Tuesday, October 1, 2013

UL Requires Site Specific 2-Wire Smoke Detector Compatability

Word on the street is that UL (Underwriters Laboratories) is stating new requirements for the certification in listing compatibility for 2-wire smoke detectors.  If you or your customers have a an FACP (fire alarm control panel) with 2-wire conventional smoke detectors you may be affected by this.

2-Wire i3 System Sensor Smoke DetectorIf you have the need to replace 2-wire smoke detectors on your existing fire alarm control panel and cannot find UL listed detectors, then you need to know this:   UL is toying with the idea of site specific testing for the certification in listing 2-wire smoke detectors.

What does this mean for you or your customers?

Answer:  In the case of an older panel that does not have 2-wire smoke detectors Listed for compatibility, you will have to pay UL to come out to the site and perform their testing.  Now this is not set in stone but it seems pretty crazy to me.  I am not sure of the pricing for this so-called certification process but I know one thing, "It can'y be cheap!".

At this point, you have to ask your customer or yourself, at what point do you seriously consider upgrading your fire life safety system?  I am reasonably sure the this testing process from UL will impact your customers budget as well as their schedule.

Like I said, earlier, this is just the word on the street and I cannot verify any of this information.  With that said, it is something to consider and look into if you are currently in this situation.

Wednesday, June 19, 2013

It is Illegal to Tamper with Fire Alarm Systems

Today I rode along with some of our technicians to perform an annual fire alarm inspection of a three story apartment complex with approximately 140 units. The system comprised of a Gamewell IF610-252 addressable fire alarm control panel with Wheelock notification devices. On the first floor there were 20 handicap units with addressable system smoke detectors (Apollo XP95-P) which activated a signal module for the notification appliance circuit within its designated unit.

Now, the addressable system smoke detectors in the handicap units were programmed to supervisory events for the purpose of central station monitoring and common area notification of the facility. However, the individual notification devices within the unit were supposed to activate if the photoelectric smoke detector was activated. Needless to say, this system was messed up. Some of the smoke detectors failed to activate the NACs and other actually activated the common corridor devices. We also found that the installing fire alarm company did not design the system with SYNC modules.

How this facility passed it original acceptance test is beyond me.

Tampering with Fire Alarms is illegal

On top of all of this we came across 4 units where the occupant had tampered with the fire alarm system mini horn within their living room. We had to remove the tape, cotton, plastic and whatever else they could find to suppress the sound from the devices and warn the occupants that it is a crime to tamper with fire alarm equipment. For your reference, the California Penal Code section for this is 148.4

It reads:

a) Any person who does any of the following is guilty of a misdemeanor and upon conviction is punishable by imprisonment in a
county jail, not exceeding one year, or by a fine, not exceeding one thousand dollars ($1,000), or by both that fine and imprisonment:

(1) Willfully and maliciously tampers with, molests, injures, or breaks any fire protection equipment, fire protection installation,
fire alarm apparatus, wire, or signal.

(2) Willfully and maliciously sends, gives, transmits, or sounds any false alarm of fire, by means of any fire alarm system or signal
or by any other means or methods.

(b) Any person who willfully and maliciously sends, gives, transmits, or sounds any false alarm of fire, by means of any fire
alarm system or signal, or by any other means or methods, is guilty of a felony and upon conviction is punishable by imprisonment in the state prison or by a fine of not less than five hundred dollars ($500) nor more than ten thousand dollars ($10,000), or by both that fine and imprisonment, if any person sustains as a result thereof, any of the following:

(1) Great bodily injury.

(2) Death.


If you are interested in taking the NICET CBT exam for fire alarms, then we have you covered!  We are now selling our CBT Levels 1 - 3 practice exam DVDs.  These DVDs are packed with tons of NICET CBT practice exams along with all code references as to where to find the answers.  We have also supplied the DVDs with all of the necessary NICET applications, CBT calculator demonstrations, links and more.  If you need more information, feel free to send an email.  You can find the link to purchase our DVDs on the top left section of each page on this site.