Thursday, March 19, 2015

Do You Need a Heat Detector in the Elevator Pit? (2024 Code Update)

Designers and plan reviewers ask this constantly: “Are you required to install a heat detector in the bottom of the elevator shaft (the elevator pit)?” The short answer is: sometimes, and only when specific code-driven conditions exist.

This topic sits at the intersection of multiple standards. For most U.S. jurisdictions using the latest model codes, the governing framework is:

  • 2024 IBC (Chapter 30: Elevators and Conveying Systems)
  • 2024 IFC (elevator-related fire code provisions and operational coordination)
  • NFPA 72 (2022) Chapter 21 (Elevator Recall and Elevator Power Shutdown)
  • NFPA 13 (2019/2022 as adopted) hoistway/pit sprinkler rules and exemptions
  • ASME A17.1 / CSA B44 (Safety Code for Elevators and Escalators) Firefighter’s Emergency Operation and sprinkler-related provisions

Important: The fire alarm heat detector is only tied to elevator shutdown when a sprinkler is present and shutdown is required. A pit heat detector is not a universal requirement.

Elevator pit with standing water showing sprinkler protection area requiring heat detection for elevator power shutdown per NFPA 72 and ASME A17.1

A sprinkler head in an elevator pit is typically intended to control a fire caused by accumulated debris (trash, packaging, lint, etc.) that can fall through door gaps over time. Whether that sprinkler is required (or exempt) is primarily a sprinkler-code question governed by NFPA 13 and referenced by the adopted building/fire code.


1) First Condition: Is There a Sprinkler in the Pit?

Under NFPA 13 (2019/2022 as adopted), sprinklers in hoistways and pits are required unless the installation meets specific exemption criteria. In modern designs, exemptions are common depending on construction type, elevator type, and whether combustibles are present.

Code References:

  • NFPA 13 (2019/2022 as adopted): Hoistway and pit sprinkler criteria and exemptions (section numbering varies by edition).
  • 2024 IBC / 2024 IFC: reference adopted sprinkler standards for system design and installation.

If there is no sprinkler in the pit, then there is generally no pit heat detector requirement for elevator power shutdown, because there is no sprinkler discharge to coordinate with.


2) Second Condition: Sprinkler Elevation Above Pit Floor (The 24-Inch Rule)

If a sprinkler exists in the pit, the next key question is: Is the sprinkler located within 24 inches (2 feet) of the pit floor?

Under ASME A17.1 / CSA B44, sprinklers installed in certain elevator locations can trigger special arrangements related to elevator power shutdown. However, when a sprinkler is installed very low (within 24 inches of the pit floor), shutdown coordination is often not required because energized elevator equipment is not typically located in that zone.

Code References:

  • ASME A17.1 / CSA B44: Provisions addressing sprinkler interactions and elevator emergency operations (edition and section numbering vary by adoption).
  • 2024 IBC Chapter 30: Elevators governed by ASME A17.1 (referenced standard) and emergency operation requirements.

3) NFPA 72 (2022): When a Pit Heat Detector Is Required for Shutdown

Elevator power shutdown (often called “shunt trip”) is governed by NFPA 72 (2022) Section 21.4. When shutdown is required to occur prior to sprinkler discharge, NFPA 72 establishes the rules for the initiating means.

  • NFPA 72 (2022) 21.4.1 – Elevator power shutdown intent and coordination (power removed prior to sprinkler discharge where required)
  • NFPA 72 (2022) 21.4.2 – Heat detection used for shutdown initiation installed within 24 inches of each sprinkler head
  • NFPA 72 (2022) 21.4.3 – If waterflow/pressure switches are used for shutdown initiation, time delay is not permitted

Key distinction: Smoke detectors are used for elevator recall under NFPA 72 (2022) Section 21.3. Heat detection (or an approved equivalent initiating means) is used for elevator power shutdown under Section 21.4.

Industry practice: Use heat for shutdown, smoke for recall. Mixing these functions is a common plan-review failure.


4) Mini Sequence of Operations (SOO): Elevator Pit Shutdown Only

Below is a compact, plan-review-friendly SOO focused only on pit shutdown coordination. Adapt point names to your panel programming standards.

Input Device / Condition FA System Action Output / Result Notes
HD-PIT Pit Heat Detector (within 24" of pit sprinkler where shutdown is required) Alarm; initiate elevator power shutdown sequence OUT-SHUNT (shunt trip control to disconnect/breaker) NFPA 72 (2022) 21.4.2 proximity; coordinate rating vs sprinkler temperature
LHD-PIT (optional) Linear Heat Detection Cable (listed, where used/approved) Alarm; initiate elevator power shutdown sequence OUT-SHUNT Allowed as listed initiating means when installed/tested per manufacturer and accepted by AHJ
WF-PIT (optional) Waterflow / Pressure Switch (dedicated elevator branch where used) Alarm; initiate immediate shutdown OUT-SHUNT No time delay permitted per NFPA 72 (2022) 21.4.3
TRB-PIT Device / Module Trouble (open, ground, loss of supervision) Trouble only (no shutdown) None Document supervision and response policy in record drawings

5) Three Common Shutdown Methods (Modern Practice)

#1 – Waterflow / Pressure Switch Method

This method uses a waterflow/pressure switch on the elevator sprinkler branch to initiate shutdown. If used, ensure compliance with NFPA 72 (2022) 21.4.3, including the “no delay” requirement.

#2 – Fixed Temperature Heat Detector (Most Common)

A heat detector is installed within 24 inches of the sprinkler head used for shutdown initiation (NFPA 72 (2022) 21.4.2). It must be selected/arranged to activate before sprinkler discharge temperature.

#3 – Pre-Action System with Supplemental Detection

Pre-Action systems can be used in certain elevator spaces. Supplemental detection (typically heat) releases the pre-action valve. The same initiating condition can also be used to trigger elevator shutdown where required, with AHJ/elevator coordination.


6) Compliance Comparison: 2016 vs 2022 vs 2024 Framework

Topic NFPA 72 (2016 Era) NFPA 72 (2022) 2024 IBC / 2024 IFC
Elevator Shutdown Rules Chapter 21.4 structure used widely (older projects often cite 21.4.x) Chapter 21.4 remains, with clearer coordination expectations and modern adoption Model codes reference NFPA 72 for interface and NFPA 13 for sprinklers
Heat vs Smoke Function Frequently mixed up in design Clear separation: recall (21.3) vs shutdown (21.4) Adopts NFPA 72 concepts through referenced standards
24" Proximity Requirement Commonly cited as 2 ft from sprinkler for shutdown detection Still required for shutdown initiation (21.4.2) Drives coordination when sprinklers exist under NFPA 13 and ASME A17.1
Waterflow Method Timing No time delay permitted No time delay permitted (21.4.3) Enforced via NFPA 72 referenced requirements

Final Code-Based Answer

A heat detector in the elevator pit is required only when:

  • A sprinkler head is installed in the pit (NFPA 13 as adopted), and
  • The sprinkler is located above the “low zone” where ASME A17.1 would not exempt shutdown coordination (commonly referenced as within 24 inches of the pit floor), and
  • Elevator power shutdown prior to sprinkler discharge is required (NFPA 72 (2022) 21.4).

If there is no pit sprinkler, a pit heat detector for shunt trip is generally not required. If the pit sprinkler is within 24 inches of the pit floor, shutdown coordination may not be required per ASME A17.1 practice. Always verify local adoption, amendments, and AHJ interpretation.

Interface wiring responsibilities (typical): FA Vendor furnishes/terminates FA monitor/control modules and provides dry-contact outputs/inputs; Electrical Contractor installs/terminates shunt-trip disconnect/breaker control wiring; Elevator Contractor terminates at the elevator controller and validates recall/shutdown operation during testing with the AHJ.

Saturday, May 18, 2013

Elevator Recall Programming for Fire Alarm

Are you up to speed with fire alarm systems in relation to elevator recall and elevator shunt trip? If not, check out this article titled Elevator Recall and Shunt Trip Basics.

Easy Way to Breakdown Elevator Recall and Shunt Trip Programming


Now that we know what elevator recall is all about, lets move on to programming basics for fire alarm systems.  The best way to start this process is to write down all of your fire alarm devices associated with the elevator recall functions.  Make a list running vertical (top to bottom) of all the smoke detectors and heat detectors used for these functions.  Example below:

1 - 1st floor elevator lobby smoke detector
2 - 1st floor elevator machine room smoke detector
3 - 1st floor elevator machine room heat detector
4 - 2nd floor elevator lobby smoke detector
5 - 3rd floor elevator lobby smoke detector
6 - 4th floor elevator lobby smoke detector
7 - Elevator hoistway smoke detector
8 - Elevator hoistway heat detector
9 - Designated elevator recall relay
10 - Alternate elevator recall relay
11 - Shunt trip relay
12 - Elevator battery back-up relay
13 - Elevator fireman's hat light relay

Now that we have all of our fire alarm devices associated with the elevator recall functions written down, it's time to place them in groups or zones.  This is the process that tells the fire alarm control panel what to do in the event one of these devices is activated.

As stated in one of our previous articles,  we know that the smoke detectors on all floors other than the first floor will send the elevator the the 1st floor.  We also know that the smoke detectors on the first floor will send the elevator to the second floor.  And last the heat detectors will activate the shunt trip and battery back-up and the elevator hoistway and elevator machine room smoke detectors will activate the fireman's hat light or visual warning per NFPA 72 2016 21.3.13.3.  To make this simple we are going to use 5 different zones (1 = general alarm, 2 = primary elevator recall, 3 = secondary elevator recall, 4 = shunt trip/battery back-up, and 5 = fire fighters hat light).

With that said, take your list above and write down the zones or groups for each point next to the device description.  Also make note of which devices are inputs and outputs.

Elevator Recall and Shunt Trip Programming Zones


1 - 1st floor elevator lobby smoke detector (input) -------- 1,3
2 - 1st floor elevator equipment room smoke detector (input) -------- 1,3,5
3 - 1st floor elevator machine room heat detector (input) -------- 1,4,5
4 - 2nd floor elevator lobby smoke detector (input) -------- 1,2
5 - 3rd floor elevator lobby smoke detector (input) -------- 1,2
6 - 4th floor elevator lobby smoke detector (input) -------- 1,2
7 - Elevator hoistway smoke detector (input) -------- 1,2,5
8 - Elevator hoistway or pit heat detector (input) -------- 1,4,5
9 - Designated elevator recall relay (output) -------- 2
10 - Alternate elevator recall relay (output) -------- 3
11 - Shunt trip relay (output) -------- 4
12 - Elevator battery back-up relay (output) -------- 4
13 - Elevator fireman's hat light relay (output) -------- 5



Elevator Recall Detail

Now that you have it all written out it makes it a lot easier to program.  Hope this helps.  If you have questions regarding elevator recall be sure to post a comment or email us.