NFPA 72 Pathway Survivability Explained: Levels 0–4, Chapter 12 & Chapter 24 Requirements

NFPA 72 Pathway Survivability: Survivability Levels (0–4), What They Mean, and When They’re Required

Pathway survivability requirements in fire alarm and emergency communication systems are governed primarily by NFPA 72 Chapter 12, which defines the physical survivability levels, and NFPA 72 Chapter 24, which establishes when survivability is required based on system type and evacuation strategy. Understanding how EVACS survivability and ECS survivability are applied in real-world designs is critical, as survivability may range from Level 0 standard wiring to enhanced protection at survivability Levels 1, 2, 3, or 4 depending on whether the system supports general evacuation, relocation, partial evacuation, high-rise operation, or smoke control integration. Properly identifying the applicable survivability level early in design helps ensure code compliance, reduces plan-review comments, and aligns the fire alarm system with the intent of the adopted building and fire codes.

Goal of this article: Provide a field-usable breakdown of NFPA 72 pathway survivability levels 0–4, including what each survivability level requires and the common code triggers (NFPA 72 + IBC/IFC scoping) that cause survivability to be mandated.

Important: Survivability triggers depend on: (1) the edition of NFPA 72 adopted, (2) the adopted IBC/IFC edition (and amendments), and (3) AHJ interpretations. This article provides reference links so readers can verify requirements in their adopted codes.



1) What “Pathway Survivability” Means

NFPA 72 uses the concept of pathway survivability to describe how well a circuit/pathway must remain operational when exposed to fire conditions. Industry guidance commonly describes this as the ability of conductors, optical fiber, radio carriers, or other transmission means to remain operational during fire conditions.

  • NFPA 72 Chapter 12 pathway survivability defines survivability levels (what Level 0/1/2/3/4 physically mean).
  • NFPA 72 Chapter 24 survivability requirements (ECS) is where survivability is most commonly required for Emergency Communications Systems applications.

Reference reading (public guidance): NEMA survivability wiring options summary and Safer Buildings Coalition pathway survivability overview.


2) Where Survivability Shows Up in Real Projects

Survivability most commonly becomes a plan-review requirement when the building/fire code requires an Emergency Voice/Alarm Communication System (EVACS) or other Emergency Communications System (ECS). The IBC/IFC typically points you to NFPA 72 for EVACS design/installation.

Example code reference page (verify your edition & amendments): IBC 2021 Section 907.5.2.2 (EVACS to NFPA 72).

Reality check: Survivability is frequently a “shadow requirement.” It may not be obvious until you correctly classify the building/system under IBC/IFC and then apply NFPA 72 Chapter 24 requirements for ECS/EVACS.


3) The Survivability Levels (NFPA 72 Chapter 12)

Think of each survivability level as a specific protection strategy the pathway must follow.

Level 0: No special survivability provisions

  • Concept: Standard wiring methods per normal electrical/fire alarm rules (no additional fire-hardening beyond baseline compliance).
  • Common use: Typical initiating and notification pathways in many buildings where ECS survivability does not apply.

Level 1: Fully sprinklered building + metallic protection approach

  • Concept (commonly summarized): Fully sprinklered building (NFPA 13) combined with a metallic/raceway-based pathway approach.
  • In practice: Many AHJs interpret “metal raceway” very literally. Verify local interpretation.

Level 2: 2-hour survivability pathway strategy

  • Concept: Maintain pathway operation under fire conditions using a 2-hour survivability method.
  • Typical options: 2-hour CI cable, 2-hour circuit protective system, 2-hour rated enclosure/protected area, or AHJ-approved alternatives (edition-dependent).

Public survivability wiring guidance: NEMA document.

Level 3: Level 2 methods + fully sprinklered building

  • Concept: Level 2 survivability methods plus a fully sprinklered building (NFPA 13).
  • Why it’s used: “Belt + suspenders” reliability where both construction method and sprinkler protection are expected.

Level 4 (newer editions): 1-hour survivability pathway strategy

  • Concept: A 1-hour survivability strategy for specific applications (edition-dependent).
  • Why it exists: To allow reduced survivability duration where the code framework permits (instead of forcing 2-hour methods for all cases).

Reference reading discussing Level 4 concepts: NFPA Research Foundation Pathway Survivability report.

NFPA 72 pathway survivability levels 0 1 2 3 4 chart showing fire alarm survivability requirements for EVACS ECS high rise relocation and smoke control systems
NFPA 72 Pathway Survivability Levels 0–4 illustrating standard wiring, sprinklered metallic pathways, 1-hour and 2-hour fire-rated pathways for EVACS, ECS, high-rise relocation, partial evacuation, and smoke control applications.



4) When Survivability Is Required (NFPA 72 Chapter 24 is the Usual Trigger)

Most “hard” survivability requirements show up in ECS/EVACS applications. A common interpretation framework is that survivability requirements increase when the system strategy depends on continued operation during a fire in another portion of the building (e.g., relocation or partial evacuation).

4.1 Relocation or partial evacuation designs (commonly drive Level 2 or Level 3)

Public survivability summaries (including NEMA guidance) describe higher survivability requirements when relocation/partial evacuation concepts are used. Verify exact section language in your adopted NFPA 72 edition.

4.2 Non-relocation general evacuation designs (often allow multiple levels)

When the system does not rely on relocation/partial evacuation, multiple survivability levels may be permitted depending on the system architecture, edition, and AHJ interpretation.

4.3 “Outside the notification zone” backbone/riser protection is where survivability often lands first

Many survivability redlines occur on risers/backbones feeding multiple zones. The intent is that a fire in Zone A should not eliminate messaging to Zone B if the design expects continued occupant instruction elsewhere.

Helpful explainer: EC&M overview on intent and survivability.


5) How IBC/IFC “Connect the Dots” to NFPA 72 Survivability

  1. IBC/IFC triggers the system type (example: EVACS required under specific building conditions).
  2. IBC/IFC points to NFPA 72 for design and installation, which then brings NFPA 72 ECS survivability requirements into scope.

Example reference page: IBC 2021 907.5.2.2.


6) Quick Reference Table: Levels, What They Look Like, Typical Triggers

Level What the pathway must be Common real-world trigger
0 Normal code-compliant wiring methods (no special fire-hardening) Non-ECS fire alarm pathways where Chapter 24 survivability doesn’t apply
1 Fully sprinklered (NFPA 13) + metallic/raceway-based pathway approach (often interpreted as metal raceway) Some ECS scenarios where Level 1 is permitted (edition/AHJ dependent)
2 2-hour survivability method (2-hour CI cable / circuit protective system / rated enclosure / approved alternative) ECS/EVACS designs that require higher survivability, especially backbones outside zones
3 Level 2 methods + fully sprinklered building Higher reliability designs where both pathway protection and sprinklers are expected
4 1-hour survivability method (newer editions) Applications where a 1-hour criterion is permitted by the adopted NFPA 72 framework

7) Design Workflow: How to Decide the Required Survivability Level

  1. Confirm adopted codes: IBC/IFC edition + local amendments.
  2. Determine if ECS/EVACS is required: if yes, NFPA 72 Chapter 24 survivability likely applies.
  3. Identify the evacuation strategy: relocation/partial evacuation vs general evacuation (edition/AHJ dependent).
  4. Map circuit geography: identify backbones/riser segments outside zones vs within a served zone.
  5. Pick the survivability method: Level 1 (sprinklers + metal pathway) vs Level 2/3 (2-hour methods) vs Level 4 (1-hour methods), as required/permitted.
  6. Document it clearly: put survivability level + method + code references on drawings/notes.

8) Common “Gotchas” That Trigger Redlines

  • “My building is sprinklered, so Level 1 automatically covers everything.”
    Not necessarily. If Chapter 24 mandates a higher level for specific ECS pathways, sprinklers alone won’t satisfy it.
  • “I used a rated enclosure so I’m good.”
    AHJs may require that your method matches the stated survivability level and approved/listed systems. Be explicit in plan notes.
  • “Survivability is only about NAC circuits.”
    In ECS architectures, survivability can apply to pathways needed for continued operation, depending on design and code language.

9) Copy/Paste Plan Notes (Ready to Use)

General Note (EVACS):

Emergency voice/alarm communication system shall be designed and installed in accordance with the adopted IBC/IFC and NFPA 72. Pathway survivability shall comply with NFPA 72 Chapter 24 requirements and survivability levels defined in NFPA 72 Chapter 12.

Riser/Backbone Note (typical survivability intent language):

Provide required Pathway Survivability for ECS/EVACS backbone/riser circuits outside the served notification zone until entering the notification zone served, in accordance with NFPA 72 Chapter 24 and Chapter 12 survivability level requirements (edition and AHJ dependent).

IBC reference example page for EVACS to NFPA 72: IBC 2021 907.5.2.2.


10) Final Reality Check (Because AHJs Exist)

Survivability is one of those topics where the code is the map, but the AHJ is the terrain. Start with the adopted IBC/IFC scoping triggers, then apply NFPA 72 Chapter 24 for ECS survivability requirements and Chapter 12 for the level definitions and permitted methods.

More reading: NEMA survivability wiring options | EC&M survivability intent overview

Friday, August 25, 2017

Occupant Evacuation Elevator Code Explained

Occupant Evacuation Elevator Code Requirements Explained

Occupant evacuation elevators (OEEs) are one of the most specialized elevator applications in the building and fire codes. If you work in fire alarm design, inspection, plan review, elevator integration, or NICET preparation, understanding how these systems are permitted, monitored, powered, and protected is critical.

This guide breaks down the code requirements for occupant evacuation elevators, including IBC Section 3008, NFPA 72 Section 21.6, emergency voice/alarm communication, elevator lobby requirements, two-way communication systems, standby power, wiring protection, and more.

NICET Prep Note: Occupant evacuation elevators are a classic crossover topic. They pull together IBC, NFPA 72, emergency controls, two-way communication, voice evacuation, fire command center functions, and survivability requirements. This is exactly the kind of material that separates surface-level memorization from real exam and field competence.

Quick Answers: Featured Snippet Q&A

What is an occupant evacuation elevator?

An occupant evacuation elevator is a passenger elevator designed and protected so it can be used for occupant self-evacuation during a fire emergency when installed in accordance with IBC Section 3008.

What code allows occupant evacuation elevators?

IBC Section 403.6.2 permits passenger elevators for public use to be used for occupant self-evacuation when installed in accordance with IBC Section 3008.

Do occupant evacuation elevators require two-way communication?

Yes. A two-way communication system is required at the lobby of each level served by an occupant evacuation elevator, with communication directed to the fire command center or another approved location.

Can occupant evacuation elevators have shunt trip?

No. A means for elevator shutdown, or shunt trip, in accordance with IBC Section 3005.5, shall not be installed on elevator controllers used for occupant evacuation elevators.

Table of Contents


What Is an Occupant Evacuation Elevator?

Much like Fire Service Access Elevators, Occupant Evacuation Elevators are in fact elevators that have strict rules and regulations put in place to allow special uses above standard elevators. An Occupant Evacuation Elevator can be used for self-evacuation during a fire emergency pending the elevator system meets the requirements set forth in the International Building Code.

Occupants running toward an occupant evacuation elevator during a fire emergency
Occupants Running to the Elevator During Fire
Related Reading: If you work with specialty elevator interfaces, also read Fire Service Access Elevators Explained.

What Code Requires or Allows the Use of Occupant Evacuation Elevators?

The requirement to provide occupant evacuation elevators can be found in the IBC or International Building Code 2021 Section 403.5.2 within the exception.

“For buildings other than Group R-2 that are more than 420 feet in building height, one additional interior stairway meeting the requirements of Sections 1011 and 1023 shall be provided in addition to the minimum number of exits required by Section 1006.3. The total width of any combination of remaining interior exit stairways with one interior exit stairway removed shall be not less than the total width required by Section 1005.1. Scissor stairways shall not be considered the additional interior exit stairway required by this section.”

Exception: An additional interior exit stairway shall NOT be required to be installed in buildings having elevators used for occupant self-evacuation in accordance with Section 3008.

Furthermore, the International Building Code 2021 Section 403.6.2 Occupant Evacuation Elevators states, “Where installed in accordance with Section 3008, passenger elevators for public use shall be permitted to be used for occupant self-evacuation.”

The requirements on how an occupant evacuation elevator is to be installed can be found in the IBC or International Building Code 2021 Section 3008.

Other references include:

NICET Practice Exam Shoutout: If you are studying emergency controls, elevator recall, shunt trip, two-way communication, smoke control interfaces, or voice evacuation, make sure you are training with realistic NICET practice exam questions, not just flash-card definitions.

Requirements for Occupant Evacuation Elevators

When an occupant evacuation elevator is to be used for occupant self-evacuation during a fire, all passenger elevators for public use shall comply with Sections 3008.1 through 3008.10. If any additional elevators are used for self-evacuation, those elevators shall comply with these sections as well.

In buildings that utilize occupant evacuation elevators, a fire safety and evacuation plan shall be approved and in place. Requirements for a fire safety and evacuation plan can be found in the International Fire Code (IFC) 2021 Section 404, Emergency Planning and Preparedness.

The operation of self-evacuating occupant evacuation elevators shall comply with the requirements in ASME A17.1, CSA B44 and the above mentioned Fire Safety and Evacuation Plan.

Emergency Voice Communication System

The building shall be equipped with an emergency voice/alarm communication system that is accessible to the fire department. System shall be installed in accordance to Section 907.5.2.2. Each elevator lobby used for occupant evacuation shall be equipped with at least one audible and one visual notification appliance.

Not that it would be common, but if you had to install voice evacuation just for the occupant evacuation elevators, it is allowed to mix audible evacuation tones. Find out more in this article, Mixing Speakers and Horns for Fire Alarm.

Recommended Read: If you are sorting out selective voice coverage, mixed appliance strategies, or emergency control interfaces, this article is a strong companion piece: Mixing Speakers and Horns for Fire Alarm.

Automatic Sprinkler Requirements

The building with occupant evacuation elevators shall be protected throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. The automatic sprinkler system shall be provided with a supervised tamper switch and alarm initiating water flow switch on every floor of the building.

Note, the following areas are prohibited from having automatic fire sprinkler protection:

  • Elevator Machine Rooms
  • Elevator Machinery Spaces
  • Elevator Control Rooms
  • Elevator Control Spaces
  • Elevator Hoistways serving the Occupant Evacuation Elevator

The lobby on each floor served by the fire service access elevator shall have an approved method of preventing water from the operation of the automatic sprinkler system from infiltrating the FSAE hoistway.

Lastly, a means for elevator shutdown or Shunt Trip in accordance with IBC Section 3005.5 shall NOT be installed on elevator controllers used for occupant evacuation elevators.

Watch-Out Item: Designers regularly mix up standard elevator concepts with occupant evacuation elevator requirements. Do not blindly apply shunt trip logic where the code specifically prohibits it.

Occupant Evacuation Elevator Hoistway Enclosure

The shaft or hoistway enclosure shall comply with IBC Section 713, Shaft Enclosures, as well as Section 403.2.3.4, Wall Assembly, and the applicable provisions for other wall assemblies.

Occupant Evacuation Elevator Cab Dimensions

Although this is not a direct requirement for occupant evacuation elevators or fire service access elevators, rather buildings that are four stories or more, it still applies and is worth mentioning.

IBC Section 3002.4, Elevator Car to Accommodate Ambulance Stretcher, gives us the dimensions required for the cab. The elevator car shall be of such a size and arrangement to accommodate an ambulance stretcher 24 inches by 84 inches with not less than 5 inch radius corners, in the horizontal, open position.

ADA Table 407.4.1 breaks this down a little further and gives us the following: the cab shall be provided with a minimum clear distance between walls and door excluding return panels not less than 80 inches by 54 inches and a minimum distance from wall to return panel not less than 51 inches with a 42 inch side slide door.

Fire service access elevator and occupant evacuation elevator car dimensions diagram
Fire Service Access Elevator and Occupant Evacuation Elevator Car Dimensions

Stretcher inside fire service access elevator cab
Stretcher inside FASE Elevator Cab

Occupant Evacuation Elevator Lobby Requirements

The Occupant Evacuation Elevator lobby shall be enclosed with a smoke barrier having a fire-resistance rating of not less than 1 hour. The occupant evacuation elevator lobby doorways shall comply with Section 3008.6.3.

NOTE: Just like Fire Service Access Elevators, enclosed occupant evacuation elevator lobbies are NOT required at the levels of exit discharge.

Lobby Sizing

Keep in mind the following for occupant evacuation elevator lobby sizing requirements:

  1. The occupant evacuation elevator lobby shall accommodate 3 square feet per person, not less than 25 percent of the occupant load of the floor area served by the lobby.
  2. Occupant evacuation elevator lobbies shall be able to house one wheelchair with a space of 30 inches by 48 inches for every 50 persons within the area the lobby serves.

There is an exception to these 2 rules. The size of an elevator lobby that serves multiple banks of elevators shall have the minimum area approved on an individual basis. This sizing shall be consistent with the building's fire safety and evacuation plan.

Lobby Doors

The occupant evacuation elevator lobby doors shall be provided with a 3/4 hour fire door assembly complying with Section 716.5. Doors shall comply with the smoke and draft control assembly requirements of Section 716.5.3.1 and UL 1784 test conducted WITHOUT the artificial bottom seal.

There shall also be a fire protection rated glazed vision window within the occupant evacuation elevator lobby doors.

No different from standard elevators or fire service access elevators, the lobby doors of occupant evacuation elevator lobbies shall close upon receipt of the fire alarm system serving the building.

The self closing mechanism shall close the door from a fully open position (90 degrees) to 12 degrees from the latch at a minimum of 5 seconds. This ensures the doors do not close too quickly. This information can be located in ANSI 117.1 2009 Section 404.2.7.1.

NICET Practice Exam Shoutout: Lobby smoke barriers, rated doors, vision panels, alarm-controlled door behavior, and code exceptions at the level of exit discharge are exactly the kind of details that show up in stronger NICET study material.

How Are Occupant Evacuation Elevators Designated or Noticed?

On all floors served by the occupant evacuation elevator, there shall be an approved sign posted adjacent to each call station. We suggest consulting with your local AHJ if they have a standard on this signage.

Occupant Evacuation Elevator System Monitoring

The occupant evacuation elevator shall be continuously monitored at the fire command center (FCC) or a central control point approved by the AHJ. The following information shall be displayed or available:

  1. The location of each elevator car
  2. The travel direction of each elevator car
  3. If the elevator car is occupied or not
  4. Status of normal power conditions to the elevator equipment, machinery, electrical apparatus cooling equipment, elevator machine room, control room and control space ventilation and cooling equipment
  5. Status of standby or emergency power conditions to the elevator equipment, machinery, electrical apparatus cooling equipment, elevator machine room, control room and control space ventilation and cooling equipment
  6. Activation of any fire alarm initiating device in any elevator lobby, elevator machine room, machine space containing a motor controller or electric driving machine, control space, control room or elevator hoistway

Elevator Landing Two-Way Communication System

You are required to provide a two-way communication system at the lobby of each level served by an occupant evacuation elevator. The two-way communication call stations shall initiate communication to the building's fire command center or an alternate location approved by the AHJ. Note the two-way communication system shall be installed in accordance with Sections 1009.8.1 and 1009.8.2.

SPACE AGE ELECTRONICS SHIELD 30 TWO-WAY COMMUNICATION SYSTEM
Product Spotlight: If you are pricing, designing, or comparing compliant communication options for elevator lobbies and accessible egress applications, the Space Age Electronics Shield 30 is worth reviewing as part of your code-compliance toolbox.

Helpful companion article: Two-Way Communication Code Requirements

Electrical Power

The following features serving each occupant evacuation elevator shall be provided with both normal power as well as Type 60/Class 2/Level 1 standby power:

  1. Elevator equipment
  2. Elevator hoistway lighting
  3. Ventilation for elevator machine rooms, elevator control rooms, machine and control spaces
  4. Elevator cab lighting

Here is the big one to watch out for.

Protection of Wiring and Cables for Occupant Evacuation Elevators

Wires and cables located outside of the fire service access elevator lobby and machine room that are provided for the fire-detection system shall be protected by construction having a fire-resistance rating of not less than 2 hours, shall be circuit integrity (CI) cable with a rating of not less than 2 hours, or shall be protected by a listed electrical protective system having a rating of not less than 2 hours.

Product / Design Callout: If you are engineering or estimating survivability requirements, make sure your team evaluates 2-hour CI cable, listed protective systems, and routing strategies early. This is one of those details that can quietly punch a hole through a submittal if missed.
NICET Practice Exam Shoutout: Circuit survivability, elevator interfaces, fire alarm monitoring, and required power sources are all fair game in advanced NICET fire alarm exam prep. The more realistic the questions, the better your retention when the pressure is on.

Hazardous Material

The building shall not contain any hazardous material areas exceeding the maximum allowable quantities per control area as noted in Section 414.2.

All code references for this article are found in the 2021 Edition of the International Building Code. Always verify adopted local code editions, state amendments, and AHJ interpretations before final design or installation.


Frequently Asked Questions About Occupant Evacuation Elevators

What is the difference between a fire service access elevator and an occupant evacuation elevator?

A fire service access elevator is intended to support firefighter operations, while an occupant evacuation elevator is designed and protected for occupant self-evacuation during a fire emergency when permitted by code.

Are enclosed lobbies required at every floor?

No. Just like fire service access elevators, enclosed occupant evacuation elevator lobbies are not required at the level of exit discharge.

Is a two-way communication system required at each elevator landing?

Yes. A two-way communication system is required at the lobby of each level served by an occupant evacuation elevator, with communication routed to the fire command center or another approved location.

Can automatic sprinklers be installed in the hoistway or machine spaces?

The article notes that elevator machine rooms, machinery spaces, control rooms, control spaces, and hoistways serving the occupant evacuation elevator are prohibited from having automatic sprinkler protection.

Does an occupant evacuation elevator require standby power?

Yes. Elevator equipment, hoistway lighting, ventilation for related spaces, and cab lighting are required to be provided with both normal power and Type 60/Class 2/Level 1 standby power.

Want More NICET and Fire Alarm Code Content?

If you found this guide useful, check out more Fire Alarms Online resources covering elevator recall, shunt trip, two-way communication, voice evacuation, and NICET practice exam prep.

The goal is simple: help fire alarm professionals design smarter, pass faster, and avoid expensive code misses in the field.

Tuesday, October 1, 2013

Is 2 Hour Rated CI Cable Too Much?

2 hour CI Cable and Survivability

As you may already know, UL (Underwriters Laboratories) has pulled their listing on 2-hour rated circuit integrity (CI) cable.  Since this cable technically no longer exists, what are we to do in current and future installations requiring the use of this CI cable?  According to the UL document, it is now up to the discretion of the local AHJ as to when it can be used or substituted with an alternate means of media.

Now, where did the 2-hour rating come from?  It is my understanding that stairwells are required to be 2-hour rated in buildings over four stories in height.  With buildings that are four stories and under in size, you will typically have a general alarm sequence and won't require any Pathway Survivability.  Buildings over four stories start getting close to the threshold for a high rise building where pathway survivability defiantly plays a role.  Depending on the level of Pathway Survivability (see NFPA 72 2010 section 12.4) level 0, 1, 2, or 3 you will have to protect your circuit pathway for a period of two hours.  Now this can be accomplished by either installing 2-hour rated cable or CI cable, 2-hour rated cable system [electrical circuit protective system(s)], 2-hour rated enclosure or protected area, or 2-hour performance alternatives approved by the authority having jurisdiction (AHJ).  Note that level 0 has no requirement for pathway survivability and level 1 can be accomplished if the building is fully protected by an automatic sprinkler system.

2-Hour Rated CI Cable Fire Alarm

To make it simple, you can run your cables for a fire fighters telephone circuit up a 2-hour rated stairwell without the use of CI cable.  However, when you exit the stairwell to extend the circuit to other areas of the building, you need to use 2-hour rated CI cable.  The intent in my mind is to provide a complete circuit pathway from the fire alarm control unit FACU to the field devices with a rating of not less than 2 hours.

Alright, so the concept is clear, you want to provide a fire alarm system that is capable of lasting at a minimum, 2 hours in the event of a fire.  This allows time for all of the occupants to evacuate and remain clear of the building.  After all it is the ultimate goal of a fire alarm, voice evacuation or mass notification system to notify the occupants of the emergency at hand.  If the wiring fails then obviously you no longer have the ability to broadcast out to your field notification appliances.  Now this is where it gets crazy.  The FACU or Fire Alarm Control Unit is not required to be 2-hour rated nor are the field devices such as fire fighter's telephone jacks, speakers, strobes, horns, etc.  So how is it that we have codes in place to insure that our fire alarm circuit pathways are secure for a period of 2 hours but not the control or notification equipment.  If there is a fire in a high rise that lasts 2 hours, the field devices would not stand a chance.  So what do we have when the fire is all said and done?  A voice evacuation system with operational cables but nothing to activate, control or notify. 

I am not sure as to why UL pulled their listing on CI cable but I honestly am not up in arms about it.  UL is remaining very silent on the issue and will not disclose any information regarding the test results of CI cables.  At this time, to save your customer money and your technicians the hassle  I recommend bringing this topic up with your local AHJ and finding out if he/she will allow the use of other cables in applications requiring NFPA 72 Pathway Survivability Levels 2 or 3.


If you are interested in taking the NICET CBT exam for fire alarms, then we have you covered!  We are now selling our CBT Levels 1 - 3 practice exam DVDs.  These DVDs are packed with tons of NICET CBT practice exams along with all code references as to where to find the answers.  We have also supplied the DVDs with all of the necessary NICET applications, CBT calculator demonstrations, links and more.  If you need more information, feel free to send an email.  You can find the link to purchase our DVDs on the top left section of each page on this site.

Monday, February 7, 2011

Why is CI Cable Required by Code?

A lot of fire alarm salesman and installers are probably wondering why CI cable is required. 

On March 12, 1984, a fire started within a retirement home in the City of Delaware, Ohio.  Smoke detectors located withing the common area sensed the fire and activated the NACS (notification appliance circuits (NAC Voltage Drop Calculations).  However, the fire quickly engulfed the surface mounted metal raceways and damaged the internal circuits.  The damage was so severe that it disabled the notification devices from sounding.  Due to the rapid silencing of the fire alarm system, some of the residents believed the signals to be false and did not evacuate.  By the time the residents learned the a the fire was in fact real it had grown large large enough to block their exits.  Two of these residents died - one from smoke inhalation and the other had a heart attack.  On top of that 7 others where injured.

In order for the fire department to properly evacuate a building they need the fire alarm system to operate through the emergency.  At least long enough for the occupants to reach safety.  In some case total evacuation is not necessary and could cause more harm than good.  This is the reason for voice evacuation and mass notification systems.  For more information on Mass Notification and Voice Evacuation read on the Notifier Onyx Series Fire Alarm Systems.

With CI cable you can be assured that the circuits have a 2 hour window of survivability.  This in most cases will be enough time to warn the occupants and respond accordingly.

What is CI Cable?

Circuit Integrity or CI Cable

The invention of CI (circuit integrity) cable has given fire alarm technicians an easy alternative to the standard MI (mineral insulated) cable.

Previously, in order to achieve the 2 hour fire rating fire alarm installers have been forced to utilize the MI cable which is copper conductors with a magnesium oxide insulation covered by a copper sheath.  Due to the MI (mineral insulated) cable's difficult installation characteristics it is typically used for emergency power circuit feeds for fire pumps and emergency generators.  However, an alternative to MI cable is now available.

CI (circuit integrity) cable is typically soft jacked with solid conductors which is also listed for use in fire alarm and voice communication systems.  The CI cable's soft jacket changes state when it is exposed to high temperatures, creating a fire resistant insulator.  However, until the CI cable's jacket is subjected to the high temperatures of a fire the cable is as flexible as your standard cable (FPLR, FPLP, etc.).  These characteristics make it as easy to install as any other cable.  Your technicians can pull it through standard raceways and conduits as well as install it without any special tools or training.  Be aware prices are not cheap!

Find out how and why CI and MI cables where demanded.