Does California require Duct Smoke Detectors on the Return Side?
Since this question comes up so often, I felt it would be
beneficial to put an article together with the answers and applicable
code/standard references. Please note that the below information is
pertinent to CA and may be altered by individual jurisdictions if they have
formally adopted a local ordinance to supersede the state level requirements.
There are two items to cover with this topic:
In California, are we
required to install the duct smoke detector on the supply or returnside
of HVAC units GREATER than 2,000 cfm?
In California, are we
required to install a duct smoke detector on both the supply and return
side of and HVAC unit GREATER than 15,000 cfm?
Before we can answer these questions, we need to know what
codes and standards California has adopted.
Chapter 35 of the California Building Code 2022 edition is
dedicated to clarifying which codes and standards are adopted by the State Fire
Marshal. The code/standard
references are on the left with vertical columns signifying which agencies have
adopted them. The third column from the left with the “Xs” is for the State
Fire Marshal. From here we can tell that based on the 2022 CBC, the applicable
standard for Fire Alarm is the 2022 edition of NFPA 72. Please also note that the IMC or International Mechanical Code is not found within this document. This
lets us know this code not valid in California and therefore its individual
language does not apply.
2022 CBC MATRIX ADOPTION TABLE - CHAPTER 35
Duct Smoke Detectors
based on NPFA 72 2022 Edition
NFPA 72 2022 Section 17.7.5.3.1 States “To prevent the
recirculation of dangerous quantities of smoke, a detector approved for air
duct use shall be installed on the supply side of air handing
systems as required by NFPA 90A and 17.7.5.4.2.1”
Duct Smoke Detectors
based on NFPA 90A
Since NFPA 90A is referenced in the above NFPA 72 standard,
it shall apply. The language for this standard is found in section 6.4.2.1 and
reads as follows:
“Smoke detectors listed for use in air distribution systems
shall be located as follows:
Downstream of the air
filters and ahead of any ranch connections in air supply systems
having a capacity greater than 2000 cfm.
At each story prior to
the connection to a common return and prior to any recirculation or fresh
air inlet connection in air return systems having a capacity greater
than 15,000 cfm and serving more than one story.”
Duct Smoke Detectors
based on the International Mechanical Code (IMC)
NO Duct Smoke Detector on Return for units greater
than 2,000 cfm in California
The code that requires a duct smoke detector in the return
side of a unit greater than 2,000 cfm is the International Mechanical Code. Keep in mind since this code is
not a referenced standard in the California Building Code, it does not apply.
Section 606.2.1 of the International Mechanical Code states a duct smoke detector shall be
installed in return air systems with a deign capacity greater than 2,000 cfm.
Summary
NFPA 72 2022 17.7.5.3.1
- In California we are required to provide a duct smoke detector on the SUPPLY
side of HVAC units per NFPA 90A.
NFPA 90A 6.4.2.1 - In
California we are required to provide a duct smoke detector on the SUPPLY
side of HVAC units greater than 2,000 cfm
NFPA 90A 6.4.2.1 – In
California we are required to provide a duct smoke detector on each return
inlet prior to a common return for HVAC units greater than 15,000 which
serve more than one floor (below is a simple
diagram showing this setup.)
IMC 2021 606.2.1 –
Requires a duct smoke detector in the return of HVAC units greater than
2,000 cfm. THIS DOES
NOT APPLY IN CALIFORNIA
How to Test a Duct Smoke Detector With a Manometer
Learn how to test the differential pressure of a duct smoke detector using a digital manometer, including sampling-tube connections, NFPA 72 testing requirements, System Sensor DNR pressure ranges and common inspection mistakes.
Quick Answer: Why Use a Manometer on a Duct Smoke Detector?
A manometer measures the differential pressure between the sampling and exhaust sides of a duct smoke detector.
This test helps verify that air from the HVAC duct is actually being drawn through the detector's sampling system so smoke present in the airstream can reach the sensing chamber.
A duct smoke detector can appear completely normal, communicate with the fire alarm panel and even respond to locally introduced test smoke while still having an improperly installed or obstructed sampling system.
Key Point:
Testing the detector head and verifying sampling-tube differential pressure are related but different inspection functions. A successful detector alarm test does not automatically prove that the sampling tubes are properly sampling the duct airstream.
What Is a Manometer?
A manometer is an instrument used to measure pressure or the difference between two pressures.
For duct smoke detector testing, a digital manometer is connected between the detector's sampling-tube inlet and exhaust side. The resulting measurement indicates the pressure differential created by air moving through the duct.
The reading is commonly displayed in:
Inches of water column
in. H2O
inH2O
This pressure difference is usually small, which is why a sensitive digital manometer is commonly used for fire alarm duct detector testing.
Actual field testing of a duct smoke detector using a manometer to verify differential pressure across the sampling and exhaust ports.
A duct smoke detector relies on the HVAC airstream to move a representative sample of air through the detector housing.
The sampling tube extends into the duct and captures moving air. The exhaust side allows that air to leave the detector housing.
The pressure difference between the two sides is what drives airflow through the detector.
If the differential pressure is too low, the detector may not receive an adequate sample of the duct airstream.
Potential causes include:
Sampling tube installed backwards
Sampling holes facing away from the airflow
Missing sampling-tube end cap
Improper sampling-tube length
Blocked or contaminated sampling holes
Damaged tubing
Improper detector mounting
Air leakage around the detector housing
Low duct velocity
Incorrect sampling or exhaust-tube configuration
Typical manometer connection concept for testing duct smoke detector differential pressure. Always follow the detector and test-equipment manufacturer's labeling and instructions because port orientation and connection details can vary by model.
What Does NFPA 72 Require for Duct Smoke Detector Testing?
NFPA 72 addresses inspection, testing and maintenance of duct smoke detectors in Chapter 14.
For duct smoke detectors that use sampling tubes, the testing framework requires verification that the detector will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with the manufacturer's published instructions.
This testing is generally performed annually.
NFPA 72 Testing Principle:
A duct smoke detector using sampling tubes must be tested to verify that the sampling arrangement is capable of properly sampling the HVAC airstream. The specific testing method and acceptable values come from the detector manufacturer's published documentation.
Do Not Use One Universal Pressure Range:
NFPA 72 does not establish one differential-pressure value that applies to every duct smoke detector. The acceptable pressure range is determined by the manufacturer of the specific detector being tested.
How to Test a Duct Smoke Detector With a Manometer
1
Identify the duct detector manufacturer and model.
Before connecting the meter, locate the manufacturer's installation or testing instructions and determine the acceptable differential-pressure range.
2
Verify the HVAC system is operating as required for the test.
Differential-pressure testing depends on airflow through the duct. Follow the detector manufacturer's instructions regarding required HVAC operating conditions.
3
Connect the manometer hoses.
Connect the positive-pressure side of the manometer to the detector's sampling or inlet side and the negative-pressure side to the exhaust side, unless the manufacturer specifies a different connection arrangement.
4
Turn on and zero the manometer.
With the hoses connected according to the test equipment instructions, zero the meter before taking the final reading.
5
Select the correct pressure units.
For many duct detector specifications, the required reading is expressed in inches of water column, typically shown as in. H2O.
6
Read the differential pressure.
Allow the reading to stabilize and record the measured pressure differential.
7
Compare the reading with the manufacturer's specification.
The measured differential pressure must fall within the acceptable range published for the specific duct detector model.
8
Document the result.
Record the reading as part of the fire alarm inspection and testing documentation.
Typical step-by-step process for checking duct smoke detector differential pressure. Always use the exact detector and test-equipment manufacturer instructions for the equipment being tested.
Using the SDi Duct Checker
The test instrument used in the original Fire Alarms Online article is the SDi Duct Checker.
The Duct Checker is a portable, battery-operated digital manometer designed specifically for measuring differential pressure associated with duct smoke detector sampling systems.
It includes test hoses and adapters that allow technicians to connect to the sampling and exhaust ports of many common duct detector housings.
SDi Duct Checker digital manometer used for duct smoke detector differential-pressure testing.
For current product information and operating instructions, visit:
The original article used the System Sensor DNR duct smoke detector as its example.
System Sensor guidance for this detector family identifies an acceptable differential-pressure range of approximately:
0.01 to 1.11 in. H2O
System Sensor differential-pressure example
This is not a universal duct detector pressure range.
The 0.01 to 1.11 in. H2O range applies to the System Sensor example discussed here. Other manufacturers and detector models can have different acceptable ranges.
Always verify the current installation manual, technical bulletin or manufacturer documentation for the exact detector model before determining whether a reading passes or fails.
What If the Differential Pressure Is Too Low?
A low or zero manometer reading can indicate that the duct detector is not properly sampling the airstream.
Before condemning the detector, inspect the installation.
Check the Sampling Tube Direction
Sampling tube openings generally need to face the incoming airflow in accordance with the detector manufacturer's instructions.
If the tube is installed backwards, the detector may not develop the required differential pressure.
Check the Sampling Tube End Cap
Some sampling tube designs require an end cap to establish the proper airflow through the detector housing.
A missing end cap can substantially affect the pressure reading.
Check Tube Length
Sampling tubes must be selected or cut for the duct width according to the manufacturer's installation instructions.
A tube that does not extend far enough across the duct can prevent proper representative sampling.
Check for Dirt or Obstructions
Dust, insulation fibers, construction debris and other contaminants can obstruct sampling holes or tubing.
Check the Detector-to-Duct Seal
Air leaking around the detector housing or duct penetration can interfere with proper airflow through the sampling chamber.
Check HVAC Air Velocity
If airflow is outside the detector manufacturer's specified operating range, the duct detector may not develop an acceptable differential pressure.
What If the Differential Pressure Is Too High?
An excessive differential-pressure reading should also be investigated.
Possible causes can include:
Air velocity outside the detector's approved range
Incorrect sampling tube
Improper tube orientation
Incorrect installation configuration
Obstructed exhaust path
Incorrect test connections
Compare the installation directly with the manufacturer's instructions before making adjustments.
Manometer Test vs. Smoke Test
These tests answer two different questions.
Test
What It Verifies
Manometer / Differential Pressure Test
Verifies that the sampling system is capable of moving duct air through the detector housing.
Smoke / Functional Alarm Test
Verifies that the smoke-sensing element can respond and initiate the required alarm or control sequence.
Both Matter:
A duct detector can successfully alarm when smoke is introduced directly into the sensing chamber but still have a sampling tube installation that does not properly sample the duct airstream.
Do You Need to Test Duct Detector Air Velocity?
Differential pressure and duct air velocity are related but are not exactly the same measurement.
The detector manufacturer specifies the acceptable airflow or air-velocity conditions under which the duct detector is listed to operate.
If a differential-pressure reading is outside the acceptable range, the manufacturer may instruct the technician to verify actual duct velocity using an appropriate airflow instrument such as an anemometer.
Never assume that a pressure reading alone proves that every other manufacturer installation requirement has been satisfied.
Common Duct Smoke Detector Testing Mistakes
Reversing the positive and negative manometer hoses
Connecting to the wrong detector ports
Failing to zero the manometer before testing
Using the wrong pressure units
Testing with the HVAC system off when airflow is required
Using one pressure range for every manufacturer
Assuming the System Sensor range applies universally
Failing to verify sampling tube direction
Ignoring a missing sampling-tube end cap
Failing to inspect blocked sampling holes
Ignoring duct air velocity
Performing only a smoke test and skipping airflow verification
Performing only a pressure test and skipping functional detector testing
Failing to document the manometer reading
Not following the detector manufacturer's installation instructions
Duct Smoke Detector Annual Inspection Checklist
☐ Identify detector manufacturer and model
☐ Review current manufacturer instructions
☐ Verify HVAC operating condition
☐ Inspect detector housing
☐ Inspect sampling tube orientation
☐ Confirm sampling holes face the required direction
☐ Verify sampling tube length
☐ Verify required sampling tube end cap
☐ Inspect sampling tube for dirt or blockage
☐ Inspect exhaust tube or exhaust opening
☐ Inspect detector-to-duct seal
☐ Connect manometer correctly
☐ Zero the meter
☐ Select the correct pressure units
☐ Measure differential pressure
☐ Compare reading with manufacturer's range
☐ Investigate readings outside the acceptable range
☐ Functionally test detector operation
☐ Verify required fire alarm system response
☐ Verify HVAC shutdown or control functions where applicable
☐ Document inspection and test results
Duct Smoke Detector Manometer Testing FAQs
What does a manometer test on a duct smoke detector?
It measures the differential pressure between the sampling and exhaust sides of the duct detector to help verify that the detector is properly sampling the duct airstream.
How often should a duct smoke detector be tested?
NFPA 72 generally establishes annual testing for duct-type smoke detectors and verification that detectors using sampling tubes properly sample the airstream.
What should the manometer reading be?
There is no single pressure range for every duct smoke detector. Use the acceptable differential-pressure range published by the manufacturer of the specific detector.
What is the System Sensor DNR differential-pressure range?
For the System Sensor example discussed in this article, the published acceptable differential-pressure range is approximately 0.01 to 1.11 in. H2O. Always verify the current documentation for the exact detector being tested.
Which hose goes to the sampling tube?
In a typical differential-pressure test, the positive side of the manometer is connected to the sampling or inlet side and the negative side to the exhaust side. Follow the manufacturer and test-equipment instructions for the exact detector.
Does a successful smoke test prove the sampling tubes work?
No. Directly introducing test smoke can verify detector operation without proving that the installed sampling tubes can properly draw smoke from the HVAC airstream.
Can I use any digital manometer?
Use a pressure-measuring instrument appropriate for the range and accuracy required by the detector and test procedure. Dedicated duct-detector tools such as the SDi Duct Checker are designed specifically for this application.
What can cause a zero pressure reading?
Possible causes include incorrect hose connections, HVAC airflow being off, improper sampling tube installation, blocked tubing, missing components, air leakage or insufficient duct velocity.
NFPA 72, National Fire Alarm and Signaling Code — inspection, testing and maintenance requirements for smoke detectors and duct-type smoke detectors
System Sensor / Honeywell manufacturer documentation — duct detector installation, differential-pressure limits and sampling tube requirements
SDi Duct Checker documentation — operation of the digital manometer used for duct smoke detector differential-pressure testing
Detector manufacturer installation instructions — acceptable pressure range, sampling tube installation, airflow requirements and test methods
Code Edition Reminder:
NFPA 72 section and table numbering can change between editions. Verify the edition adopted for your project and follow the current manufacturer's instructions rather than relying on an older section number from a previous code cycle.
Educational information only. Always verify testing procedures against the adopted codes, approved plans, equipment listings, manufacturer instructions, project specifications and the authority having jurisdiction.
System Sensor D4120 InnovairFlex Duct Smoke Detectors
These conventional duct smoke detectors include a tamper switch feature that results in a trouble signal at the fire control panel when the duct detector cover has been removed or is not properly installed. If your System Sensor D4120 duct smoke detector is displaying a solid Amber LED, then this is the device's indication that the cover is either missing or not properly tightened down. Keep in mind that this trouble condition will also disable the System Sensor's detector test feature, which is activated using one of the following methods; the Push Button on the power board, the Magnet Test or Remote Test Stations.
If you are experiencing this trouble condition, ensure that the System Sensor D4120 duct detector cover of the device is properly aligned and the connecting screws are tightened firmly. When properly attached, a small pole on the cover should contact the bottom left terminal of the tamper switch and depress to contact a terminal on the underside of the cover, closing the tamper switch.
Duct smoke detectors are a common device found in most fire alarm systems from the past and present. Whether the duct smoke detector is addressable or conventional, they both work the same way. A sample tube is inserted into the duct work and samples the air for smoke. If smoke is detected then the photoelectric smoke detector head within the duct smoke detectors sends an alarm signal to the fire alarm panel and shuts down the air conditioning unit.
With that said, most of these duct smoke detectors are located in areas that are not very easily accessed. These areas could include areas such as above t-bar or hard lid ceilings, attic spaces or roof tops. If the actual duct detector is located above a ceiling then access hatches or panels must be provided for obvious reasons. Also if the duct smoke detector is located in an area out of sight then you must provide a detailed description of the device location within the fire alarm control panel program as well as a remote LED plate on the ceiling below the device. This will assist the fire department, end user and technician locate the device. In fact, some jurisdictions such as L.A. County are requiring the remote LED plate to be installed any time you have a duct smoke detector above a ceiling and out of plain view.
With all of this information it is hard for me to understand how some of these local fire alarm installation companies are getting away with installing the remote LED plates on the wall directly above the thermostat controls for the particular HVAC unit. This picture was taken at a local restaurant in the Valencia, CA area. Now with these remote LED plates installed on the wall it makes it easy for fire alarm testing but it totally eliminates their true purpose. If there is a fire reported at the building with a signal coming from a duct smoke detector then the fire department is going to want to know exactly where it's location is the minute they enter. The LED on the wall does not exactly help.