Showing posts with label voltage drop. Show all posts
Showing posts with label voltage drop. Show all posts

Monday, April 22, 2019

Voltage Drop For Fire Alarm Circuits

·     Code Requirement for Voltage Drop Calculations?

NFPA 72 2013 Edition Section 7.2.1 - "Where documentation is required by the enforcing authority, the following list shall represent the minimum documentation required for all fire alarm and emergency communication systems, including new systems and additions or alternations to existing systems.", Within this list, you will find #7, Battery Calculations  and #8, Voltage Drop Calculations.

Keep in mind almost all fire alarm control units are 24 volts DC.  Also note that there are a few fire alarm control panels that are 12 volt DC.  Now these panels are typically combination fire and burglar system.  Just remember that the calculations for NAC voltage drops are the same for these systems, however the cut off voltage for a 12 volt system will be roughly half that of a 24 volt system.

·        What is the reason for voltage drop calculations?


NAC voltage drop calculations are critical for determining if your notification appliances will in fact work with the provided head end equipment.  (This is of course based on the installation contractor installing the system per plans and noted wiring distances).  If you perform your NAC voltage drop calculations correctly at the time of design, you will know exactly how many remote power supplies and NAC circuits are needed as well as the wall space requirements and 120 VAC connections required by the electrical contractor.  Keep in mind that this is a requirement of NFPA 72.

·         Voltage Drop Calculation Methods


There are primarily two methods to perform a NAC voltage drop calculation.  These methods are better known as “Point to Point (PTP)” and “End of Line (EOL)”.

·       Point to Point Voltage Drop requires much more math than the “EOL” method.  However, the extra work pays off as this method is more accurate.
  •          Designers generally use this method with a spreadsheet as the math can become tedious
  •          This is the method typically used by panel manufacturers within their own calculation programs
  •          Since it is less conservative of the “EOL” method, it allows for more devices on a circuit.
  •          There are cases of a 30% difference between the PTP and EOL methods
End of Line method is the easiest, quickest calculation
  •          Can be done easily by hand or with a calculator
  •          Results are less accurate that provide lots of head room for future expansion
Did you know the 2021 International Fire Code now requires 120 VAC single and multiple station smoke alarms to produce a 520 Hz low frequency audible tone? 

Starting Voltage and Cut-Off Voltage


UL (Underwriters Laboratories) 864, 9th Edition Standards for Fire Alarm Control Panels:
  •          All panels must have a demonstrated 20.4 VDC panel cut off voltage.

You may be asking, “Where did they come up with 20.4 VDC on a 24 Volt system?”

It is actually quite simple.  20.4 VDC is 85% of 24 VDC. Or like we stated earlier, there are a few 12 VDC systems floating around.  In their case, the demonstrated voltage shall be 10.2 VDC.  Once again, 10.2 VDC is 85% of 12 VDC.

Now, above we mentioned a term “Cut-Off Voltage”.  All fire alarm control units (FACU) have and internal voltage drop.  The voltage at the actual NAC output terminal is always less than 20.4/10.2 volts at cut-off.
  •          This amount of drop varies with every panel.  The variance can be as much as .5 VDC to 2.5 VDC.

Keep in mind that this value is not often found within the panel documentation.  I have found that the easiest way to obtain this value is to contact the panel manufacture and get it in writing.

You now may be asking yourself, “Why is it so critical that I get this value from the manufacturer and not just use the 20.4/10.2 value figured from the 85% set forth by UL 864 9th Edition?”

In order for your NAC voltage drop calculations to be precise and as accurate as possible based on the facts and information provided, you must use the specific panel/power supply terminal cut-off value.

How to determine your NAC Voltage Drop using the End of Line method:

Step #1
Add up the total current draw for your entire notification appliance circuit.  This is based on the manufacture, type (strobe only, horn/strobe, mini horn, audible level, wall, ceiling, etc.)  Make sure to consult with the appliance documentation to get these figures.

Step #2
Add up the total wire length for the run and multiple it by 2 (if class B).  The 2 represents the number of conductors used in the run.

Step #3
Multiply the total wire length times the wire resistance value per foot for a total circuit wire resistance.  The wire resistance per foot can be found in Table 8 “Conductor Properties” in Chapter 9 of the National electrical Code.

Step #4
Using Ohm’s Law we know that Current (I) x Resistance (R) = Voltage (E).  Simply take the total current found in step #1 and multiply it by the resistance found in Step #3.  This will give you the volts dropped.

Step #5
Subtract the volts dropped from the panel/power terminal cut-off voltage to obtain the voltage that will be supplied to the last appliance on the circuit.  This value MUST exceed 16 volts.

Keep in mind that this method is not as accurate as the Point to Point method.  This method assumes that the voltage drop at each appliance will be the same when in reality, they are not.

NEC Table 8 Conductor Properties

Below is an example of an End of Line voltage drop calculation:


End of Line Voltage Drop Fire Alarm

Diagram notes:
  • ·        We will assume that the terminal cut-off voltage is .5 volts below the 20.4 VDC giving us a voltage of 19.9.
  • ·         Use the wire lengths shown in the diagram
  • ·         V1=85mA / V2=75mA / V3=115mA / V4=100mA
  • ·         The circuit is using #12 AWG wire
  • ·         Use the Table 8 of the NEC (National Electric Code) provided previously in this document

Using the Diagram and notes above, can you provide the voltage drop for this circuit using the End of Line method?  Give it a try and when you are ready move on to the next page where we will break it down for you.

End of Line Voltage Drop Calculation Break Down:

Step #1
Add up the total current for all four notification appliances within the circuit.  We know that V1 = 85 mA, V2 = 75 mA, V3 = 115 mA and V4 = 100 mA.  The total of all four of these is 375 mA.

Step #2
Add up the total wire length and multiply it by 2.  We know based on the diagram that the first section is 200 feet, the second section is 150 feet, the third section is 25 feet and the final section is 70 feet.  This totals up to 445 feet x 2 = 890 Total Feet

Step #3
We know from the Table 8 “Conductor Properties” we have a value of 1.98 Ohms/1000 feet of #12 AWG stranded uncoated wire.  To find our resistance for our circuit simply take the total wire length (890 Feet) and divide it by 1000.  This gives us a value of .89.  Now take .89 and multiply it by the 1.98 value found in the NEC Table.  (.89 x 1.98 = 1.7622 Ohms of Resistance)

Step #4
Using Ohm’s Law we know that Current (I) x Resistance (R) = Voltage (E).  Take the total current found in Step #1 (.375) and multiply it by the total found in Step #3 (1.7622).  .375 x 1.7622 = .660825 volts dropped.

Step #5
Finally we need to subtract the .660825 volts from our terminal cut-off voltage.  We know from the previous diagram and notes that we have a terminal cut-off voltage of 19.9 volts.  19.9 volts - .660825 = 19.239 Volts at the last appliance.

Point to Point Voltage Drop Calculation Break Down:

Point to Point Voltage Drop Calculation

Diagram notes:
  • ·         We will assume that the terminal cut-off voltage is .5 volts below the 20.4 VDC giving us a voltage of 19.9.
  • ·         Use the wire lengths shown in the diagram
  • ·         V1=85mA / V2=75mA / V3=115mA / V4=100mA
  • ·         The circuit is using #12 AWG wire
  • ·         Use the Table 8 of the NEC provided previously in this document

Calculation Breakdown:

To perform a point to point voltage drop calculation is basically the same as the End of Line method however; we are going to do a breakdown of each path/appliance.

Calculation #1
  • ·         First wire run section resistance multiplied by the total current for appliance V1, V2, V3 and V4
  • ·         Subtract the total from the terminal cut-off voltage to get the voltage drop for V1.

Calculation #2
  • ·         Second wire run section resistance multiplied by the total current for appliances V2, V3 and V4.
  • ·         Subtract the total of V1 from the terminal cut-off voltage to get the voltage drop of V2

Calculation #3
  • ·         Third wire run section resistance multiplied by the total current for appliances V3 and V4.
  • ·         Subtract the total of V2 from the terminal cut-off voltage to get the voltage drop of V3

Calculation #4
  • ·         Fourth wire run section resistance multiplied by the total current for appliances V4.
  • ·         Subtract the total of V3 from the terminal cut-off voltage to get the voltage drop of V4

If this last value is greater than 16 volts, the circuit should work.

Using the Diagram and notes above, can you provide the voltage drop for this circuit using the Point to Point method?  Give it a try and when you are ready move on to the next page where we will break it down for you.

Calculation # 1
  • ·         200 Feet x 2 = 400 Feet.  400 / 1000 = .4 x 1.98 = .792 Ohms (From the FACU to V1)
  • ·         .792 x .375 (Current of all Appliances) = .297 volts dropped @ V1
  • ·         19.9 (Terminal Cut-Off Voltage) - .297 = 19.603 VDC @ V1

Calculation #2
  • ·         150 Feet x 2 = 300 Feet.  300 / 1000 = .3 x 1.98 = .594 Ohms (From the FACU to V1)
  • ·         .594 x .290 (Current of Appliances V2-V4) = .17226 volts dropped @ V2
  • ·         19.603 (Terminal Cut-Off Voltage) - .17226 = 19.43074 VDC @ V2

Calculation # 3
  • ·         25 Feet x 2 = 50 Feet.  50 / 1000 = .05 x 1.98 = .099 Ohms (From the FACU to V1)
  • ·         .099 x .215 (Current of Appliances V3-V4) = .021285 volts dropped @ V3
  • ·         19.43074 (Terminal Cut-Off Voltage) - .021285 = 19.40946 VDC @ V3

 Calculation # 4
  • ·         70 Feet x 2 = 140 Feet.  140 / 1000 = .14 x 1.98 = .2772 Ohms (From the FACU to V1)
  • ·         .2772 x .200 (Current of Appliance V4) = .05544 volts dropped @ V4
  • ·         19.40946 (Terminal Cut-Off Voltage) - .05544 = 19.35402 VDC @ V4

Both of these calculations are commonly used and widely accepted by your local AHJs.  As you can see the PTP method came up with a total voltage drop of 19.35402 while the EOL method came up with 19.239.  Remember both of these examples used the same parameters.  I personally recommend using the Point to Point method purely based on its accuracy.

Thursday, March 12, 2015

Voltage Drop for Fire Alarm Systems

Fire Alarm Voltage Drop Calculations

All electrical conductors include a small amount of resistance.  This resistance increases if the length of the conductor increases or or the conductor size decreases.  Think of blowing air through a hose. If the hose diameter decreases and or the length increases it would be harder to blow through.  You can also think of freeway traffic as resistance.  The freeway is the conductor.  The wider the freeway, the faster and smoother you travel.

Fire Alarm Voltage DropAs electrical current flows through the conductor it will experience a decrease in voltage between the source (starting point) and at various points along the conductor path.  Another example to look at is the voltage drop in a 1000 foot run of 16 AWG wire would be greater than that of a 1000 foot run of 12 AWG.  This is simply because a 16 AWG conductor is smaller in diameter than a 12 AWG conductor.

Fire alarm equipment LISTED to the standards of the National Fire Protection Association and Underwriters Laboratories (U.L.) is tested to determine if can operate properly at 85% of the rated nameplate voltage.  This limit was set in place to make sure the circuit can deal with a "brownout" condition or a possible voltage drop which might result from excessive resistance in the system wiring.

As required in the CFC (California Fire Code), fire alarm designers are required to prepare voltage drop calculations for the notification appliance circuits (NAC) as part of the design.  These voltage drop calculations must be included in the submittal plans and specifications.  This is to assure that the devices on the system are supplied with electrical power within the operating voltage range.

You as a designer can use several different methods to calculate voltage drop on a fire alarm circuit. One method calculates the actual voltage drop for each length of cable and device within the circuit and the other calculates the overall voltage drop.  Either method will have slightly different results but should be acceptable by your local AHJ (authority having jurisdiction)

The suggested maximum allowable voltage drop on a fire alarm circuit is 10% or the voltage drop included in the fire alarm control panel installation guide, whichever is less.


"Lump Sum Method"


Step #1)  Take the total current of the circuit.  You can achieve this figure by adding up the current draw of each device on the circuit.  This will represent "A"

Step #2)  Measure out the length of the circuit in feet.  Do not double the distance of the circuit for 2 wire loops unless you want to use a multiplying factor of 10.8 versus 21.6 (see step #3).  This will represent "L"

Step #3)  Use a multiplying factor of 21.6.  This number represents the resistivity of copper conductors.  This is a constant used in the formula.

Step #4)  Find the Circular Mils for the particular gauge wire you are using.  This can be found in the National Electrical Code (NEC) chapter 9 table 8.  #14 AWG is 4110 and #12 AWG is 6530.  This will represent "C.M".

A x L x 21.6
-------------  =   VD
C.M.

Example

.356 x 450' x 21.6
-------------------   =   0.530 Volts Dropped
6530

To find the percentage of voltage dropped do the following:
0.530 / 24 = 0.022
0.022 x 100 = 2.2
= 2.2% Voltage Drop

Now remember you can also perform this calculation for each individual length of wire and device on the circuit.  This is known as the "point-to-point" method.  This is a better way to perform the calculation as it gives you a chance to really break down the circuit and pin point exactly where a circuit must end do to voltage drop.  Simply use the above formula for each wire run and add the voltage drop totals for each circuit section together for the total voltage drop.  Then divide by the source voltage (in this example we will use 24VDC) and then multiply by 100 to come to a total voltage drop percentage.

I will be adding info in the near future on the calculations for the "point-to-point" method using Ohm's Law

Be sure to join our Facebook group and join in on the conversation.