Showing posts with label elevator recall. Show all posts
Showing posts with label elevator recall. Show all posts

Wednesday, April 22, 2026

Elevator Recall & Shunt Trip Explained (2024 Code + Real-World Design Guide)

Elevator Recall & Shunt Trip Explained (2024 Code + Wiring + Sequence of Operation)

Elevator Recall & Shunt Trip Explained (2024 Code + Real-World Design Guide)

Fire Alarm Interface • Code Requirements • Wiring • Point Lists • Sequence of Operation

Elevator recall and shunt trip are among the most misunderstood fire alarm interfaces in commercial construction. When these functions are designed incorrectly, the result can be failed inspections, confusion during acceptance testing, unsafe conditions, and expensive rework between trades.

This guide breaks down how elevator recall and shunt trip actually work in the real world using IBC 2024, IFC 2024, NFPA 72 (2022), and ASME A17.1.

👉 If you have not already, review our complete fire alarm requirements by occupancy guide to understand when these systems are triggered in the first place.

💡 Real-World Design Tip:

Coordinating elevator recall devices, machine room detection, shunt trip circuits, and trade responsibilities across construction drawings can get complicated fast.

👉 Use our Bluebeam Fire Alarm Toolkit to speed up layouts, takeoffs, and coordination

Built specifically for fire alarm and low voltage professionals working real-world projects.

🚨 What Is Elevator Recall?

Elevator recall, commonly referred to as Phase I Emergency Recall Operation, is intended to automatically remove elevators from normal service and return them to a designated landing when a fire condition is detected. This helps keep occupants from unknowingly traveling to a fire-affected floor and gives responding personnel a more controlled condition.

  • Primary Recall Floor: The normal designated landing floor.
  • Alternate Recall Floor: The floor used when the primary recall floor is compromised by smoke detection.

Typical code references associated with recall include:

  • IBC 3003.1
  • IFC 607.3.2
  • ASME A17.1 Section 2.27.3
  • NFPA 72 (2022) Section 21.3

In practice, the fire alarm system does not “run the elevator.” It provides the proper initiating signals so the elevator controller performs the recall sequence it has been programmed to execute.

👉 For a broader code relationship breakdown, see our NFPA 72, IFC, and IBC code adoption guide.


⚡ What Is Shunt Trip?

Shunt trip is a power disconnect function associated with elevators where elevator power is removed before sprinkler discharge can create an electrical hazard. This is one of the most misunderstood areas in the field because many people casually mix recall and shunt trip together, even though they are not the same function and are not triggered by the same type of device.

  • Recall is generally associated with smoke detection.
  • Shunt trip is generally associated with heat detection in sprinklered elevator spaces.

Typical references associated with shunt trip include:

  • NEC 620.51(B)
  • NFPA 72 (2022) Section 21.4
  • ASME A17.1 Section 2.8.3.3

Real-world confusion usually happens when a project team assumes the smoke detector in a machine room should also trip the breaker. That is not the typical design intent. The smoke detector is generally part of recall logic. The heat detector is generally what initiates the shunt trip function where required.


🔥 Detection Requirements: What Goes Where

Smoke Detection for Recall

  • Elevator lobby smoke detectors at required floors
  • Machine room smoke detector where applicable
  • Control room or control space smoke detector where applicable

Heat Detection for Shunt Trip

  • Heat detectors installed in proximity to sprinkler heads serving elevator spaces
  • Top of hoistway heat detection where sprinklers exist there
  • Machine room heat detection where sprinklers are present

Simple field rule:
Smoke = Recall
Heat = Power Shutdown

That single distinction prevents a surprising amount of bad design.


🧠 Elevator Recall Logic in Real Life

In the field, the exact recall response depends on where the alarm originates:

  • If smoke is detected at the primary recall floor lobby, the elevator is usually recalled to the alternate recall floor.
  • If smoke is detected at another floor lobby, the elevator is usually recalled to the primary recall floor.
  • If smoke is detected in the machine room or control room, the elevator is generally recalled according to programmed logic, often to the primary floor unless site-specific design says otherwise.
  • If the required heat detector activates, the shunt trip signal can disconnect elevator power.

These rules sound simple on paper, but on live jobs they break down fast when the sequence of operation is vague, floor designations are not clearly coordinated, or the elevator vendor and fire alarm contractor are not aligned before programming begins.


📊 Elevator Recall & Shunt Trip Diagram

🔥 Fire Event Initiated
Smoke Detector
Elevator Lobby / Machine Room
⬇️
Fire Alarm Recall Relay
⬇️
Elevator Controller
Returns car to designated recall floor
Heat Detector
Near Sprinkler in Elevator Space
⬇️
Shunt Trip Relay
⬇️
Electrical Shunt Trip Breaker
Removes elevator power

Key Logic: Smoke = Recall   |   Heat = Power Shutdown


🔧 Real-World Coordination: Where Jobs Actually Fail

  • Fire alarm contractor installs initiating devices and interface relays
  • Electrical contractor typically handles shunt trip breaker wiring and power pathway
  • Elevator contractor programs or confirms recall response through the elevator controller
  • Sprinkler contractor determines whether sprinklers are present in the machine room, hoistway, or pit, which directly affects whether shunt trip may be needed

The reality: most failed inspections do not come from someone never reading the code. They come from poor coordination, vague scope language, incomplete shop drawings, or the old classic: “I thought the other trade was doing that.”

Another common issue is late-stage discovery that the electrical contractor never received clear direction on the shunt trip interconnection, while the elevator contractor assumed the fire alarm contractor would handle all interface programming. By the time everyone realizes the gap, the inspection date is already breathing down the neck of the project.

👉 Also see our related article on Fire Service Access Elevators Explained.


🔥 FIRE ALARMS ONLINE • FIELD TECH TOOL
AI-POWERED POCKET RECORDER
Stop Trying to Remember Everything
From the Job Walk
Capture job walks, coordination meetings, troubleshooting conversations and field notes with Pocket. Record the conversation, then turn it into searchable transcripts, summaries and action items you can reference later.
✓ Job Walks    ✓ Coordination Meetings    ✓ Service Calls
✓ Project Notes    ✓ Troubleshooting    ✓ Action Items
See Pocket & Current Offer →
Affiliate disclosure: Fire Alarms Online may earn a commission if you purchase through this link, at no additional cost to you.

⚠️ Common Design and Installation Mistakes

  • Using a smoke detector to initiate shunt trip instead of the required heat detector arrangement
  • Missing heat detection near sprinkler heads serving elevator spaces
  • Failing to clearly identify the primary and alternate recall floors
  • Submitting a vague or incomplete sequence of operation
  • Not coordinating responsibilities between fire alarm, electrical, sprinkler, and elevator trades
  • Assuming every elevator condition is identical without verifying project-specific design and AHJ expectations
🔥 NICET Exam Insight:

Elevator recall logic, detector placement, interface relays, and sequence of operation are heavily tested topics because they combine code knowledge with practical system behavior.

👉 Practice real NICET-style fire alarm questions here

Designed to match real exam difficulty and code-based thinking.


📋 Typical Fire Alarm Point List for Elevator Interface

Point Type Description Function
Input Elevator Lobby Smoke Detector Initiates elevator recall based on floor location
Input Machine Room Smoke Detector Initiates elevator recall
Input Control Room / Control Space Smoke Detector Initiates elevator recall where applicable
Input Heat Detector at Sprinklered Elevator Space Triggers shunt trip function where required
Output Elevator Recall Relay Sends recall signal to elevator controller
Output Shunt Trip Relay Initiates breaker trip through electrical interface
Supervisory / Monitor Elevator Power Status Monitor Confirms elevator power condition when provided in design
Trouble / Monitor Interface Relay Fault or Wiring Fault Annunciates abnormal condition or loss of control path

Note: Exact point naming, labeling, and annunciation method vary by fire alarm manufacturer, project specifications, and AHJ preferences.


🧾 Sequence of Operation Table (AHJ-Ready Format)

Event Fire Alarm System Action Elevator / Building Response
Smoke detector activation at primary recall floor elevator lobby Fire alarm panel activates recall relay for alternate recall response Elevator returns to alternate recall floor and is removed from normal service
Smoke detector activation at elevator lobby on any floor other than primary recall floor Fire alarm panel activates recall relay for primary recall response Elevator returns to primary recall floor and is removed from normal service
Machine room or control room smoke detector activation Fire alarm panel activates recall relay in accordance with approved sequence Elevator returns to designated recall floor per elevator programming and approved design
Heat detector activation associated with sprinkler-protected elevator space Fire alarm panel activates shunt trip relay Electrical shunt trip breaker disconnects elevator power
System reset after alarm condition is cleared and all interfacing systems are restored Fire alarm panel resets initiating devices and restores control relays to normal Elevator may return to normal service subject to elevator controller logic and authorized reset procedures

🧩 Advanced Design Considerations

  • Mission-critical facilities may use air sampling detection for early warning in elevator support spaces, depending on design goals and approvals.
  • Linear heat detection may be considered in some hoistway applications depending on project conditions and engineering approach.
  • Survivability requirements may affect associated pathways, especially where emergency communication or other protected functions are involved.
  • AHJ interpretation matters. Some jurisdictions apply stricter coordination expectations, submittal requirements, or local amendments.

This is why experienced designers do not rely only on generic one-line notes. They make the sequence explicit, show interface intent clearly on the drawings, and coordinate early with elevator and electrical trades before installation starts.


📈 Pro Insight

Elevator recall systems rarely fail because the code is impossible. They fail because the project team leaves too much unsaid.

If your sequence of operation is vague, your point list is incomplete, and your trade responsibilities are fuzzy, inspection day turns into a demolition derby in slow motion.

On the other hand, when the initiating devices, relay outputs, floor logic, breaker interface, and sequence are all clearly documented, the system reads like a good set of plans should: boring, predictable, and correct.

Master Fire Alarm Design and Pass NICET Faster

Bluebeam Fire Alarm Toolkit NICET Practice Exams

Built by real fire alarm professionals. Used on real projects. Designed to help you move faster and pass with confidence.

Related Fire Alarm Resources

Monday, February 19, 2018

NFPA 72 2016 Chapter 21 Changes

NFPA 72 2016 Chapter 21 - Emergency Control Function Interfaces


The following information contains the changes, updates and additions to Emergency Control Function Interfaces found in Chapter 21 of the NFPA 72 2016 edition.  Remember if you see a * make sure to consult the Annex A for additional information.

All information highlighted in this light blue color is NEW to the 2016 edition of NFPA 72.

  • 21.1.1 The Requirements of Chapters 7, 10, 17, 18, 23, 24, and 26 shall apply, unless otherwise noted in this chapter.
  • 21.1.3 The requirements of this chapter shall not apply to Chapter 29 unless otherwise stated.
  • 21.2.6 The installation wiring between the fire alarm control unit and the emergency control function interface device shall be Class A, Class B, Class D, Class N, or Class X in accordance with NFPA 72 Chapter 12 Circuit Pathways.  
The following pertains to Elevator Phase 1 Recall

  • 21.3* Elevator Phase 1 Emergency Recall Operation
  • 21.3.1 All fire alarms initiating devices used to initiate elevator phase 1 emergency recall operation shall be connected to the required building fire alarm system.
  • 21.3.2* In facilities without a required building fire alarm system, fire alarm initiating devices used to initiate elevator phase 1 emergency recall operation shall be connected to either a non-required building fire alarm system or a dedicated function fire alarm control unit that shall be designated as "elevator recall control and supervisory control unit," permanently identified on the dedicated function fire alarm control unit and on the record drawings. 
  •  
The following is a California State Amendment.

  • 21.3.6 Smoke detectors shall not be installed in un-sprinklered elevator hoistways unless they are installed to activate the elevator hoistway smoke relief equipment or where required by Chapter 30 by the California Building Code (CBC).
CBC: 3005.4.1 Automatic sprinkler system.  Automatic sprinklers shall not be required to be installed in the elevator hoistway, elevator machine room, elevator machinery space, elevator control space, or elevator control room where the following are met.  NOTE:  All 6 of the following conditions must be met.
  1. Approved smoke detectors shall be installed in the elevator hoistway, elevator machine room, elevator machinery spaces, elevator control spaces, or elevator control rooms and connected to the building fire alarm system in accordance with Section 907.
  2. Activation of any smoke detector located in the elevator hoistway, elevator machine room, elevator machinery spaces, elevator control spaces, or elevator control room shall cause the actuation of the building fire alarm notification appliances in accordance with section 907.
  3. Activation of any smoke detector located in the elevator hoistway, elevator machine room, elevator machinery spaces, elevator control spaces, or elevator control room shall cause all elevators having equipment located in that elevator hoistway, elevator machine room, elevator machinery spaces, elevator control spaces, or elevator control room to recall nonstop to the appropriate floor in accordance with CCR Titile 8, Division 1, Chapter 4, Subchapter 6, Elevator Safety Order.
  4. The elevator machine room, elevator machinery spaces, elevator control spaces, or elevator control room shall be enclosed with fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed with Section 712, or both.  The fire-resistance rating shall not be less than the required rating of the hoistway enclosure served by the machinery.  Openings in the fire barriers shall be protected with assemblies having a fire protection rating not less than that required for the hoistway enclosure doors.  The exception to Section 3005.4 shall not apply.
  5. The building fire alarm system shall be monitored by an approved supervising station in accordance with Section 907.
  6. An approved sign shall be permanently displayed in the elevator machine room, elevator machinery space, elevator control space, or elevator control room in a conspicuous location with a minimum of 1 1/2" letters on a contrasting background stating, NO COMBUSTIBLE STORAGE PERMITTED IN THIS ROOM By Order of the Fire Marshal (or name of fire authority).
  • 21.3.11 Actuation from the elevator hoistway, elevator machine room, elevator machinery space, elevator control space or elevator control room smoke detectors or other automatic fire detection as permitted by 21.3.9 shall cause separate and distinct visible annunciation at the building fire alarm control unit or at the fire alarm control unit described in 21.3.2.  Removed the following portion: and at required annunciators to alert firefighters and other emergency personnel that the elevators are no longer safe to use. 
  • 21.3.13 Separate outputs from the building fire alarm control unit or the fire alarm control unit or the fire alarm control unit described in 21.3.2 to the elevator controller(s) shall be provided to implement elevator Phase 1 Emergency Recall Operation in accordance with Section 2.27 of ANSI/ASME A17.1/CSA B44, Safety Code for Elevators and Escalators, as required in 21.3.13 through 21.3.13.3.

Chapter 21 Changes - Specific to Fire Service Access Elevators

  • 21.5 Fire Service Access Elevators.  Where one or more elevators are specifically designated and marked as fire service access elevators, 21.5.1 and 21.5.2 shall apply.
  • 21.5.1* Status of elevator(s), including location within the hoistway, direction of travel, and whether the elevator(s) are occupied, shall be permitted to be displayed on a building fire alarm system annunciator located at the fire command center.
  • 21.5.2 Temperature and presence of smoke in associated lobbies, machine rooms, control rooms, machinery spaces, or control spaces shall be continuously monitored and displayed on a building fire alarm system annunciator located in the fire command center.  

  • The conditions in 21.5.1 and 21.5.2 shall be permitted to be displayed on a standard emergency services interface complying with Section 18.11.

Chapter 21 Changes - Specific to Door and Shutter Release

  • 21.8.3 All door and shutter hold-open release and integral door and shutter release and closure devices used for release service shall be monitored for integrity in accordance with section 12.6.  Exception: Pathways installed as Class D circuits in accordance with 12.3.4.

NFPA 72 2016 Chapter 23 - Protected Premise Fire Alarm Systems



NFPA 72 2016 Chapter 18 - Notification Appliances


Friday, August 25, 2017

Occupant Evacuation Elevator Code Explained

Occupant Evacuation Elevator Code Requirements Explained

Occupant evacuation elevators (OEEs) are one of the most specialized elevator applications in the building and fire codes. If you work in fire alarm design, inspection, plan review, elevator integration, or NICET preparation, understanding how these systems are permitted, monitored, powered, and protected is critical.

This guide breaks down the code requirements for occupant evacuation elevators, including IBC Section 3008, NFPA 72 Section 21.6, emergency voice/alarm communication, elevator lobby requirements, two-way communication systems, standby power, wiring protection, and more.

NICET Prep Note: Occupant evacuation elevators are a classic crossover topic. They pull together IBC, NFPA 72, emergency controls, two-way communication, voice evacuation, fire command center functions, and survivability requirements. This is exactly the kind of material that separates surface-level memorization from real exam and field competence.

Quick Answers: Featured Snippet Q&A

What is an occupant evacuation elevator?

An occupant evacuation elevator is a passenger elevator designed and protected so it can be used for occupant self-evacuation during a fire emergency when installed in accordance with IBC Section 3008.

What code allows occupant evacuation elevators?

IBC Section 403.6.2 permits passenger elevators for public use to be used for occupant self-evacuation when installed in accordance with IBC Section 3008.

Do occupant evacuation elevators require two-way communication?

Yes. A two-way communication system is required at the lobby of each level served by an occupant evacuation elevator, with communication directed to the fire command center or another approved location.

Can occupant evacuation elevators have shunt trip?

No. A means for elevator shutdown, or shunt trip, in accordance with IBC Section 3005.5, shall not be installed on elevator controllers used for occupant evacuation elevators.

Table of Contents


What Is an Occupant Evacuation Elevator?

Much like Fire Service Access Elevators, Occupant Evacuation Elevators are in fact elevators that have strict rules and regulations put in place to allow special uses above standard elevators. An Occupant Evacuation Elevator can be used for self-evacuation during a fire emergency pending the elevator system meets the requirements set forth in the International Building Code.

Occupants running toward an occupant evacuation elevator during a fire emergency
Occupants Running to the Elevator During Fire
Related Reading: If you work with specialty elevator interfaces, also read Fire Service Access Elevators Explained.

What Code Requires or Allows the Use of Occupant Evacuation Elevators?

The requirement to provide occupant evacuation elevators can be found in the IBC or International Building Code 2021 Section 403.5.2 within the exception.

“For buildings other than Group R-2 that are more than 420 feet in building height, one additional interior stairway meeting the requirements of Sections 1011 and 1023 shall be provided in addition to the minimum number of exits required by Section 1006.3. The total width of any combination of remaining interior exit stairways with one interior exit stairway removed shall be not less than the total width required by Section 1005.1. Scissor stairways shall not be considered the additional interior exit stairway required by this section.”

Exception: An additional interior exit stairway shall NOT be required to be installed in buildings having elevators used for occupant self-evacuation in accordance with Section 3008.

Furthermore, the International Building Code 2021 Section 403.6.2 Occupant Evacuation Elevators states, “Where installed in accordance with Section 3008, passenger elevators for public use shall be permitted to be used for occupant self-evacuation.”

The requirements on how an occupant evacuation elevator is to be installed can be found in the IBC or International Building Code 2021 Section 3008.

Other references include:

NICET Practice Exam Shoutout: If you are studying emergency controls, elevator recall, shunt trip, two-way communication, smoke control interfaces, or voice evacuation, make sure you are training with realistic NICET practice exam questions, not just flash-card definitions.

Requirements for Occupant Evacuation Elevators

When an occupant evacuation elevator is to be used for occupant self-evacuation during a fire, all passenger elevators for public use shall comply with Sections 3008.1 through 3008.10. If any additional elevators are used for self-evacuation, those elevators shall comply with these sections as well.

In buildings that utilize occupant evacuation elevators, a fire safety and evacuation plan shall be approved and in place. Requirements for a fire safety and evacuation plan can be found in the International Fire Code (IFC) 2021 Section 404, Emergency Planning and Preparedness.

The operation of self-evacuating occupant evacuation elevators shall comply with the requirements in ASME A17.1, CSA B44 and the above mentioned Fire Safety and Evacuation Plan.

Emergency Voice Communication System

The building shall be equipped with an emergency voice/alarm communication system that is accessible to the fire department. System shall be installed in accordance to Section 907.5.2.2. Each elevator lobby used for occupant evacuation shall be equipped with at least one audible and one visual notification appliance.

Not that it would be common, but if you had to install voice evacuation just for the occupant evacuation elevators, it is allowed to mix audible evacuation tones. Find out more in this article, Mixing Speakers and Horns for Fire Alarm.

Recommended Read: If you are sorting out selective voice coverage, mixed appliance strategies, or emergency control interfaces, this article is a strong companion piece: Mixing Speakers and Horns for Fire Alarm.

Automatic Sprinkler Requirements

The building with occupant evacuation elevators shall be protected throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. The automatic sprinkler system shall be provided with a supervised tamper switch and alarm initiating water flow switch on every floor of the building.

Note, the following areas are prohibited from having automatic fire sprinkler protection:

  • Elevator Machine Rooms
  • Elevator Machinery Spaces
  • Elevator Control Rooms
  • Elevator Control Spaces
  • Elevator Hoistways serving the Occupant Evacuation Elevator

The lobby on each floor served by the fire service access elevator shall have an approved method of preventing water from the operation of the automatic sprinkler system from infiltrating the FSAE hoistway.

Lastly, a means for elevator shutdown or Shunt Trip in accordance with IBC Section 3005.5 shall NOT be installed on elevator controllers used for occupant evacuation elevators.

Watch-Out Item: Designers regularly mix up standard elevator concepts with occupant evacuation elevator requirements. Do not blindly apply shunt trip logic where the code specifically prohibits it.

Occupant Evacuation Elevator Hoistway Enclosure

The shaft or hoistway enclosure shall comply with IBC Section 713, Shaft Enclosures, as well as Section 403.2.3.4, Wall Assembly, and the applicable provisions for other wall assemblies.

Occupant Evacuation Elevator Cab Dimensions

Although this is not a direct requirement for occupant evacuation elevators or fire service access elevators, rather buildings that are four stories or more, it still applies and is worth mentioning.

IBC Section 3002.4, Elevator Car to Accommodate Ambulance Stretcher, gives us the dimensions required for the cab. The elevator car shall be of such a size and arrangement to accommodate an ambulance stretcher 24 inches by 84 inches with not less than 5 inch radius corners, in the horizontal, open position.

ADA Table 407.4.1 breaks this down a little further and gives us the following: the cab shall be provided with a minimum clear distance between walls and door excluding return panels not less than 80 inches by 54 inches and a minimum distance from wall to return panel not less than 51 inches with a 42 inch side slide door.

Fire service access elevator and occupant evacuation elevator car dimensions diagram
Fire Service Access Elevator and Occupant Evacuation Elevator Car Dimensions

Stretcher inside fire service access elevator cab
Stretcher inside FASE Elevator Cab

Occupant Evacuation Elevator Lobby Requirements

The Occupant Evacuation Elevator lobby shall be enclosed with a smoke barrier having a fire-resistance rating of not less than 1 hour. The occupant evacuation elevator lobby doorways shall comply with Section 3008.6.3.

NOTE: Just like Fire Service Access Elevators, enclosed occupant evacuation elevator lobbies are NOT required at the levels of exit discharge.

Lobby Sizing

Keep in mind the following for occupant evacuation elevator lobby sizing requirements:

  1. The occupant evacuation elevator lobby shall accommodate 3 square feet per person, not less than 25 percent of the occupant load of the floor area served by the lobby.
  2. Occupant evacuation elevator lobbies shall be able to house one wheelchair with a space of 30 inches by 48 inches for every 50 persons within the area the lobby serves.

There is an exception to these 2 rules. The size of an elevator lobby that serves multiple banks of elevators shall have the minimum area approved on an individual basis. This sizing shall be consistent with the building's fire safety and evacuation plan.

Lobby Doors

The occupant evacuation elevator lobby doors shall be provided with a 3/4 hour fire door assembly complying with Section 716.5. Doors shall comply with the smoke and draft control assembly requirements of Section 716.5.3.1 and UL 1784 test conducted WITHOUT the artificial bottom seal.

There shall also be a fire protection rated glazed vision window within the occupant evacuation elevator lobby doors.

No different from standard elevators or fire service access elevators, the lobby doors of occupant evacuation elevator lobbies shall close upon receipt of the fire alarm system serving the building.

The self closing mechanism shall close the door from a fully open position (90 degrees) to 12 degrees from the latch at a minimum of 5 seconds. This ensures the doors do not close too quickly. This information can be located in ANSI 117.1 2009 Section 404.2.7.1.

NICET Practice Exam Shoutout: Lobby smoke barriers, rated doors, vision panels, alarm-controlled door behavior, and code exceptions at the level of exit discharge are exactly the kind of details that show up in stronger NICET study material.

How Are Occupant Evacuation Elevators Designated or Noticed?

On all floors served by the occupant evacuation elevator, there shall be an approved sign posted adjacent to each call station. We suggest consulting with your local AHJ if they have a standard on this signage.

Occupant Evacuation Elevator System Monitoring

The occupant evacuation elevator shall be continuously monitored at the fire command center (FCC) or a central control point approved by the AHJ. The following information shall be displayed or available:

  1. The location of each elevator car
  2. The travel direction of each elevator car
  3. If the elevator car is occupied or not
  4. Status of normal power conditions to the elevator equipment, machinery, electrical apparatus cooling equipment, elevator machine room, control room and control space ventilation and cooling equipment
  5. Status of standby or emergency power conditions to the elevator equipment, machinery, electrical apparatus cooling equipment, elevator machine room, control room and control space ventilation and cooling equipment
  6. Activation of any fire alarm initiating device in any elevator lobby, elevator machine room, machine space containing a motor controller or electric driving machine, control space, control room or elevator hoistway

Elevator Landing Two-Way Communication System

You are required to provide a two-way communication system at the lobby of each level served by an occupant evacuation elevator. The two-way communication call stations shall initiate communication to the building's fire command center or an alternate location approved by the AHJ. Note the two-way communication system shall be installed in accordance with Sections 1009.8.1 and 1009.8.2.

SPACE AGE ELECTRONICS SHIELD 30 TWO-WAY COMMUNICATION SYSTEM
Product Spotlight: If you are pricing, designing, or comparing compliant communication options for elevator lobbies and accessible egress applications, the Space Age Electronics Shield 30 is worth reviewing as part of your code-compliance toolbox.

Helpful companion article: Two-Way Communication Code Requirements

Electrical Power

The following features serving each occupant evacuation elevator shall be provided with both normal power as well as Type 60/Class 2/Level 1 standby power:

  1. Elevator equipment
  2. Elevator hoistway lighting
  3. Ventilation for elevator machine rooms, elevator control rooms, machine and control spaces
  4. Elevator cab lighting

Here is the big one to watch out for.

Protection of Wiring and Cables for Occupant Evacuation Elevators

Wires and cables located outside of the fire service access elevator lobby and machine room that are provided for the fire-detection system shall be protected by construction having a fire-resistance rating of not less than 2 hours, shall be circuit integrity (CI) cable with a rating of not less than 2 hours, or shall be protected by a listed electrical protective system having a rating of not less than 2 hours.

Product / Design Callout: If you are engineering or estimating survivability requirements, make sure your team evaluates 2-hour CI cable, listed protective systems, and routing strategies early. This is one of those details that can quietly punch a hole through a submittal if missed.
NICET Practice Exam Shoutout: Circuit survivability, elevator interfaces, fire alarm monitoring, and required power sources are all fair game in advanced NICET fire alarm exam prep. The more realistic the questions, the better your retention when the pressure is on.

Hazardous Material

The building shall not contain any hazardous material areas exceeding the maximum allowable quantities per control area as noted in Section 414.2.

All code references for this article are found in the 2021 Edition of the International Building Code. Always verify adopted local code editions, state amendments, and AHJ interpretations before final design or installation.


Frequently Asked Questions About Occupant Evacuation Elevators

What is the difference between a fire service access elevator and an occupant evacuation elevator?

A fire service access elevator is intended to support firefighter operations, while an occupant evacuation elevator is designed and protected for occupant self-evacuation during a fire emergency when permitted by code.

Are enclosed lobbies required at every floor?

No. Just like fire service access elevators, enclosed occupant evacuation elevator lobbies are not required at the level of exit discharge.

Is a two-way communication system required at each elevator landing?

Yes. A two-way communication system is required at the lobby of each level served by an occupant evacuation elevator, with communication routed to the fire command center or another approved location.

Can automatic sprinklers be installed in the hoistway or machine spaces?

The article notes that elevator machine rooms, machinery spaces, control rooms, control spaces, and hoistways serving the occupant evacuation elevator are prohibited from having automatic sprinkler protection.

Does an occupant evacuation elevator require standby power?

Yes. Elevator equipment, hoistway lighting, ventilation for related spaces, and cab lighting are required to be provided with both normal power and Type 60/Class 2/Level 1 standby power.

Want More NICET and Fire Alarm Code Content?

If you found this guide useful, check out more Fire Alarms Online resources covering elevator recall, shunt trip, two-way communication, voice evacuation, and NICET practice exam prep.

The goal is simple: help fire alarm professionals design smarter, pass faster, and avoid expensive code misses in the field.

Friday, August 4, 2017

Fire Service Access Elevators Explained

What are Fire Service Access Elevators (FSAE)


Fire Service Access Elevators or F.S.A.E. for short, are designed with strict and rigorous standards to allow firemen and first responders to utilize the elevator for the purpose of quickly accessing floors as well as evacuating occupants in the event of an emergency.  This is a huge step for first responders as time is extremely crucial when addressing buildings of this size.

Another special condition for elevators is known as Occupant Evacuation Elevators.  These are self-evacuation elevators with special requirements much like FSAEs.

Fire Service Access Elevators
Fire Service Access Elevators

What Code Requires the Use of Fire Service Access Elevators?


Did you know the 2021 International Fire Code now requires 120 VAC single and multiple station smoke alarms to produce a 520 Hz low frequency audible tone? 

The requirement to provide fire service access elevators can be found in the IBC or International Building Code 2021 section 403.6.1

"In buildings with an occupied floor more than 120 feet above the lowest level of fire department vehicle access, no fewer than two fire service access elevators, or all elevators, whichever is less, shall be provided in accordance with section 3007.  Each fire service access elevator shall have a capacity not less than 3500 pounds."

The requirements on how a fire service access elevator is to be installed can be found in the IBC or International Building Code 2021 section 3007.

Other references include:

Requirements of Fire Service Access Elevators


When a fire service access elevator is required by the IBC section 403.6.1, every floor within the building shall be served and comply with sections 3007.1 through 3007.9

Automatic Sprinkler Requirements:


The building with FSAE shall be protected throughout with an approved automatic sprinkler system in accordance with section 903.3.1.1.  The automatic sprinkler system shall be provided with a supervised tamper switch and alarm initiating water flow switch on every floor of the building.  Note, the following areas are prohibited from having automatic fire sprinkler protection:

  • Elevator Machine Rooms  
  • Elevator Machinery Spaces
  • Elevator Control Rooms
  • Elevator Control Spaces
  • Elevator Hoistways of the Fire Service Access Elevator

The lobby on each floor served by the fire service access elevator shall have an approved method of preventing water from the operation of the automatic sprinkler system from infiltrating the FSAE hoistway.

Lastly, a means for elevator shutdown or Shunt Trip in accordance with IBC section 3005.5 shall NOT be installed on elevator controllers used for fire service access elevators.

Fire Service Access Elevator Hoistway Enclosure

fire service access elevator hoistway

The shaft or hoistway enclosure shall comply with IBC section 713 "Shaft Enclosures" as well as section 403.2.3.1 "Wall Assembly" and sections 403.2.3.4 "Other Wall Assemblies".

Another important aspect to keep in mind is the hoistway lighting for the FSAE shaft.  When the Fire Service Access operation is active, the entire height of the hoistway shall be illuminated at NOT less than 1 footcandle (11 lux).  This measurement is to be taken from the top of each fire service access elevator cab.  

**The fire service access elevator status panel (located in the FCC room) shall have a switch to manually operate this lighting feature.    

Fire Service Access Elevator Cab Dimensions


Although this is not a direct requirement for FSAE rather buildings that are four stories or more, it still applies and is worth mentioning.  IBC section 3002.4 "Elevator Car to Accommodate Ambulance Stretcher" gives us the dimensions required for the cab.  "The elevator car shall be of such a size and arrangement to accommodate an ambulance stretcher 24 inches by 84 inches with not less than 5 inch radius corners, in the horizontal, open position.  ADA Table 407.4.1 breaks this down a little further and gives us the following:  The cab shall be provided with a minimum clear distance between walls and door excluding return panels not less than 80 inches by 54 inches and a minimum distance from wall to return panel not less than 51 inches with a 42 inch side slide door.

Fire Service Access Elevator Car Dimensions
Fire Service Access Elevator Car Dimensions

FSAE Lobby Requirements


Egress through the fire service access elevator lobby is permitted in accordance with IBC section 1016.2 "Egress Through Intervening Spaces" item #1.  The exception to this rule is if the FSAE lobby has two entrances onto the floor, the second entrance shall be permitted to open into an elevator lobby in accordance with IBC section 3006.3 "Hoistway Opening Protection".

The fire service access elevator lobby shall have direct access to to an enclosed interior exit stairway or ramp.  The interior exit stairway or ramp can be in a protected pathway that has a level of protection not less than the FSAE lobby.  The path of travel and FSAE lobby shall be separated via an opening protected by a smoke and draft control assembly in accordance with IBC section 716.5.3 "Door Assemblies in Corridors and Smoke Barriers".  

The FSAE lobby enclosure shall have smoke barrier having a fire-resistance rating of not less than 1 hour.  The FSAE lobby doors shall be 3/4 hour fire door assemblies in accordance with IBC section 716.5 "Fire Door and Shutter Assemblies".  This rule does NOT apply to the hoistway doors, elevator control room doors or elevator control space doors.  Fire Service Access Elevators (FSAE) lobbies are not required to be enclosed at the levels of exit discharge.

Keep in mind the elevator lobbies for fire service access elevators shall be no smaller than 150 square feet in area with a dimension not less than 8 feet.  This rule applies no matter how many FSAE cabs are served by the same lobby.  Example 8 feet x 19 feet would give you 152 square feet of lobby area.  

Fire Service Access Elevator Stretcher
Fire Service Access Elevator Stretcher

How are Fire Service Access Elevators Designated or Noticed?


IBC section 3007.6.5 gives us the following information.  A pictorial symbol of a STANDARDIZED design shall be placed on each side of the hoistway door frame on the portion of the frame at right angles to the fire service access elevator lobby.  To clear that up, the symbol shall be installed on the frame where it is noticeable immediately upon entry to the FSAE lobby.

Here is a picture of the symbol depicted in the IBC figure 3007.6.5

Fire Service Access Elevator Symbol
Fire Service Access Elevator Symbol

The following are guidelines for the design of the symbol:
  • The FSAE symbol shall not be less than 3 inches in height
  • The helmet shall contrast the background.  It states you can use a dark helmet on light background or light helmet on dark background.
  • The symbol shall be located on center line of the symbol and FSAE door frame at a height of not less 78 inches or more than 84 inches.  

FSAE Monitoring


The fire service access elevators shall be continuously monitored at the FCC by a standard emergency service interface system meeting requirements found in NFPA 72 the National Fire Alarm and Signaling Code.

FSAE Electrical Power


The following that serve each fire service access elevator shall be provided with both normal power as well as Type 60/Class 2/Level 1 standby power:
  1. Elevator equipment
  2. Elevator hoistway lighting
  3. Ventilation for elevator machine rooms, elevator control rooms, machine and control spaces.
  4. Elevator cab lighting
He is the big one to watch out for.

Protection of Wiring and Cables for Fire Service Access Elevators


Wires and cables located OUTSIDE of the fire service access elevator lobby and machine room that are provided for the fire-detection system shall be protected by construction having a fire-resistance rating of not less than 2 hours, shall be circuit integrity (CI) cable with a rating of not less than 2 hours or shall be protected by a listed electrical protective system having a rating of not less than 2 hours.

Phase 1 Recall for Fire Service Access Elevators


This is currently taken from our home state of California out of the California Building Code 2013 of CBC section 3007.2.  Activation of ANY initiating device within the building shall active the phase 1 recall of all fire service access elevators.  All standard elevators shall remain in the normal operation unless they are manually taken over via key or the activation of their associated fire alarm initiating devices.  

Firemen Inside Elevator Cab FSAE
Firemen Inside Elevator Cab FSAE


NFPA 72 Requires Elevator Lobby and Equipment Rooms to Monitor the Presence of Heat 


NFPA 72 2019 section 21.5 requires an approved means for firefighters to monitor smoke and heat conditions in the FSAE lobbies and associated machine/control rooms.  This is intended to provide firefighters with more information to determine whether the FSAE lobby protection has been compromised. This means shall include a dedicated FSAE Status Panel located at the FCC. (Reference NFPA 72-2019 Section 21.5 indicated in item 4.g below).  For Notifier we use the addressable FMM-4-20 module along with a Veris Industries TW or TE wall mounted temperature sensor.  We then provide a custom LED status panel from the H.R. Kirkland Company Inc. with each elevator lobby broken down into 3 temperature levels.  See image below of a Fire Service Access Elevator Status Panel for San Francisco, CA.

Read this article to see how Notifier is accomplishing the monitoring of individual temperature ranges within each fire service access elevator lobby.  "Temperature Sensors for Fire Service Access Elevators"


Fire Service Access Elevator Panel
Fire Service Access Elevator Status Panel


In closing fire service access elevators are a fairly new setup allowing fire fighters and first responders to access the elevators in the event of a fire.  Since these lifts are established as Fire Service Access Elevators, they must meet some very strict rules to ensure they are safe and will function in the extreme conditions of a structure fire.

All code references for this article are found in the 2021 Edition of the International Building Code.



Tuesday, December 20, 2016

Elevator Shunt Trip Wiring Diagram | Fire Alarm Power Shutdown

An elevator shunt trip is used to automatically disconnect elevator power when required by the approved elevator and fire protection design, typically where sprinkler operation could create an unsafe condition for elevator equipment.

The fire alarm system commonly provides the initiating interface for this function through heat detection and listed control equipment.

This guide explains the basic elevator shunt trip wiring sequence, the purpose of the heat detector, fire alarm control relay, shunt-trip disconnect, power monitoring, and how elevator recall differs from elevator power shutdown.

Important: The diagram below is a typical educational example, not a universal construction detail. Elevator power shutdown must follow the adopted elevator code, NFPA 72, NFPA 13 where applicable, electrical requirements, equipment listings, approved plans, elevator manufacturer's requirements, and the AHJ-approved sequence of operations.

Elevator Shunt Trip Wiring Diagram

The diagram above illustrates a typical concept for interfacing a fire alarm system with an elevator shunt-trip disconnect.

The exact arrangement varies by project. Always use the approved project drawings and equipment-specific wiring diagrams rather than treating a generic diagram as a universal installation detail.

What Is an Elevator Shunt Trip?

An elevator shunt trip is a means of automatically disconnecting electrical power to elevator equipment when required by the elevator/fire protection design.

The objective is not simply to "turn the elevator off."

Where the applicable elevator code requires automatic power shutdown because sprinkler water could create an unsafe elevator condition, the shutdown must occur upon or prior to the application of water.

The fire alarm system commonly interfaces with the electrical disconnect through a control relay or other listed interface equipment.

Elevator Recall and Elevator Shunt Trip Are Different Functions

This distinction is extremely important.

Elevator recall and elevator power shutdown are separate emergency-control functions.

Function Typical Purpose
Elevator Recall Causes the elevator system to respond to a fire alarm recall signal and move according to the approved recall sequence.
Elevator Shunt Trip Disconnects applicable elevator power when automatic power shutdown is required.

A smoke detector used for elevator recall should therefore not be confused with a heat detector used to initiate elevator power shutdown.

Basic Elevator Shunt Trip Sequence

A typical elevator shunt-trip sequence can be understood as:

Heat Detector → Fire Alarm System → Control Relay → Shunt-Trip Disconnect → Elevator Power Removed

The actual system may contain additional monitoring modules, relays, power supplies, disconnects, elevator-controller interfaces, and other components.

Each component serves a specific function and must be coordinated with the approved sequence of operations.

Why Is a Heat Detector Used for Elevator Shunt Trip?

Where automatic elevator power shutdown is required in connection with sprinkler protection, heat detection is commonly used to initiate the shutdown function before sprinkler water is discharged onto elevator equipment.

The purpose is timing.

The shutdown arrangement must coordinate the initiating device and sprinkler so the required power disconnect occurs upon or before water application.

This is different from elevator recall, which is commonly initiated by smoke detection in designated elevator-related locations.

Heat Detector Location Near the Sprinkler

Where heat detection is used to initiate elevator power shutdown, the detector location and temperature characteristics must be coordinated with the sprinkler installation and applicable requirements.

The commonly encountered arrangement places the heat detector within the required proximity of the associated sprinkler so that the detector can respond in time to initiate the shutdown sequence.

Do not simply install one heat detector somewhere in an elevator machine room and assume the requirement has been satisfied. The detector arrangement must correspond with the sprinkler protection and approved design.

Heat Detector Temperature Rating and Sprinkler Temperature

The temperature characteristics of the heat detector and sprinkler are critical.

The goal is for the elevator shutdown sequence to operate before sprinkler discharge when the applicable design requires power removal before water is applied to elevator equipment.

For this reason, the heat detector selection cannot be treated independently from the sprinkler temperature classification and response characteristics.

Design Point: Never select the elevator shunt-trip heat detector solely because a particular temperature rating is normally stocked. Coordinate the detector with the sprinkler and the approved elevator shutdown design.

Fire Alarm Relay for Elevator Shunt Trip

The fire alarm system commonly controls the elevator shunt-trip function through a listed control relay or control module.

When the appropriate heat detector activates, the fire alarm system changes the state of the control output according to the programmed sequence.

That interface then operates the shunt-trip circuit associated with the elevator disconnect.

The exact relay contact configuration, control voltage, wiring method, and fail-safe arrangement depend on the equipment and approved design.

Never assume that normally open or normally closed is universally correct for every shunt-trip installation.

Need the detailed wiring method? For a deeper explanation of ECID placement, supervised control wiring, addressable relay modules, FCM-1 versus FRM-1 operation and external interface relays, see our How to Wire an Elevator Shunt Trip | ECID & Relay Supervision guide.

What Does the Shunt-Trip Breaker or Disconnect Do?

A shunt-trip mechanism allows a circuit breaker or disconnecting means to be electrically operated from a remote signal.

In an elevator power-shutdown application, activation of the required interface causes the applicable elevator power to be disconnected.

The fire alarm control equipment is therefore generally providing the control signal. It is not carrying the elevator motor power through the fire alarm relay.

Critical: Elevator power must never be routed directly through ordinary fire alarm relay contacts unless the equipment is specifically listed and rated for that application. The fire alarm interface normally controls the appropriate listed shunt-trip equipment.

Why Shunt-Trip Control Power Matters

A shunt-trip mechanism needs an available source of control power in order to operate.

That creates an important supervision question:

What happens if the shunt-trip control power is lost before a fire occurs?

If the power necessary to perform the required shutdown is unavailable, the fire alarm system needs to provide the required indication of that impairment where required by the applicable system design and code.

This is why elevator shunt-trip installations commonly include monitoring associated with the availability of the control power.

Monitoring Shunt-Trip Power

A properly designed system should not silently lose the power necessary to perform a required elevator shutdown function.

Depending on the design, the fire alarm system may monitor the availability of the shunt-trip control power through an approved supervisory interface.

If that power becomes unavailable, the fire alarm system can then indicate the abnormal condition rather than leaving a hidden impairment.

The exact monitoring arrangement depends on the disconnect, control-power source, fire alarm equipment, approved plans, and applicable adopted requirements.

What Happens When the Shunt-Trip Heat Detector Activates?

A typical sequence is:

  1. The elevator-area heat detector reaches its operating point.
  2. The fire alarm control unit receives the detector input.
  3. The fire alarm system activates the programmed elevator power-shutdown output.
  4. The associated fire alarm control relay or module changes state.
  5. The shunt-trip mechanism operates.
  6. The applicable elevator power is disconnected.
  7. The fire alarm system provides the required event indications according to the approved sequence.

The actual project sequence may contain additional operations and must always be verified against the approved input/output matrix.

Should Elevator Recall Happen Before Shunt Trip?

Elevator recall and power shutdown are coordinated functions, but technicians should be careful with the common field explanation that the fire alarm system simply "recalls the elevator first and then waits to shunt it."

The power-shutdown function is governed by the required response to the sprinkler hazard and the approved elevator-system design.

Do not create an arbitrary fire alarm timer intended to delay required elevator power shutdown unless that exact arrangement is permitted by the applicable codes, elevator equipment, and approved design.

The fire alarm system should execute the approved sequence rather than improvising a delay in the field.

Smoke Detector vs. Heat Detector for Elevator Functions

Device Common Elevator Function
Smoke Detector Elevator recall and related Phase I emergency operation inputs where required.
Heat Detector Elevator power shutdown where required in coordination with sprinkler protection.
Waterflow Reports sprinkler waterflow but should not automatically be assumed to be the initiating input for the elevator shunt-trip function.

Does Sprinkler Waterflow Shunt Trip the Elevator?

Do not automatically use the sprinkler waterflow switch as the elevator shunt-trip initiating device simply because the shutdown is associated with sprinkler protection.

The purpose of the elevator power-shutdown arrangement is to disconnect the required power upon or prior to the application of water where the elevator code requires that protection.

Waiting for established sprinkler waterflow can be inconsistent with that objective.

Follow the approved heat-detection and shutdown design for the project.

Elevator Machine Room Shunt Trip

Where sprinklers are installed in an elevator machine room, machinery space, control room, control space, hoistway, or other applicable elevator equipment area, the designer must determine whether elevator power shutdown is required by the adopted elevator code and project conditions.

The answer should not be based simply on the fact that the building has elevators or sprinklers.

Modern elevator and sprinkler requirements contain important exceptions and installation options, so each project needs to be evaluated under its adopted codes and elevator design.

Elevator Pit Sprinklers and Shunt Trip

Elevator pits deserve particular attention because the presence of a sprinkler does not automatically mean every pit requires identical fire alarm shutdown equipment.

The sprinkler arrangement, elevator equipment exposure, applicable elevator-code provisions, and approved design determine the required sequence.

Never copy the machine-room shunt-trip design into the pit without verifying the requirements for that specific elevator installation.

NFPA 72 and Elevator Power Shutdown

NFPA 72 addresses the fire alarm system's role in emergency control function interfaces, including elevator-related functions.

The fire alarm system may be responsible for receiving the appropriate initiating-device input, processing the programmed sequence, operating listed control interfaces, supervising applicable pathways or functions, and annunciating abnormal conditions.

However, NFPA 72 is not the only standard involved.

Elevator shunt trip can involve requirements from:

  • NFPA 72, National Fire Alarm and Signaling Code
  • The adopted elevator safety code, commonly based on ASME A17.1/CSA B44
  • NFPA 13 where sprinkler protection is involved
  • NFPA 70 / NEC for electrical installation requirements
  • The adopted building and fire codes
  • Elevator manufacturer requirements
  • Fire alarm equipment listings and instructions
  • The Authority Having Jurisdiction

Do Not Treat the Fire Alarm Diagram as the Complete Elevator Design

A fire alarm drawing may show a heat detector, control module, monitor module, and interface to the elevator disconnect.

That does not necessarily document every part of the elevator electrical installation.

Coordination may be required between:

  • Fire alarm contractor
  • Elevator contractor
  • Electrical contractor
  • Sprinkler contractor
  • Mechanical contractor
  • Engineer of record
  • Fire alarm designer
  • Elevator inspector
  • Fire marshal or other AHJ

Elevator shunt trip is one of those deceptively small details on a fire alarm drawing that can involve several trades.

Testing an Elevator Shunt-Trip Interface

Testing should verify the complete approved sequence rather than merely checking whether a relay LED turns on.

Depending on the project and applicable requirements, coordinated testing should verify items such as:

  • Correct initiating heat detector
  • Correct fire alarm input identification
  • Correct programmed output
  • Operation of the fire alarm control relay or module
  • Operation of the approved elevator power-shutdown interface
  • Required monitoring of control power
  • Correct annunciation at the fire alarm control unit
  • Restoration of the system after testing
  • Coordination with elevator recall and other elevator emergency functions
Testing Warning: Do not intentionally remove elevator power during testing without coordination with the elevator contractor, building representative, and other responsible parties. An uncontrolled shunt-trip test can trap occupants, interrupt building operations, or create equipment and safety problems.

Common Elevator Shunt Trip Wiring Mistakes

  • Confusing recall with shunt trip. They are separate elevator emergency functions.
  • Using the wrong initiating device. Smoke detection and heat detection commonly perform different elevator functions.
  • Using waterflow as the automatic shutdown trigger without verifying the design.
  • Failing to coordinate the heat detector with the sprinkler installation.
  • Ignoring loss of shunt-trip control power.
  • Using an arbitrary software timer to delay shutdown.
  • Assuming every elevator pit or machine room has the same requirements.
  • Using a generic wiring diagram instead of the approved project documents.
  • Failing to coordinate fire alarm, elevator, electrical and sprinkler trades.
  • Testing the fire alarm relay but not the complete integrated function.

Elevator Shunt Trip Quick Reference

Primary Purpose Automatic elevator power shutdown where required
Typical Initiating Device Heat detector associated with applicable sprinkler protection
Fire Alarm Output Listed control relay/module or other approved interface
Controlled Equipment Approved elevator shunt-trip disconnecting means
Separate From Elevator recall
Important Coordination Elevator, fire alarm, sprinkler and electrical systems

Frequently Asked Questions

What is an elevator shunt trip?

An elevator shunt trip is an automatic means of disconnecting applicable elevator electrical power when required by the approved elevator and fire-protection design.

What activates an elevator shunt trip?

Where power shutdown is required in coordination with sprinkler protection, heat detection is commonly used to initiate the fire alarm control sequence that operates the approved shunt-trip interface.

Does a smoke detector shunt trip an elevator?

Smoke detectors are commonly associated with elevator recall functions rather than the sprinkler-related power-shutdown function. The exact operation must follow the approved elevator and fire alarm sequence.

Does a sprinkler waterflow switch shunt trip an elevator?

Waterflow should not automatically be assumed to be the correct initiating input. Where shutdown is required upon or prior to sprinkler water application, the approved design commonly uses heat detection coordinated with the sprinkler rather than waiting for established waterflow.

Is elevator recall the same as elevator shunt trip?

No. Recall commands the elevator system to perform its approved emergency recall operation. Shunt trip disconnects applicable elevator power when power shutdown is required.

Does every elevator require shunt trip?

No. Whether automatic power shutdown is required depends on the elevator equipment, sprinkler protection, adopted elevator code, building conditions, and approved design.

Does every sprinkler in an elevator area require a heat detector?

Not automatically. The required detection and shutdown arrangement depends on whether automatic elevator power shutdown is required for that sprinkler/elevator condition under the applicable codes and approved design.

Why is shunt-trip power monitored?

If electrical power necessary to operate a required shunt-trip function is lost, the shutdown function can become impaired. Where required, monitoring allows that abnormal condition to be reported rather than remaining hidden.

Can the fire alarm relay directly switch elevator motor power?

Ordinary fire alarm control contacts are generally used to interface with the approved elevator power-shutdown equipment, not to carry elevator motor power. Always follow the equipment listings and approved electrical design.

Related Elevator Fire Alarm Guides

Final Thoughts

The key to understanding elevator shunt-trip wiring is recognizing that the fire alarm system is only one part of an integrated elevator power-shutdown function.

The heat detector provides the initiating condition. The fire alarm system processes that condition and operates the approved control interface. The shunt-trip equipment disconnects the required elevator power.

Meanwhile, elevator recall remains a separate emergency function with its own initiating devices and sequence.

For a successful installation, the fire alarm, elevator, sprinkler and electrical designs all have to agree on the same sequence of operation.

Technical Disclaimer: This article is intended for educational use by qualified fire alarm and life-safety professionals. Elevator power shutdown is an integrated life-safety function. Always follow the adopted codes and standards, approved construction documents, elevator manufacturer requirements, equipment listings, electrical-safety procedures, and AHJ requirements for the specific installation.