HyperTerminal with Gamewell IF602 FACP

As we all know, HyperTerminal is a great program that came with Windows based PCs prior to Vista. HyperTerminal is a great program to assist with programming and capturing data for specific fire alarm control panels via their SIM 232 connection port.

In this post we will explain how to properly connect your laptop computer running HyperTerminal to a Gamewell IF602 addressable fire alarm control panel. First of all as with all Gamewell and HyperTerminal connections, make sure to disconnect the Remote Annunciator (RAN) and/or SAN cards.

Next you will notice two phone jacks at the top of the motherboard. These are labeled as J5 and J6. When programming via SmartProgram or HyperTerminal make sure to connect to J6 as shown in the picture.
Gamewell IF602 Motherboard


Port J5 is used for firmware updates.

Once you have connected your programming cable to the Motherboard via J6 and to your computer's serial port open the HyperTerminal program.

After you have completed the above steps be sure to view my HyperTerminal for Gamewell 600 Series video for a complete walk through on the HyperTerminal settings and usage.

Make sure to join our Fire Alarms Online Facebook Group HERE.


Thursday, May 16, 2013

Hyper Terminal Commands for FCI E3

Okay a lot of people have been asking me for this information.  I constantly get asked if I know the Hyper Terminal commands for the Fire Control Instruments (FCI) E3.  In this post I have put down a few to get you guys started.  I will try to get more and update this list as they are found. 

If you know any other ones besides the list I have provided, then please be sure to leave a comment with them.
Honeywell FCI E3 Series Fire Alarm Control Panel

E3 Hyper Terminal / OTS Commands

Level 2 Password for access - [P22] [22] [22] You replace the 2's with whichever level you're needing to access with the correct level's password.

Reset - [R]

Silence - [S] [1] also there is [S] [0] to unsilence.

Version - [V]

Sensitivity Report - [DS]

History Events: Last 20 events - [LP] [2] Also there is this one, All events - [LP] [1]

This should be good to get you started.  I have also put together a small list for the Fire Control Instruments 7100  series fire alarm control panel.  See it here.

Make sure to join our Fire Alarms Online Facebook Group HERE.

HyperTerminal Settings For Fire Alarm Panels

Hyperterminal is a great way to connect to a fire alarm control panel.  It is also the preferred method to achieving a fire alarm control panels device parameters f you cannot access the program.  Simply connect your laptop to the fire alarm control panel with the appropriate cable and enter the correct values for HyperTerminal.  Once in, your laptop will mimic the FACUs screen or display.  From here you can capture the text file making it easy to store fire alarm testing reports and device parameters.

Here is a little trick if you need to know exactly what devices are on each loop.  While connected with Hyperterminal, pull off each SLC circuit one at a time.  Your laptop screen will then start to display every device on that loop as they go into trouble due to the lack of communication with the FACU loop card.  Capture the text file and your done.  You now have a simple starting plan to re-write a program if necessary.

Below are some of the HyperTerminal settings I have come across:

FCI E3 Series FACU:
  1. Start HyperTerminal from its Start Menu icon.
  2. Give the connection a name (for example, E3) and select any icon that you’d like. Click OK to continue.
  3. In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
  4. Set your parameters as follows:
    • Bits per second: 115200
    • Data bits: 8
    • Parity: None
    • Stop bits: 1
    • Flow Control: None
  5. Click OK.
  6. You are now connected to the panel.
  7. Click here for a video demonstration
Gamewell 600 Series FACU: Includes the IF610, IF602, IF650, IF630
  1. Start HyperTerminal from its Start Menu icon.
  2. Give the connection a name (for example, 600) and select any icon that you’d like. Click OK to continue.
  3. In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
  4. Set your parameters as follows:
    • Bits per second: 2400
    • Data bits: 8
    • Parity: None
    • Stop bits: 1
    • Flow Control: Xon / Xoff
  5. Click OK.
  6. Select the pull down file menu at the top of the screen
  7. Select properties
  8. Select settings tab
  9. Set emulation to VT-100
  10. Select ASCII setup
  11. Change the line display setting to 1 milliseconds
  12. Change character display setting to 100 milliseconds
  13. Click OK twice
  14. You are now connected to the panel.
  15. Click here for a video demonstration.
Notifier Fire Warden Series FACU: Includes NFW2-50 and NFW2-100
  1. Start HyperTerminal from its Start Menu icon.
  2. Give the connection a name (for example, Fire Warden) and select any icon that you’d like. Click OK to continue.
  3. In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
  4. Set your parameters as follows:
    • Bits per second: 19200
    • Data bits: 7
    • Parity: Even
    • Stop bits: 1
    • Flow Control: None
  5. Click OK.
  6. You are now connected to the panel.
  7. click here for a video demonstration
Fire-Lite Series FACU: Includes MS-9200, MS-9600, MS-9200UDLS, MS-9600UDLS
  1. Start HyperTerminal from its Start Menu icon.
  2. Give the connection a name (for example, Fire-Lite) and select any icon that you’d like. Click OK to continue.
  3. In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
  4. Set your parameters as follows:
    • Bits per second: 19200
    • Data bits: 7
    • Parity: Even
    • Stop bits: 1
    • Flow Control: None
  5. Click OK.
  6. You are now connected to the panel.
  7. Click here for a video demonstration
FCI 7100 Series FACU:
  1. Start HyperTerminal from its Start Menu icon.
  2. Give the connection a name (for example, 7100) and select any icon that you’d like. Click OK to continue.
  3. In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
  4. Set your parameters as follows:
    • Bits per second: 9600
    • Data bits: 8
    • Parity: None
    • Stop bits: 1
    • Flow Control: None
  5. Click OK.
  6. You are now connected to the panel.
  7. Click here for a video demonstration
FCI 7200 Series FACU:
  1. Start HyperTerminal from its Start Menu icon.
  2. Give the connection a name (for example, 7200) and select any icon that you’d like. Click OK to continue.
  3. In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
  4. Set your parameters as follows:
    • Bits per second: 1200
    • Data bits: Leave Default
    • Parity: Leave Default
    • Stop bits: Leave Default
    • Flow Control: None
  5. Click OK.
  6. You are now connected to the panel.
  7. Click here for a video demonstration
I have more coming.  In the mean time if you guys know of any others you would like to share drop me an email or comment on this post.