control.
- Coordinate with mechanical ventilation controls per CMC 403.7.2.
- Maintain per CFC 915.6.1 and manufacturer requirements.

CONTROL LEVELS (VERIFY WITH EOR / MECH DESIGN)
Low CO Setpoint (typical 25–35 ppm; adjustable):
- Enable exhaust fans at LOW SPEED (Stage 1).
- Enable supply/make-up air as required.
- Send RUN status to BAS if provided.

High CO Setpoint (typical 50–100 ppm; adjustable):
- Enable exhaust fans at HIGH SPEED (Stage 2).
- Flag high-level condition to BAS (supervisory/trend).
- Continue ventilation until levels fall below reset threshold.

RESET / PURGE DELAY
- After CO drops below LOW setpoint, continue fans for timed purge (typical 5–15 minutes) then return to standby.

FAIL-SAFE
- On sensor fault, power loss, or communications loss, command minimum fan operation (Stage 1) and report TROUBLE/FAULT to BAS.

MAINTENANCE
- Test/calibrate per manufacturer interval.
- Maintain per adopted code requirements and NFPA 72 (2022) where applicable.

Keywords: 2025 California carbon monoxide requirements, CBC 915 carbon monoxide alarms, CFC 915 carbon monoxide detection, IFC 915 carbon monoxide code, CMC 403.7.2 garage ventilation control, NFPA 72 (2022) carbon monoxide.