Showing posts with label backflow preventer. Show all posts
Showing posts with label backflow preventer. Show all posts

Sunday, March 29, 2015

Fire Alarm Underground Conduits

Is it OK to Install Fire Alarm Cable underground?


PIV Post Indicator Valve for Fire Alarm Sprinkler System
Post Indicator Valve  with Fire Department Connection
A common task when installing a new fire alarm system is undergrounds. Typically when a C-16 or fire protection (fire sprinkler) contractor installs their incoming lines they will at the same time install the necessary fire alarm underground conduits for the connections to the backflow prevention switches (OS&Y Outside Screw and Yoke) or PIV (Post Indicator Valve) switches. However, sometimes this task could be a part of the fire alarm contractor's scope of work. If you find yourself installing underground conduit or direct burial cable make sure to follow all of the national codes and regulations.

Direct Burial Cable as an Alternate to Conduit


Backflow Preventor OS&Y For Fire Alarm Sprinklers
Backfloe Preventor with OS$Y Switches for Fire Alarm
Some contractor's may choose to use direct burial cable also referred to as UF Cable commonly identified by its grey coating. Direct burial fire alarm cable not protected in conduit must be installed at a depth of 24" below grade with either schedule 80 PVC or Rigid conduit stubs up to your box. When fire alarm cable is installed within plastic conduit it must be 18" deep and installed with schedule 80 PVC. This is a more durable plastic conduit (grey color) than the common household irrigation lines. The best way to install these conduits or cable is with a Ditch Witch. Simply set the depth and go.

Junction boxes that are run out into the middle of a remote area without an anchor point must have the schedule 80 PVC embedded in the concrete to support the box. Another method is to attach the box to a post that is either driven or buried in the ground 18" and connects directly to the schedule 80 PVC conduit. Junction boxes should be installed at least 12" above grade but not more than 18" for the unattached method.

See also conduit bending videos.

Make sure to join our Fire Alarms Online Facebook Group HERE.

Tuesday, October 1, 2013

Fire Sprinkler Waterflow, Tamper, OS&Y & Backflow | Fire Alarm Guide

Fire Alarms Online • Sprinkler Monitoring Guide
Waterflow switches, tamper switches, OS&Y valves and backflow preventers are commonly found around fire sprinkler risers, but they do not perform the same jobs. This guide explains what each component does and what the fire alarm system actually monitors.

Understanding Fire Sprinkler Monitoring

Fire alarm technicians routinely encounter sprinkler equipment without necessarily working on the hydraulic side of the sprinkler system.

Four terms come up constantly:

  • Waterflow switch
  • Tamper or valve supervisory switch
  • OS&Y valve
  • Backflow preventer

These components can be located close together, but each performs a different function.

The quickest way to understand the riser:

Waterflow switch: Detects sprinkler-system operation.
Tamper switch: Supervises the position of a control valve.
OS&Y: A type of indicating gate valve.
Backflow preventer: Protects the water supply against reverse flow.

What Is a Wet Pipe Sprinkler System?

A wet pipe sprinkler system normally contains pressurized water throughout the sprinkler piping.

When sufficient heat operates an automatic sprinkler, water discharges through that sprinkler and sustained water movement occurs through the system.

That water movement can operate a waterflow alarm-initiating device monitored by the fire alarm system.

For the complete operating sequence, see: Wet Pipe Fire Sprinkler Systems | How They Work →

What Is a Fire Sprinkler Waterflow Switch?

A waterflow switch detects the applicable waterflow condition associated with sprinkler-system operation.

On many wet pipe systems, this is accomplished with a vane- or paddle-type device mounted directly to the sprinkler piping.

A paddle extends into the water-filled pipe. When sufficient sustained water movement occurs, the paddle moves and operates the switch mechanism.

Sprinkler Operates → Water Moves → Paddle Moves → Waterflow Switch Operates → FACU Receives Alarm

We have an entire guide dedicated to the internal operation, retard and testing of this device: Fire Sprinkler Waterflow Switch | How It Works & Fire Alarm Monitoring →

Is Waterflow an Alarm or Supervisory Signal?

Sprinkler waterflow is an alarm function.

This is one of the most important distinctions for fire alarm technicians.

When the sprinkler waterflow alarm-initiating device operates, the fire alarm system processes the sprinkler waterflow as an alarm condition according to the approved system design.

A valve tamper condition is different.

Device What It Detects Fire Alarm Function
Waterflow Switch Required sprinkler waterflow condition Alarm
Valve Supervisory / Tamper Switch Control valve moved from its normal position Supervisory

What Is a Fire Sprinkler Tamper Switch?

The term tamper switch is commonly used in the field for a sprinkler valve supervisory switch.

Its purpose is to monitor the position of a valve controlling the sprinkler water supply.

If the valve moves sufficiently from its normal position, the supervisory switch changes state and the fire alarm system can receive a supervisory signal.

Important: A tamper switch does not normally detect waterflow. It monitors the position of a valve that can affect the availability of the sprinkler water supply.

Why Are Sprinkler Control Valves Supervised?

An automatic sprinkler system cannot provide its intended protection if a critical water-supply control valve has been improperly closed.

Electrical supervision allows movement of a monitored control valve from its normal position to create a supervisory condition at the fire alarm system.

That gives building personnel, service personnel or the supervising station an opportunity to investigate the condition before the sprinkler system is needed during a fire.

What Does OS&Y Mean?

OS&Y means Outside Screw and Yoke.

An OS&Y valve is a type of gate valve commonly encountered in fire protection water-supply arrangements.

One useful feature of this valve design is its visible stem.

As the valve is opened, the stem extends outward. As the valve is closed, the stem moves inward.

This gives technicians and inspectors a visible indication of valve position.

How Does an OS&Y Tamper Switch Work?

A listed OS&Y supervisory switch mounts to the valve and mechanically monitors movement of its stem.

A common arrangement uses a trip rod positioned in a groove on the valve stem when the valve is fully open.

When the valve begins moving away from its normal position, movement of the stem displaces the trip rod and changes the state of the supervisory switch contacts.

OS&Y Valve Moves → Supervisory Switch Operates → Monitor Module/Input Changes State → FACU Receives Supervisory Signal

Technician Tip: The OS&Y is the valve. The device mounted to it is the valve supervisory switch. In field conversation you may hear the entire arrangement called an "OS&Y tamper."

Is an OS&Y Valve a Backflow Preventer?

No.

This is a surprisingly common terminology mistake.

An OS&Y valve and a backflow preventer can both be part of the sprinkler water-supply arrangement, but they perform different functions.

An OS&Y valve is an indicating gate valve used to control water flow.

A backflow prevention assembly is intended to prevent unwanted reverse flow from the fire protection system toward the supplying water system.

Common Mistake: Do not use "backflow preventer" and "OS&Y" as two names for the same device. They are not synonymous.

What Is a Fire Sprinkler Backflow Preventer?

A backflow prevention assembly protects the supplying water system against reverse flow from the fire protection system.

The exact assembly used depends on the water-supply arrangement and applicable requirements.

Depending on the installation, a backflow assembly can have control valves that also require electrical supervision.

That is one reason fire alarm technicians frequently see supervisory switches physically located around a backflow assembly.

Does a Backflow Preventer Stop False Waterflow Alarms?

That should not be considered the primary purpose of a backflow preventer.

Its primary function is backflow protection.

Water-supply pressure fluctuations and transient movement can influence sprinkler alarm equipment, but those hydraulic effects should not be confused with the fundamental purpose of the backflow prevention assembly.

Can a Backflow Preventer Have Tamper Switches?

Yes. Control valves associated with a backflow assembly can be equipped with listed supervisory switches where valve-position supervision is required.

Depending on the valve style, different supervisory devices can be used.

For example, fire protection systems can use supervisory switches designed for:

  • OS&Y gate valves
  • Butterfly valves
  • Post indicator valves
  • Other listed valve arrangements

The important concept is that the switch must be appropriate for the valve and installed according to its listing and manufacturer's instructions.

What Is a Butterfly Valve Tamper Switch?

Not every supervised sprinkler valve is an OS&Y.

Butterfly valves are also commonly encountered in sprinkler systems and can incorporate or accept listed supervisory switches that monitor valve position.

From the fire alarm system's perspective, the objective is similar:

Valve Moves From Normal Position → Supervisory Device Operates → FACU Receives Supervisory Signal

The mechanical method used to monitor the valve depends on the valve and supervisory device.

What Is a Post Indicator Valve?

A Post Indicator Valve, or PIV, is another type of indicating control-valve arrangement commonly associated with fire protection water supplies.

A PIV provides a visible indication of whether the valve is open or shut.

Where electrical supervision is required, listed supervisory equipment can monitor movement of the valve from its normal position.

OS&Y valves, butterfly valves and PIVs may look completely different, but from the fire alarm technician's perspective the question remains:

What valve is being supervised, and what signal should the FACU receive when it moves from normal?

How Are Tamper Switches Connected to a Fire Alarm System?

On an addressable fire alarm system, dry contacts from the valve supervisory device are commonly connected to an addressable monitor or input module.

The basic sequence is:

Valve Supervisory Switch → Monitor Module → SLC → FACU → Supervisory Signal

The exact wiring depends on the fire alarm manufacturer, module, pathway configuration and approved design.

On conventional systems, valve supervisory contacts can instead be connected to an appropriate initiating circuit according to the listed fire alarm system design.

How Should Sprinkler Tamper Points Be Labeled?

Clear point descriptions matter.

A point labeled only:

TAMPER

does not tell responding personnel very much in a large building.

Where the system and approved documentation allow, descriptions should identify the actual valve or area being supervised.

Examples might include:

  • SPRINKLER MAIN CONTROL VALVE
  • 1ST FLOOR SPRINKLER VALVE TAMPER
  • 2ND FLOOR EAST SPRINKLER TAMPER
  • BACKFLOW CONTROL VALVE SUPERVISORY
  • PARKING GARAGE SPRINKLER VALVE

Specific descriptions can save a tremendous amount of time during service calls and emergency response.

How Fast Should a Tamper Switch Operate?

A valve supervisory device is intended to identify movement of the monitored valve from its normal position before the valve reaches a condition that could significantly impair the sprinkler water supply.

The exact operating criteria depend on the applicable code, valve type, supervisory device and installation.

Technicians should therefore verify operation using the applicable requirements and manufacturer's instructions rather than creating an arbitrary number of valve turns for every installation.

Waterflow Retard vs Tamper Switch Operation

Another common mistake is applying waterflow-switch thinking to valve supervision.

A waterflow switch can incorporate a retard intended to reduce unwanted alarms from brief water movement.

A valve supervisory switch performs a completely different function: detecting abnormal movement of a monitored valve.

Do not add an arbitrary waterflow-style delay to a sprinkler supervisory point simply because both devices happen to be located on the same riser.

What About the 90-Second Waterflow Requirement?

The familiar 90-second waterflow requirement applies to waterflow alarm initiation under the applicable sustained-flow criteria.

It does not mean every waterflow switch should simply be adjusted to delay for 90 seconds.

Remember: 90 seconds is a maximum alarm-initiation period under the applicable waterflow criteria, not a universal target retard setting.

For the detailed explanation, see: Fire Sprinkler Waterflow Switch | Retard, Testing & Fire Alarm Monitoring →

Does One Sprinkler Cause Every Sprinkler to Open?

No.

In a conventional wet pipe sprinkler system using automatic sprinklers, individual sprinklers operate when sufficient heat reaches their heat-responsive elements.

One sprinkler operating does not electrically command every other sprinkler in the building to open.

Additional sprinklers operate only if conditions at those sprinklers cause their individual heat-responsive elements to operate.

Hollywood vs Reality: Pulling a manual fire alarm box also does not normally make every automatic sprinkler in a wet pipe system start dumping water. Movies owe quite a few fictional hotel owners new carpeting.

What Should a Fire Alarm Technician Check at a Sprinkler Riser?

When troubleshooting sprinkler monitoring, identify each component before touching wiring or programming.

A useful sequence is:

  1. Identify the sprinkler-system type.
  2. Identify the waterflow alarm device.
  3. Identify each supervised control valve.
  4. Determine what each switch physically monitors.
  5. Identify the associated fire alarm monitor module or circuit.
  6. Verify the point description at the FACU.
  7. Verify whether the point should create alarm, supervisory or trouble.
  8. Functionally test the actual monitored condition using the approved procedure.
Fire Alarm Technician's Field Rule: Never identify a sprinkler input solely by the wires connected to it. Follow the wiring to the physical device and determine what that device actually monitors. The mechanical function tells you what the electrical signal is supposed to mean.

Common Sprinkler Monitoring Mistakes

  • Calling a backflow preventer an OS&Y.
  • Calling every sprinkler valve an OS&Y.
  • Programming waterflow as supervisory.
  • Programming a valve tamper as a fire alarm.
  • Assuming a backflow preventer's primary purpose is preventing false waterflow alarms.
  • Assuming every supervised valve uses the same type of tamper switch.
  • Labeling every sprinkler supervisory point simply "TAMPER."
  • Setting every waterflow retard to 90 seconds.
  • Testing only the electrical contacts instead of the actual monitored condition.
  • Assuming one automatic sprinkler operating causes every sprinkler to discharge.

Wet, Dry and Deluge Systems Use Different Monitoring Arrangements

The equipment discussed in this guide is commonly encountered on wet pipe systems, but technicians should not assume the same waterflow arrangement is used on every sprinkler-system type.

Dry pipe systems commonly add pneumatic-pressure supervision and can use pressure-operated alarm devices associated with the dry pipe valve.

Deluge systems add another layer because detection, releasing circuits, releasing devices and valve operation can all become part of the sequence.

Continue through the sprinkler-system series:

Frequently Asked Questions

Is an OS&Y a backflow preventer?

No. OS&Y stands for Outside Screw and Yoke and describes a type of indicating gate valve. A backflow prevention assembly performs a separate function by protecting the water supply against reverse flow.

What does a sprinkler tamper switch do?

A valve supervisory or tamper switch monitors the position of a sprinkler control valve. Movement from the normal position causes the switch to change state so the fire alarm system can receive a supervisory signal.

Is a sprinkler tamper switch an alarm?

A sprinkler control-valve supervisory switch normally initiates a supervisory signal, not a fire alarm signal.

Is sprinkler waterflow an alarm?

Yes. The required sprinkler waterflow condition is an alarm function.

What is the difference between a waterflow switch and a tamper switch?

A waterflow switch detects sprinkler-system waterflow. A tamper switch monitors the position of a sprinkler control valve.

What does OS&Y stand for?

OS&Y stands for Outside Screw and Yoke. It is a gate-valve configuration with an exposed stem that provides a visible indication of valve position.

Why does a backflow preventer matter on a sprinkler system?

Its purpose is to protect the supplying water system against reverse flow from the fire protection system. It should not be confused with the sprinkler waterflow alarm device or valve supervisory switch.

Can the valves on a backflow preventer be supervised?

Yes. Where required, control valves associated with a backflow assembly can be equipped with listed valve supervisory switches appropriate for the particular valve type.

Related Fire Sprinkler Guides

Studying for the NICET Fire Alarm Systems Exam?

Waterflow alarms, valve supervision, sprinkler interfaces and the difference between alarm and supervisory signals are fundamental concepts for fire alarm technicians.

Fire Alarms Online offers a 550-question NICET Fire Alarm Systems practice collection covering Levels I through IV, along with a free 35-question sample.

NICET Fire Alarm Practice Exams • Levels I–IV

Practice sprinkler monitoring, initiating devices, alarm and supervisory signals, code navigation, testing and troubleshooting.

View NICET Practice Exams →

Reviewing Sprinkler Interfaces in Bluebeam?

Waterflow switches, control-valve tampers, backflow assemblies and monitor modules should be clearly identified when reviewing fire alarm plans and sprinkler interface points.

Bluebeam Toolkit for Fire Alarm Professionals

Built for fire alarm layouts, takeoffs, estimating and faster PDF markup workflows.

View the Bluebeam Toolkit →

Bottom Line

The easiest way to understand sprinkler monitoring is to stop treating every device at the riser as the same thing.

A waterflow switch detects sprinkler-system operation and initiates an alarm. A tamper or valve supervisory switch monitors a sprinkler control valve and initiates a supervisory condition. An OS&Y is a type of indicating gate valve. A backflow preventer protects the supplying water system against reverse flow.

Once those four functions are separated, sprinkler monitoring becomes much easier to design, program, test and troubleshoot.