An elevator shunt trip is used to automatically disconnect elevator power when required by the approved elevator and fire protection design, typically where sprinkler operation could create an unsafe condition for elevator equipment.
The fire alarm system commonly provides the initiating interface for this function through heat detection and listed control equipment.
This guide explains the basic elevator shunt trip wiring sequence, the purpose of the heat detector, fire alarm control relay, shunt-trip disconnect, power monitoring, and how elevator recall differs from elevator power shutdown.
Elevator Shunt Trip Wiring Diagram
The diagram above illustrates a typical concept for interfacing a fire alarm system with an elevator shunt-trip disconnect.
The exact arrangement varies by project. Always use the approved project drawings and equipment-specific wiring diagrams rather than treating a generic diagram as a universal installation detail.
What Is an Elevator Shunt Trip?
An elevator shunt trip is a means of automatically disconnecting electrical power to elevator equipment when required by the elevator/fire protection design.
The objective is not simply to "turn the elevator off."
Where the applicable elevator code requires automatic power shutdown because sprinkler water could create an unsafe elevator condition, the shutdown must occur upon or prior to the application of water.
The fire alarm system commonly interfaces with the electrical disconnect through a control relay or other listed interface equipment.
Elevator Recall and Elevator Shunt Trip Are Different Functions
This distinction is extremely important.
Elevator recall and elevator power shutdown are separate emergency-control functions.
| Function | Typical Purpose |
|---|---|
| Elevator Recall | Causes the elevator system to respond to a fire alarm recall signal and move according to the approved recall sequence. |
| Elevator Shunt Trip | Disconnects applicable elevator power when automatic power shutdown is required. |
A smoke detector used for elevator recall should therefore not be confused with a heat detector used to initiate elevator power shutdown.
Basic Elevator Shunt Trip Sequence
A typical elevator shunt-trip sequence can be understood as:
Heat Detector → Fire Alarm System → Control Relay → Shunt-Trip Disconnect → Elevator Power Removed
The actual system may contain additional monitoring modules, relays, power supplies, disconnects, elevator-controller interfaces, and other components.
Each component serves a specific function and must be coordinated with the approved sequence of operations.
Why Is a Heat Detector Used for Elevator Shunt Trip?
Where automatic elevator power shutdown is required in connection with sprinkler protection, heat detection is commonly used to initiate the shutdown function before sprinkler water is discharged onto elevator equipment.
The purpose is timing.
The shutdown arrangement must coordinate the initiating device and sprinkler so the required power disconnect occurs upon or before water application.
This is different from elevator recall, which is commonly initiated by smoke detection in designated elevator-related locations.
Heat Detector Location Near the Sprinkler
Where heat detection is used to initiate elevator power shutdown, the detector location and temperature characteristics must be coordinated with the sprinkler installation and applicable requirements.
The commonly encountered arrangement places the heat detector within the required proximity of the associated sprinkler so that the detector can respond in time to initiate the shutdown sequence.
Do not simply install one heat detector somewhere in an elevator machine room and assume the requirement has been satisfied. The detector arrangement must correspond with the sprinkler protection and approved design.
Heat Detector Temperature Rating and Sprinkler Temperature
The temperature characteristics of the heat detector and sprinkler are critical.
The goal is for the elevator shutdown sequence to operate before sprinkler discharge when the applicable design requires power removal before water is applied to elevator equipment.
For this reason, the heat detector selection cannot be treated independently from the sprinkler temperature classification and response characteristics.
Fire Alarm Relay for Elevator Shunt Trip
The fire alarm system commonly controls the elevator shunt-trip function through a listed control relay or control module.
When the appropriate heat detector activates, the fire alarm system changes the state of the control output according to the programmed sequence.
That interface then operates the shunt-trip circuit associated with the elevator disconnect.
The exact relay contact configuration, control voltage, wiring method, and fail-safe arrangement depend on the equipment and approved design.
Never assume that normally open or normally closed is universally correct for every shunt-trip installation.
What Does the Shunt-Trip Breaker or Disconnect Do?
A shunt-trip mechanism allows a circuit breaker or disconnecting means to be electrically operated from a remote signal.
In an elevator power-shutdown application, activation of the required interface causes the applicable elevator power to be disconnected.
The fire alarm control equipment is therefore generally providing the control signal. It is not carrying the elevator motor power through the fire alarm relay.
Why Shunt-Trip Control Power Matters
A shunt-trip mechanism needs an available source of control power in order to operate.
That creates an important supervision question:
What happens if the shunt-trip control power is lost before a fire occurs?
If the power necessary to perform the required shutdown is unavailable, the fire alarm system needs to provide the required indication of that impairment where required by the applicable system design and code.
This is why elevator shunt-trip installations commonly include monitoring associated with the availability of the control power.
Monitoring Shunt-Trip Power
A properly designed system should not silently lose the power necessary to perform a required elevator shutdown function.
Depending on the design, the fire alarm system may monitor the availability of the shunt-trip control power through an approved supervisory interface.
If that power becomes unavailable, the fire alarm system can then indicate the abnormal condition rather than leaving a hidden impairment.
The exact monitoring arrangement depends on the disconnect, control-power source, fire alarm equipment, approved plans, and applicable adopted requirements.
What Happens When the Shunt-Trip Heat Detector Activates?
A typical sequence is:
- The elevator-area heat detector reaches its operating point.
- The fire alarm control unit receives the detector input.
- The fire alarm system activates the programmed elevator power-shutdown output.
- The associated fire alarm control relay or module changes state.
- The shunt-trip mechanism operates.
- The applicable elevator power is disconnected.
- The fire alarm system provides the required event indications according to the approved sequence.
The actual project sequence may contain additional operations and must always be verified against the approved input/output matrix.
Should Elevator Recall Happen Before Shunt Trip?
Elevator recall and power shutdown are coordinated functions, but technicians should be careful with the common field explanation that the fire alarm system simply "recalls the elevator first and then waits to shunt it."
The power-shutdown function is governed by the required response to the sprinkler hazard and the approved elevator-system design.
Do not create an arbitrary fire alarm timer intended to delay required elevator power shutdown unless that exact arrangement is permitted by the applicable codes, elevator equipment, and approved design.
The fire alarm system should execute the approved sequence rather than improvising a delay in the field.
Smoke Detector vs. Heat Detector for Elevator Functions
| Device | Common Elevator Function |
|---|---|
| Smoke Detector | Elevator recall and related Phase I emergency operation inputs where required. |
| Heat Detector | Elevator power shutdown where required in coordination with sprinkler protection. |
| Waterflow | Reports sprinkler waterflow but should not automatically be assumed to be the initiating input for the elevator shunt-trip function. |
Does Sprinkler Waterflow Shunt Trip the Elevator?
Do not automatically use the sprinkler waterflow switch as the elevator shunt-trip initiating device simply because the shutdown is associated with sprinkler protection.
The purpose of the elevator power-shutdown arrangement is to disconnect the required power upon or prior to the application of water where the elevator code requires that protection.
Waiting for established sprinkler waterflow can be inconsistent with that objective.
Follow the approved heat-detection and shutdown design for the project.
Elevator Machine Room Shunt Trip
Where sprinklers are installed in an elevator machine room, machinery space, control room, control space, hoistway, or other applicable elevator equipment area, the designer must determine whether elevator power shutdown is required by the adopted elevator code and project conditions.
The answer should not be based simply on the fact that the building has elevators or sprinklers.
Modern elevator and sprinkler requirements contain important exceptions and installation options, so each project needs to be evaluated under its adopted codes and elevator design.
Elevator Pit Sprinklers and Shunt Trip
Elevator pits deserve particular attention because the presence of a sprinkler does not automatically mean every pit requires identical fire alarm shutdown equipment.
The sprinkler arrangement, elevator equipment exposure, applicable elevator-code provisions, and approved design determine the required sequence.
Never copy the machine-room shunt-trip design into the pit without verifying the requirements for that specific elevator installation.
NFPA 72 and Elevator Power Shutdown
NFPA 72 addresses the fire alarm system's role in emergency control function interfaces, including elevator-related functions.
The fire alarm system may be responsible for receiving the appropriate initiating-device input, processing the programmed sequence, operating listed control interfaces, supervising applicable pathways or functions, and annunciating abnormal conditions.
However, NFPA 72 is not the only standard involved.
Elevator shunt trip can involve requirements from:
- NFPA 72, National Fire Alarm and Signaling Code
- The adopted elevator safety code, commonly based on ASME A17.1/CSA B44
- NFPA 13 where sprinkler protection is involved
- NFPA 70 / NEC for electrical installation requirements
- The adopted building and fire codes
- Elevator manufacturer requirements
- Fire alarm equipment listings and instructions
- The Authority Having Jurisdiction
Do Not Treat the Fire Alarm Diagram as the Complete Elevator Design
A fire alarm drawing may show a heat detector, control module, monitor module, and interface to the elevator disconnect.
That does not necessarily document every part of the elevator electrical installation.
Coordination may be required between:
- Fire alarm contractor
- Elevator contractor
- Electrical contractor
- Sprinkler contractor
- Mechanical contractor
- Engineer of record
- Fire alarm designer
- Elevator inspector
- Fire marshal or other AHJ
Elevator shunt trip is one of those deceptively small details on a fire alarm drawing that can involve several trades.
Testing an Elevator Shunt-Trip Interface
Testing should verify the complete approved sequence rather than merely checking whether a relay LED turns on.
Depending on the project and applicable requirements, coordinated testing should verify items such as:
- Correct initiating heat detector
- Correct fire alarm input identification
- Correct programmed output
- Operation of the fire alarm control relay or module
- Operation of the approved elevator power-shutdown interface
- Required monitoring of control power
- Correct annunciation at the fire alarm control unit
- Restoration of the system after testing
- Coordination with elevator recall and other elevator emergency functions
Common Elevator Shunt Trip Wiring Mistakes
- Confusing recall with shunt trip. They are separate elevator emergency functions.
- Using the wrong initiating device. Smoke detection and heat detection commonly perform different elevator functions.
- Using waterflow as the automatic shutdown trigger without verifying the design.
- Failing to coordinate the heat detector with the sprinkler installation.
- Ignoring loss of shunt-trip control power.
- Using an arbitrary software timer to delay shutdown.
- Assuming every elevator pit or machine room has the same requirements.
- Using a generic wiring diagram instead of the approved project documents.
- Failing to coordinate fire alarm, elevator, electrical and sprinkler trades.
- Testing the fire alarm relay but not the complete integrated function.
Elevator Shunt Trip Quick Reference
| Primary Purpose | Automatic elevator power shutdown where required |
| Typical Initiating Device | Heat detector associated with applicable sprinkler protection |
| Fire Alarm Output | Listed control relay/module or other approved interface |
| Controlled Equipment | Approved elevator shunt-trip disconnecting means |
| Separate From | Elevator recall |
| Important Coordination | Elevator, fire alarm, sprinkler and electrical systems |
Frequently Asked Questions
What is an elevator shunt trip?
An elevator shunt trip is an automatic means of disconnecting applicable elevator electrical power when required by the approved elevator and fire-protection design.
What activates an elevator shunt trip?
Where power shutdown is required in coordination with sprinkler protection, heat detection is commonly used to initiate the fire alarm control sequence that operates the approved shunt-trip interface.
Does a smoke detector shunt trip an elevator?
Smoke detectors are commonly associated with elevator recall functions rather than the sprinkler-related power-shutdown function. The exact operation must follow the approved elevator and fire alarm sequence.
Does a sprinkler waterflow switch shunt trip an elevator?
Waterflow should not automatically be assumed to be the correct initiating input. Where shutdown is required upon or prior to sprinkler water application, the approved design commonly uses heat detection coordinated with the sprinkler rather than waiting for established waterflow.
Is elevator recall the same as elevator shunt trip?
No. Recall commands the elevator system to perform its approved emergency recall operation. Shunt trip disconnects applicable elevator power when power shutdown is required.
Does every elevator require shunt trip?
No. Whether automatic power shutdown is required depends on the elevator equipment, sprinkler protection, adopted elevator code, building conditions, and approved design.
Does every sprinkler in an elevator area require a heat detector?
Not automatically. The required detection and shutdown arrangement depends on whether automatic elevator power shutdown is required for that sprinkler/elevator condition under the applicable codes and approved design.
Why is shunt-trip power monitored?
If electrical power necessary to operate a required shunt-trip function is lost, the shutdown function can become impaired. Where required, monitoring allows that abnormal condition to be reported rather than remaining hidden.
Can the fire alarm relay directly switch elevator motor power?
Ordinary fire alarm control contacts are generally used to interface with the approved elevator power-shutdown equipment, not to carry elevator motor power. Always follow the equipment listings and approved electrical design.
Related Elevator Fire Alarm Guides
- Elevator Shunt Trip Requirements & Codes
- Elevator Recall and Shunt Trip Basics
- Heat Detectors and Elevator Pits
- Elevator Recall Programming and Operation
Final Thoughts
The key to understanding elevator shunt-trip wiring is recognizing that the fire alarm system is only one part of an integrated elevator power-shutdown function.
The heat detector provides the initiating condition. The fire alarm system processes that condition and operates the approved control interface. The shunt-trip equipment disconnects the required elevator power.
Meanwhile, elevator recall remains a separate emergency function with its own initiating devices and sequence.
For a successful installation, the fire alarm, elevator, sprinkler and electrical designs all have to agree on the same sequence of operation.
No comments:
Post a Comment