Showing posts with label fire alarm. Show all posts
Showing posts with label fire alarm. Show all posts

Sunday, March 29, 2015

Fire Alarm Underground Conduits

Is it OK to Install Fire Alarm Cable underground?


PIV Post Indicator Valve for Fire Alarm Sprinkler System
Post Indicator Valve  with Fire Department Connection
A common task when installing a new fire alarm system is undergrounds. Typically when a C-16 or fire protection (fire sprinkler) contractor installs their incoming lines they will at the same time install the necessary fire alarm underground conduits for the connections to the backflow prevention switches (OS&Y Outside Screw and Yoke) or PIV (Post Indicator Valve) switches. However, sometimes this task could be a part of the fire alarm contractor's scope of work. If you find yourself installing underground conduit or direct burial cable make sure to follow all of the national codes and regulations.

Direct Burial Cable as an Alternate to Conduit


Backflow Preventor OS&Y For Fire Alarm Sprinklers
Backfloe Preventor with OS$Y Switches for Fire Alarm
Some contractor's may choose to use direct burial cable also referred to as UF Cable commonly identified by its grey coating. Direct burial fire alarm cable not protected in conduit must be installed at a depth of 24" below grade with either schedule 80 PVC or Rigid conduit stubs up to your box. When fire alarm cable is installed within plastic conduit it must be 18" deep and installed with schedule 80 PVC. This is a more durable plastic conduit (grey color) than the common household irrigation lines. The best way to install these conduits or cable is with a Ditch Witch. Simply set the depth and go.

Junction boxes that are run out into the middle of a remote area without an anchor point must have the schedule 80 PVC embedded in the concrete to support the box. Another method is to attach the box to a post that is either driven or buried in the ground 18" and connects directly to the schedule 80 PVC conduit. Junction boxes should be installed at least 12" above grade but not more than 18" for the unattached method.

See also conduit bending videos.

Make sure to join our Fire Alarms Online Facebook Group HERE.

Sunday, May 19, 2013

When Are Fire Alarm Batteries Required to be Replaced

What is the Code for Replacing Fire Alarm Batteries?


It is common knowledge in the fire alarm installation industry that fire alarm batteries are to be replaced typically within 4-5 years from date of manufacturing. What you will commonly notice with companies is a lack of experience resulting in dead fire alarm batteries. Most fire alarm technicians will simply take a label maker or Sharpie and write down the installation date on the backup fire alarm batteries.

You may ask yourself, "What's wrong with this?"

Fire Alarm Battery Manufacturer Date Code

The answer is simple. As stated above the the fire alarm batteries must be replaced with 4 - 5 years from date of manufacture. If you write the installation date on the batteries then you are not noting accurate information. The reason for this is that there is no telling how long those fire alarm batteries sat in your warehouse or even the manufacturer's warehouse.

What's the Correct Way to Note the Battery Date?


Fire Alarm Back-up battery manufacturers are stamping the fire alarm batteries with the month and year of manufacture. This is the date that you want to mark down.  The fire alarm battery pictured above is manufactured by Power Sonic and has a date tamp of 10194-H on it.  I wont go into too many details about battery date codes as I have another files to assist you with this.  The code of 10194 = the Month (10) the Day (19) and the Year (2004). So as you can see by a technician labeling the batteries new on "2/2/2015" throws things off a bit.  If you want to download our multi-tool with voltage drop calculations, battery calcs, dB loss and battery date codes, click here.

For your reference I have included the NFPA 72 2013 edition code sections below:

Table 14.4.3.2 #9  Fire alarm batteries shall be replaced in accordance with the recommendations of the alarm equipment manufacturer or when the recharged battery voltage or current falls below the manufacturer's recommendations.

10.6.10.1.1 When the fire alarm batteries are not marked with the month/year by the manufacturer, the installer shall obtain the date code and mark the batteries with month/year of battery manufacture.

Make sure to join our Fire Alarms Online Facebook Group HERE.