Showing posts with label 520 Hz Sounders. Show all posts
Showing posts with label 520 Hz Sounders. Show all posts

Saturday, February 18, 2023

520 Hz Fire Alarm Requirements for R-1 & R-2 | 2021 IFC Update

520 Hz low-frequency fire alarm notification is one of the most important requirements to understand when designing fire alarm systems for hotels, apartments, condominiums, dormitories, and other occupancies containing sleeping areas.

The requirement can affect both the building fire alarm system and the audible signal produced when single- or multiple-station smoke alarms activate within applicable dwelling units and sleeping units.

Quick Answer:
The 2021 International Fire Code introduced a major new requirement for applicable Group R-1 and R-2 sleeping rooms: activation of single- or multiple-station smoke alarms must result in a 520 Hz low-frequency audible signal where the building is required to have a fire alarm system. Later code editions continue this basic requirement.

When Did the 520 Hz Smoke Alarm Requirement Start?

The 2021 International Fire Code was the first IFC code cycle to introduce the specific requirement addressing the audible signal produced by single- and multiple-station smoke alarms in applicable Group R-1 and Group R-2 sleeping rooms.

The requirement appeared in 2021 IFC Section 907.5.2.1.3.2.

Under that section, where a Group R-1 or R-2 occupancy is required by the applicable occupancy provisions to have a fire alarm system, the audible alarm signal initiated by the smoke alarms within the dwelling unit or sleeping unit must be a 520 Hz signal complying with NFPA 72.

If the smoke alarm itself cannot produce the required low-frequency signal, the code allows that signal to be provided by:

  • A listed notification appliance, or
  • A smoke detector with an integral 520 Hz sounder
Code History:
Before the 2021 IFC, fire alarm designers were already dealing with NFPA 72 low-frequency sleeping-area notification requirements for building fire alarm systems. The significant 2021 IFC change was the specific requirement tying the activation of in-unit smoke alarms in applicable R-1 and R-2 occupancies to a 520 Hz audible signal.

What Is a 520 Hz Low-Frequency Fire Alarm Signal?

A 520 Hz low-frequency alarm signal is intended to improve the ability of sleeping occupants to awaken during a fire emergency.

Traditional fire alarm horns and residential smoke alarms have historically produced higher-frequency audible signals. Modern codes and standards recognize that lower-frequency notification can be more effective for sleeping occupants and certain higher-risk populations.

NFPA 72 establishes requirements for listed low-frequency notification equipment used in sleeping areas.

Important:
A Temporal 3 evacuation pattern and a 520 Hz low-frequency signal are not the same thing. Temporal 3 describes the timing pattern. The appliance must also be listed to produce the required low-frequency waveform.

2021 IFC 520 Hz Requirement for the Building Fire Alarm System

The IFC separates low-frequency sleeping-room notification into two concepts.

The first applies to the building fire alarm system.

Under the IFC framework, audible notification activated by the building fire alarm system in applicable Group R-1 and R-2 sleeping rooms must provide a 520 Hz low-frequency signal complying with NFPA 72.

Depending on the approved design, this can be accomplished using equipment such as:

  • Listed 520 Hz horns
  • Listed 520 Hz horn/strobes
  • Compatible smoke detector sounder bases
  • Other listed low-frequency notification appliances

2021 IFC 520 Hz Requirement for Smoke Alarm Activation

The second concept is the one that made the 2021 IFC especially important.

In applicable Group R-1 and R-2 sleeping rooms where the occupancy is required to have a fire alarm system, activation of single- or multiple-station smoke alarms within the dwelling unit or sleeping unit must result in the required 520 Hz audible signal.

This created a major design and estimating issue because traditional 120 VAC residential smoke alarms typically did not produce the required low-frequency waveform.

The code therefore recognizes alternative ways to provide the required signal when the smoke alarm itself cannot do so.

520 Hz fire alarm requirements showing sleeping areas in Group R-1 hotel rooms and Group R-2 apartments
520 Hz low-frequency notification applies to applicable sleeping areas in Group R-1 and R-2 occupancies. Bedrooms, hotel guest rooms and other sleep-capable spaces should be evaluated carefully.

What Does NFPA 72 Consider a Sleeping Area?

The sleeping-area concept is broader than simply looking for a room labeled Bedroom on the architectural plans.

The intent is to protect spaces intended for sleeping as well as areas where occupants could reasonably sleep.

Depending on the floor plan, these areas can include:

  • Bedrooms
  • Hotel guest rooms
  • Living rooms
  • Spare rooms
  • Dens
  • Other spaces reasonably capable of being used for sleeping
Example:

A one-bedroom apartment contains a bedroom, living room, kitchen, bathroom, and entry hallway.

The bedroom clearly qualifies as a sleeping area. The living room should also be evaluated because occupants could reasonably sleep there.

The kitchen, bathroom, and common building corridor do not automatically become low-frequency areas simply because the building is residential.

Do Apartment Living Rooms Need 520 Hz?

They can.

A living room can fall within the sleeping-area provisions where it is a space in which occupants could reasonably sleep.

This is why simply installing a 520 Hz appliance in each room labeled “Bedroom” should not automatically be assumed to satisfy the entire sleeping-area requirement.

Do Apartment Corridors Need 520 Hz?

Not solely because the building contains sleeping units.

Common corridors, elevator lobbies, stairways, and similar tenantless spaces are evaluated under their applicable general fire alarm notification requirements.

The low-frequency sleeping-area requirement is aimed specifically at areas where occupants are sleeping or could reasonably be sleeping.

Group R-1 Hotels and Motels

Group R-1 typically includes transient residential occupancies such as:

  • Hotels
  • Motels
  • Transient boarding houses
  • Other similar transient sleeping occupancies

Guest sleeping rooms should be evaluated for low-frequency notification where the applicable fire alarm requirements apply.

Other portions of the building such as corridors, lobbies, meeting rooms, restaurants, and service areas are evaluated separately.

For more information:

Fire Alarm Requirements for Group R-1 Occupancies

Group R-2 Apartments, Condominiums and Residential Buildings

Group R-2 commonly includes:

  • Apartments
  • Condominiums
  • Dormitories
  • Student housing
  • Other permanent residential occupancies

These projects require careful coordination between the building fire alarm system and the residential smoke alarm design.

Items that may need to be coordinated include:

  • 520 Hz audible notification
  • 120 VAC smoke alarms
  • System smoke detectors
  • Visible notification
  • Secondary or emergency power
  • Accessible dwelling units
  • Electrical and fire alarm trade responsibilities

For more information:

Fire Alarm Requirements for Group R-2 and R-2.1 Occupancies

Four Common Ways to Meet the 520 Hz Requirement

There is more than one way to design a compliant low-frequency sleeping-area notification system.

The correct method depends on the occupancy, fire alarm system, smoke alarm arrangement, accessibility requirements, selected equipment, listings, project specifications, and AHJ approval.

Option 1: Listed 520 Hz fire alarm notification appliance

Option 2: Addressable system smoke detector with integral 520 Hz sounder base

Option 3: Listed 120 VAC smoke alarm capable of producing the required 520 Hz audible signal

Option 4: Listed combination equipment incorporating low-frequency audible notification and integral visual notification where approved for the required application
Four ways to meet 520 Hz fire alarm requirements using low frequency notification appliances, sounder bases, 120 VAC smoke alarms and visual notification
Common design approaches for meeting applicable 520 Hz low-frequency sleeping-area requirements. Verify equipment listings and project-specific code requirements before design.

Option 1: Listed 520 Hz Fire Alarm Notification Appliance

The first method is to provide listed low-frequency fire alarm notification appliances within the required sleeping areas.

These can include:

  • Low-frequency horns
  • Low-frequency horn/strobes
  • Other listed 520 Hz notification appliances

These devices are typically controlled directly by the building fire alarm system.

Option 1 Design Considerations

  • Confirm the appliance is listed for the required low-frequency waveform.
  • Verify audible performance at the sleeping location.
  • Determine whether visible notification is also required.
  • Calculate NAC loading and voltage drop.
  • Verify synchronization requirements.
  • Determine how activation of the residential smoke alarm will initiate the required low-frequency signal where applicable.

For additional information:

Low-Frequency Sounders for Fire Alarm Systems

Option 2: System Smoke Detector With Integral 520 Hz Sounder Base

A second approach is to use an addressable system smoke detector with a compatible listed low-frequency sounder base.

This can combine system smoke detection and low-frequency audible notification at the same general device location.

Addressable smoke detector with integral 520 Hz low frequency sounder base

Option 2 Design Considerations

  • Provide the required signaling line circuit.
  • Provide sounder-base power or notification circuit as required.
  • Verify sounder-base power supervision.
  • Confirm detector, base, and panel compatibility.
  • Account for additional system power loading.
  • Evaluate visible notification separately.
  • Verify whether system detectors are permitted to replace required smoke alarms for the specific project.
Important:
Do not automatically remove required single- or multiple-station smoke alarms simply because system smoke detectors are being installed. Verify the applicable IFC, IBC, NFPA 72, residential code, equipment listing, and local requirements.

Option 3: Listed 120 VAC Smoke Alarm With a 520 Hz Sounder

When the 2021 IFC requirement first appeared, one of the industry's biggest challenges was the limited availability of listed 120 VAC single- and multiple-station smoke alarms capable of directly producing the required low-frequency audible signal.

That product landscape has changed.

Listed hardwired residential smoke alarm products incorporating low-frequency audible technology are now available.

Gentex PLACE hardwired smoke alarm with low frequency sounder

Advantages of This Approach

  • The residential smoke alarm can potentially provide the required low-frequency audible signal directly.
  • The electrical contractor can maintain a more traditional hardwired smoke alarm installation method.
  • The design may reduce the number of separate fire alarm appliances required solely for in-unit audible notification.
  • Fire alarm and electrical scope coordination may be simplified.

Items That Must Be Verified

  • Exact product listing
  • Required low-frequency listing
  • Primary and secondary power
  • Smoke alarm interconnection
  • Required system interface
  • Visible notification requirements
  • Manufacturer instructions
  • AHJ acceptance

Option 4: Combination Smoke Alarm and Visual Notification Products

Another developing option is listed residential equipment that combines smoke alarm functions with integral visual notification.

For certain projects, especially accessible sleeping rooms, combining functions into fewer devices can simplify installation and coordination.

However, the exact listing matters enormously.

Do Not Assume Combination Means Compliant:
A smoke alarm may include an integral strobe but still use a conventional higher-frequency audible signal. Likewise, a 520 Hz smoke alarm may not include a visual appliance. Verify the exact product listing for both the audible and visual functions before specification.

What to Verify on a Combination Product

  • Does the audible portion produce the required 520 Hz low-frequency waveform?
  • Is it listed for the intended smoke alarm application?
  • What is the visual appliance candela rating?
  • Is the strobe listed for the required sleeping-room application?
  • How is the unit powered?
  • What happens during loss of normal power?
  • Does activation by the building fire alarm system operate the visual appliance where required?
  • Does activation of the in-unit smoke alarm operate the visual appliance where required?
Author's Note for California:
California has additional requirements involving visible notification, accessibility, equipment approval, and emergency power for certain 120 VAC smoke alarms with integral strobes. For California projects, verify the current California Fire Code, California Building Code, OSFM requirements, and the manufacturer's exact listing before using an integral-strobe solution.

For more information on the California-specific issue:

California OSFM Emergency Power Requirements for 120 VAC Smoke Alarms With Integral Strobes

Visible Notification in Accessible Sleeping Units

The 520 Hz audible requirement does not eliminate applicable visible-notification requirements.

Where visible notification is required, designers must separately verify:

  • Required candela
  • Mounting location
  • Activation sequence
  • Power source
  • Accessibility provisions
  • NFPA 72 requirements
  • Applicable IBC provisions
High candela fire alarm strobes for accessible residential sleeping units

520 Hz Sound Pressure Requirements

Using a listed low-frequency appliance is only part of the design.

The system must also provide the required sound-pressure level at the sleeping location.

Walls, doors, distance, appliance orientation, room configuration, and background sound can all affect the final audible level.

Design Reminder:
A device can produce the correct 520 Hz waveform and still fail the design if the required audible level is not achieved at the sleeping location.

520 Hz Versus Traditional Higher-Frequency Smoke Alarm Signals

Traditional residential smoke alarms commonly use higher-frequency audible signals.

When a conventional smoke alarm and a separate 520 Hz fire alarm appliance are installed in the same sleeping area, the designer should evaluate how the two audible sources operate together.

Potential issues include:

  • Different audible frequencies operating simultaneously
  • Independent activation sources
  • Synchronization
  • Conflicting audible signals
  • Manufacturer limitations
  • AHJ acceptance

The complete sequence of operations should be reviewed instead of assuming that multiple independently operating audible devices will automatically produce a compliant installation.

Does Every 120 VAC Smoke Alarm Need to Produce 520 Hz?

No.

The requirement does not apply to every residential smoke alarm in every building.

The applicable occupancy, fire alarm system requirement, sleeping-room configuration, IFC edition, locally adopted amendments, and project conditions determine whether the 520 Hz requirement applies.

520 Hz Design and Estimating Checklist

Before designing or estimating the project, confirm:

☐ What is the occupancy classification?

☐ Is the occupancy Group R-1 or R-2?

☐ Is a building fire alarm system required?

☐ Which areas qualify as sleeping areas?

☐ Could occupants reasonably sleep in living rooms or dens?

☐ Will the building fire alarm system provide 520 Hz notification?

☐ Will the residential smoke alarm itself provide the required 520 Hz signal?

☐ If not, how will smoke alarm activation initiate low-frequency notification?

☐ Will listed low-frequency horns or horn/strobes be used?

☐ Will system smoke detectors with low-frequency sounder bases be used?

☐ Will a listed 120 VAC low-frequency smoke alarm be used?

☐ Is visible notification required?

☐ Is an integral strobe being considered?

☐ What candela rating is required?

☐ Has sound pressure been verified at the sleeping location?

☐ Have doors, walls, and room geometry been considered?

☐ Have NAC and SLC loading been calculated?

☐ Have voltage-drop calculations been completed?

☐ Has product compatibility been verified?

☐ Have fire alarm and electrical scopes been coordinated?

☐ Has the exact product listing been reviewed?

☐ Has the locally adopted IFC/IBC edition been confirmed?

☐ Have local amendments and AHJ requirements been reviewed?

Common 520 Hz Design Mistakes

  • Assuming only bedrooms qualify as sleeping areas.
  • Ignoring living rooms and other sleep-capable spaces.
  • Assuming Temporal 3 automatically means 520 Hz.
  • Using a standard high-frequency horn in a required sleeping area.
  • Ignoring the smoke-alarm-initiated low-frequency requirement introduced in the 2021 IFC.
  • Failing to coordinate fire alarm and electrical contractor responsibilities.
  • Assuming every smoke alarm with a strobe also produces a listed 520 Hz signal.
  • Assuming every low-frequency smoke alarm includes compliant visible notification.
  • Failing to verify candela requirements.
  • Failing to verify audible performance at the sleeping location.
  • Failing to review product listings.
  • Using a newer product without verifying AHJ acceptance.
  • Failing to check locally adopted amendments.

520 Hz Frequently Asked Questions

What code cycle introduced the 520 Hz smoke alarm requirement?

The 2021 International Fire Code introduced the specific requirement addressing 520 Hz audible signaling initiated by single- and multiple-station smoke alarms in applicable Group R-1 and R-2 sleeping rooms.

What does 520 Hz mean?

520 Hz refers to the fundamental frequency of the required low-frequency audible waveform used for applicable sleeping-area notification.

Does Temporal 3 automatically mean 520 Hz?

No. Temporal 3 describes the alarm timing pattern. The equipment must also be listed for the required low-frequency waveform.

Do living rooms require 520 Hz?

They can where the space is reasonably capable of being used for sleeping.

Do common apartment corridors require 520 Hz?

Not solely because they are located in a residential building. Common areas are evaluated under their applicable general notification requirements.

Can a smoke detector with a low-frequency sounder base meet the requirement?

Yes, where the equipment is listed for the application and installed in accordance with the applicable code, NFPA 72, and manufacturer instructions.

Are 120 VAC low-frequency smoke alarms available now?

Yes. The product market has evolved significantly since the 2021 requirement was introduced, and listed hardwired residential products with low-frequency audible capabilities are now available.

Does an integral strobe automatically make a 120 VAC smoke alarm compliant?

No. The exact audible and visual listings, candela, power arrangement, activation sequence, and application must all be verified.

Related Fire Alarm Resources

Primary Code and Standard References

  • 2021 International Fire Code Section 907.5.2.1.3 – Audible signal frequency in Group R-1 and R-2 sleeping rooms
  • 2021 International Fire Code Section 907.5.2.1.3.1 – Fire alarm system low-frequency audible signal
  • 2021 International Fire Code Section 907.5.2.1.3.2 – Smoke alarm signal in sleeping rooms
  • International Building Code – Occupancy classification, accessibility, and related fire alarm provisions
  • NFPA 72 – Low-frequency audible notification and sleeping-area requirements
  • Manufacturer listing documentation – Product-specific installation, compatibility, power, candela, and operating requirements
Important: Fire alarm requirements vary by adopted code edition, occupancy, jurisdiction, project configuration, equipment listing, and local amendment. Always verify the locally adopted IFC, IBC, NFPA 72 edition, project documents, manufacturer instructions, and AHJ requirements before final design or installation.

Thursday, August 3, 2017

Low Frequency Sounders for Sleeping Areas

What are Low Frequency Sounders for Sleeping Areas?


Anyone in the fire alarm design and installation industry has more than likely heard the term low frequency sounders.  These newer sounders first appeared in the NFPA 72 2010 edition under section 18.4.5.3 and stated an effective date of January 1, 2014.  In short these are re-designed audible appliances for sleeping areas only!  Multiple studies have been performed on sleeping parties to see how they react in different scenarios.  Some of the scenarios involved older individuals who have a difficulty with their hearing,  others were individuals who are under the influence of narcotics.  The original thought was that these people would have a difficult time awaking from a sleeping state via the standard 3 Hz sound put out by a typical mini-horn commonly found in apartment and hotel sleeping areas.  The newer low frequency sounders have a square wave signal with 520 Hz plus or minus 10 percent.  Below are two links to show you the difference between the two sound outputs:

Listen to a 520HZ Low Frequency Tone

Listen to a 3 KHz Standard Tone 

Now that it is 2024, most of the country is currently enforcing the NFPA 72 2022 edition.  If your AHJ is enforcing the 2013 version of this standard, you have been required to provide these low frequency appliances in all sleeping areas for nearly 4 years.

Are you Installing Low Frequency Sounders Correctly?  


Now the same installation factors found in the NFPA 72 standard apply to low frequency sounders. They shall have a sound level of at least 15 dB over average ambient, 5 dB or maximum sound level (duration of at least 60 seconds) or 75 dB whichever is highest.  Now seeing that NFPA 72 2013 has been nice enough to provide us with a chart depicting average ambient sound levels for different types of occupancies, this cannot be used in lieu of actual readings taken at the site.  However we can take away from this chart that a residential occupancy has an average ambient sound level of 35 dB.  If we use this as an example and tack on the additional 15 dB per NFPA 72 2022 18.4.5.1, we only come up with 50 dB.  This is 25 dB lower than the required 75 dB per the same standard section.  An example of the only time you would be going higher than 75 db is a sleeping area with an average ambient sound level of 61 dB.  61 dB plus 15 dB = 76 dB.  In short, 99 percent of the time, a designer will be aiming to achieve 75 dB.

Occupancy Average Ambient Sound Level NFPA 72
NFPA 72 Occupancy Average Ambient Sound Levels
Tips to keep in mind:

  • If you double the power to the sounder, you will gain 3 dB
  • The dB from the appliance is measure at 10' away.  Every time you double the distance from the appliance, you loose 6 dB.  Read more here.


What Exactly is a Sleeping Area?


Seems like a pretty easy question to answer right?  Well I'll have you know this comes up a lot and more often than not, designers get it wrong!  A sleeping area is obviously associated with a bedroom and a bedroom is not classified as such unless it has a closet.  However, as defined by NFPA 72 2022 A.18.4.6.3, low frequency sounders are required for use in areas intended for sleeping (bedrooms) as well as areas that might be reasonably used for sleeping (Living Rooms).  Most apartments or hotel rooms are outfitted with a comfy couch in the living room.  It's not uncommon to find yourself falling asleep in this area.  This is what has prompted the requirement for low frequency sounders to be installed in not only the bedrooms but the living rooms as well. 

How Does this Affect my Design?  


It is pretty common knowledge that these 520 Hz low frequency sounders draw a lot more current than the standard 3 Hz mini-horns.  You will need to take this into effect when calculation voltage drop and battery calculations for the remote power supplies serving the areas in question.  Depending on the size of the project, this may mean you need additional notification appliance circuits and remote power supplies. 

Tuesday, December 20, 2016

Low Frequency Sounders for Fire Alarm Evacuation


Are Low Frequency Sounders Being Enforced by your AHJ


Is your jurisdiction enforcing the new code mandated 520 Hz low frequency sounders for fire alarm audibility yet?  If so how are you tackling this new requirement?  And finally did you know that the smoke alarms within the sleeping rooms and guest units do not need to meet the 520 Hz requirement?

When did this start?

System Sensor Low Frequency Sounder and Sounder StrobeNot a lot of people are aware that this requirement was originally noted in the (2010) NFPA 72 National Fire Alarm Code section 18.4.5.3.  It states "Effective January 1, 2014, where audible appliances are provided to produce signals for sleeping areas, they shall produce a low frequency alarm signal that complies with the following:
(1) The alarm signal shall be square wave or provide equivalent awakening ability.
(2) The wave shall have a fundamental frequency of 520 Hz +/- 10 percent.

Now we fast forward to 2013.

Note that the (2013) NFPA 72 Fire Alarm and Signaling Code requirements are the same found in Section 18.4.5.3

Now lets break it down.  There are a lot of code sections so stay with me.

The Annex A of NFPA 72 (2013) section A18.4.5.3 lets us know that this section does not cover the audible requirements of single and multiple station smoke alarms and instructs us to consult chapter 29 for said requirements.

If you refer to Chapter 29 "Single and Multiple-Station Alarms and Household Fire Alarm Systems" section 29.3.6 it states the following: "All audible fire alarm signals installed shall meet the performance requirements of 18.4.3, 18.4.5.1, 18.4.5.2 and 29.3.8."  Please notice that this section does not include section 18.4.5.3. This may lead one to believe that single and multiple station smoke alarms for dwelling units do not need to meet the new 520 Hz low frequency requirements.

The key section to pay attention to here is section 29.3.8 which states "Notification appliances provided in sleeping rooms and guest rooms for those with hearing loss shall comply with 29.3.8.1 and 29.3.8.2, as applicable."

Section 29.3.8.1 "Mild to Severe Hearing Loss.  Notification appliances provided for those with mild to severe hearing loss shall comply with the following:

(1) An audible notification appliance producing a low frequency alarm signal shall be installed in the following situations:

    (a) Where required by governing laws, codes, or standards for people with hearing loss.
    (b) Where provided voluntarily for those with hearing loss.

(2) The low frequency alarm signal output shall comply with the following:

    (a) The waveform shall have a fundamental frequency of 520 Hz +/- 10 percent.
    (b) The minimum sound level at the pillow shall be 75 dba, or 15 dba above the average ambient sound level or 5 dba above the maximum sound level having a duration of at least 60 seconds, whichever is greater."

Section 29.3.8.2 "Moderately Severe to profound Hearing Loss.  Visible notification appliances in accordance with the requirements of 18.5.5.7 and tactile notification appliances in accordance with the requirements of section 18.10 shall be required for those with moderately severe to profound hearing loss in the following situations:

(1) Where required by governing laws, codes, or standards for people with hearing loss.
(2) Where provided voluntarily for those with hearing loss.

What does this mean?  


Low frequency sounder internal view speaker coneIf we read section 29.3.8 very carefully you will notice the word "AND" between sleeping rooms and guest rooms for those with hearing loss.  This is telling us that the requirements of section 29.3.8.1 and 29.3.8.2 apply to ALL sleeping rooms including guest rooms for those hard of hearing.

How does this effect your design?

To this date there are no UL listed UBC smoke alarms that can produce an audible tone at 520 Hz.  In fact the only manufacture that has a UL listed 520 Hz low frequency sounder appliance is System Sensor.  This means no more mini horns in the sleeping rooms of R-1, R-2 and R-2.1 occupancies.  The only way to accomplish this is by installing a System Sensor HW-LF (low frequency sounder) or addressable smoke detector with low frequency sounder base in place of all mini horns.  This will give us the required 520 Hz in all sleeping areas during a general alarm condition.

How do we accomplish 520 Hz when the Single or multiple station smoke alarm is activated?

Since there is no such thing as a low frequency LISTED smoke alarm, I propose installing addressable system smoke detectors in all sleeping rooms and guest rooms.  On top of this an addressable control module will need to be installed for each residential unit.  The control module will then need to be wired so that it controls an individual NAC (Notification Appliance Circuit) for that particular unit.  Through programming we can activate this individual control module upon activation of any smoke detectors within the unit.  Lastly the control module for each unit will need to be mapped to activate during a general alarm condition.  This way we are activating the in room low frequency sounders via the in room smoke detectors as well as any building wide general alarm device.  This method allows us to accomplish the requirements of section 18.4.5.3 as well as 29.3.8 with listed equipment and methods.

How does this effect your final cost?

Obviously there is a lot more equipment needed to perform this requirement such as addressable system smokes and control modules.  On top of this the low frequency sounders are more expensive than mini horns.  Also note that the new low frequency sounders draw more current than mini horns which will decrease your total allowable appliances per NAC ultimately increasing the number of required remote power supplies.

This is going to be a huge adjustment for our industry which will ultimately comes with a large learning curve.  I suggest your contact your local AHJ (Authority Having Jurisdiction) and find out what their interpretations on this subject are.

Saturday, December 17, 2016

Strobes Flash When Fire Alarm Silenced

End Users, AHJs (Authority Having Jurisdiction) and Technicians seem to think that fire alarm strobes are required to continue flashing when the fire alarm control unit or panel is silenced.  


Fire Alarm LED Strobe LightsFACT #1:  There is not and never has been anything in the code that requires the fire alarm visual notification appliances AKA Strobes to continue flashing once the fire alarm control panel has been silenced.   

FACT #2:  NFPA 72 2013 Section 10.13.2: “When an occupant notification alarm signal deactivation means is actuated, both audible and visible notification appliances shall be simultaneously deactivated."

So Why did we have Strobes Flashing when the Fire Alarm System has been Silenced?



From what information I have been able to gather, this function crept into the minds of installers and inspectors sometime in the 1980's. The thought of having strobes continue flashing while firefighters validated the alarm condition was a plus.  Firefighters could communicate via their radios without the loud distraction caused by the audible signal.   Lastly, individuals looking to enter a facility would see the visual appliances flashing and know not to enter due to a potential threat of a fire.

This is an argument that comes up less as time moves forward, however, some people are stuck on the ability to have strobes continue flashing during a fire alarm system silence.  Please note that while NOT required by any code or standard, this can still be required within a particular building specification or City Ordinance.

The function can be done by most manufacturers and is not hard to accomplish.  However, it does not make sense to have it enabled and that is why you will not find it in any code references.  Strobes where brought into the code for ADA adaptability.  With that said, does it make sense to leave the strobes flashing if you silence the fire alarm?

Ask yourself, "How is a deaf person affected by this feature?".

When a fire alarm system is activated, a hearing impaired individual will see the strobes flashing but NOT hear the audible tone.  Once the fire alarm panel has been silenced and the audible tone is cut off, this individual has no idea the fire department is on scene, the system as been silenced and the event is being investigated.  To this individual there is still an active evacuation scenario in place until the fire alarm panel has been reset.

Ask yourself, "How is a blind person affected by this feature?".

When a fire alarm system is activated, a visually impaired individual will NOT see the strobes flashing but will hear the audible tone.   If the fire alarm system is silenced and the audible tone is cut off, this individual will have no idea there is still a potential treat in the building.  They could potentially return to their business when in fact there is an active fire alarm investigation occurring in their close proximity.  Another point noted above was the ability for flashing strobes to notify individuals to not enter a building as it is being investigated for a fire.  If you are blind, you would not be aware the fire alarm system is activated and under investigation.  The blind individual could potentially walk right into harmful or fatal situation.  

In my mind this is why NFPA 72 2013 directly addresses this situation in section 10.13.2.  If we agree to just cut off both audible and visual signals in the event of a system silence, we are not favoring or discriminating against anyone with or without a disability.

Join our Facebook Group for up to the minute fire alarm system here.

Have you freshened up on the newer fire alarm LED strobe technology?

Tuesday, December 13, 2016

Fire Alarm Requirements for Group R-1 Occupancy

Group R-1: (Residential)


Systems required to be monitored per the 2021 IFC section 907.6.6.

A manual fire alarm system (manual fire alarm boxes) that activates the occupant notification system (horns, strobes, sounders, speakers, chimes, mass notification, etc.)

Manual Fire Alarm Box Requirements:

Manual fire alarm boxes are not required if the facility is two stories or less in height and all individual sleeping units and contiguous attic and crawl spaces to the sleeping units are separated from one another and public/common spaces by a minimum of 1-hour partitions.  Each sleeping unit must also have a direct exit to a public way, egress court or yard.

Manual fire alarm boxes are not required to be installed when ALL of the following conditions exist:

#1: The Group R-1 facility is equipped with an automatic sprinkler system installed in accordance with section 903.3.1.1 or 903.3.1.2. 

#2: The occupant notification systems will activate upon sprinkler water flow.

#3: At minimum one manual fire alarm box is installed at an approved location.


2021 IFC section 907.2 - If the facility is provided with an approved automatic sprinkler system in which the Waterflow activates the occupant notification system a minimum of one (1) manual fire alarm box is required to be provided in an area approved by the local AHJ (Authority Having Jurisdiction).
Exceptions:
#1: The manual fire alarm box is not required for fire alarm systems dedicated to elevator recall control and supervisory service.
#2: The manual fire alarm box is not required for group R2 occupies unless required by the fire code official to provide a means for fire watch personnel to initiate an alarm during a sprinkler system impairment event. Where provided, the manual fire alarm box shall not be located in an area that is open to the public.

UL 268 Automatic Smoke Detection Requirements:

System smoke detectors shall be provided for all of the following applications:

Above control panels and power supplies
For the purpose of elevator capture
On all HVAC units over 2,000 CFM (Duct Detector)
For releasing service
Fire Smoke Dampers
Delayed egress locks

Automatic smoke detectors are required to be installed in all interior corridors serving the sleeping units.

Exception:

Automatic smoke detectors are not required to be installed in interior corridors if the building does not contain interior corridors serving the sleeping units where all sleeping units have a means of direct exit access to the exterior.

UL 217 Smoke Alarm Requirements:

Low frequency sounders for fire alarms in sleeping areas
Single or multiple station smoke alarms shall be installed in all of the following areas:

Sleeping areas.

Each room in the path of the means of egress from sleeping area to the door leading to the sleeping unit.

On each level within the sleeping unit.  This includes basements.  If the sleeping unit has split levels without a door separation, one smoke alarm on the upper level will suffice.  Note this is only for slip level where the distance between levels is less than one full story.

Fire Alarm Notification Requirements:

520 Hz low frequency sounders shall be installed in all sleeping areas.  Horns can be provided in common areas including but not limited to corridors, public restrooms, elevator lobbies, etc.  Emergency voice/alarm communications systems shall be provided for high rise applications.  High rise buildings are classified by the International Building Code as a structure that has occupied floors located more than 75 feet above the lowest level of fire department vehicle access.

Note:  R-1 occupancies have a required amount of handicap accessible rooms that need to be provided with visible appliances.  This requires sounder/strobes, horn/strobes or speaker/strobes in the sleeping rooms and living rooms as well as a strobe in the restrooms.  Keep in mind that the strobe located in sleeping areas shall be 110 candela if the top of the lens is greater than or equal to 24 inches from the ceiling.  If the top of the lens is 23 inches or closer to the ceiling you shall provide a setting of 177 candela. ** These visible alarms shall activate upon system smoke detectors or single or multiple station smoke alarms.

** Use the ADA Room tool found in the main menu of this application to determine the quantity of accessible rooms you need to include in your design.

ADA Room Fire Alarm Strobe Chart

Using a sound pressure meter or dB Meter, verify you comply with the following:

Public Mode Audibility: You must have 15 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.

Private Mode Audibility: You must have 10 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.

Wednesday, March 18, 2015

Pre-Wire for ADA Adaptability in R2 Occupancies

What does it mean to pre-wire for future ADA adaptability?

The 2021 International Fire Code or IFC is where we look to find out what fire alarm requirements to follow when designing systems.  Specifically Chapter 9 "Fire Protection Systems".  If we dive deeper into section 907, we are informed as to what is required for each occupancy group.

For this article, we will be reviewing the requirements for an "R-2" occupancy.  As defined in the International Building Code or IBC, an R-2 group occupancy consists of: "occupancies containing sleeping units or more than 2 dwelling units where the occupants are primarily permanent in nature, including: Apartments Houses, Boarding House with more than 16 occupants, Convents, Dormitories, Fraternities and Sororities, Hotels (non-transient), Live/Work units, Monitories, Motels (non-transient), Vacation timeshare properties."

Since this article revolves around the requirements to pre-wire for future visual alarms, we will stay away from discussing the initiating side of the code.  Full requirements for an R-2 occupancy.

International Fire Code Section 907.5.2.3.3 Pre-Wire for Group R-2


Section 907.5.2.3.3 states "In group R-2 occupancies required by section 907 to have a fire alarm systems, all dwelling units and sleeping units shall be provided with the capability to support visible alarm notification appliances in accordance with Chapter 10 of ICC A117.1.  Such capability shall be permitted to include the potential for future interconnection of the building fire alarm systems with the unit smoke alarms, replacement of audible appliances with combination audible/visible appliances. or future extension of the existing wiring from the unit smoke alarm locations to required locations for visible appliances."

This is a major upgrade in comparison to a group R-1 occupancy such as Hotels and Motels.  In these facilities, the code gives us parameters as to how many rooms with visible alarms are needed based on the total quantity of sleeping units.

"So what does all this mean?"

In basic terms all living spaces within a group R-2 occupancy must contain the necessary wires, raceways and boxes to support the ability to upgrade to audible and visual notification throughout. ADA aside, our design must provide at least 75 dB in all areas of the quest room.  On top of this, your jurisdiction may now be requiring the fire alarm occupant notification to produce a 520Hz low frequency tone in all sleeping areas.  Find out more about 520Hz requirements.

A lot of fire alarm designers are confused to the actual requirements of this code section.  To be clear, it is the intent of the code to have a fully functional low frequency audible occupant notification system that can be upgraded with visual alarms without cutting walls, adding boxes or running new conduit.  All of the necessary wire or a conduit raceway must be in place to all living spaces, sleeping rooms and bathrooms within each living space.  As stated in the paragraph above, we need a minimum of 75 dB throughout the space.  To achieve this, it's typical to have a low frequency audible appliance in each sleeping room as well as the living space.  This design makes it easy to just swap out the low frequency sounder appliance for a combination low frequency and visual appliance. Don't forget that you will need a box and wire to each restroom within the guestroom.            

ADA section 4.28 "Alarms" gives us the requirements for visual appliances within ADA compliant areas.  Pay close attention to section 4.28.4 "Auxiliary Alarms" Units and sleeping accommodations shall have visual alarms connected to the building emergency alarm system or shall have a standard 110-volt electrical receptacle into which such an alarm can be connected and a means by which a signal from the building emergency alarm system can trigger such an auxiliary alarm.  When visual alarms are in place the signal shall be visible in all areas of the unit or room. Once a group R-2 living unit is upgraded to meet ADA requirements for visual alarms, you will need a low frequency audible tone of at least 75 dB throughout as well as visual alarms in all areas of the living unit.  This includes restrooms.

Side note: NFPA 72 2022 Table 18.5.5.10.3 informs us of the candela rating required visual appliances installed in  sleeping areas.

Distance from the ceiling to the top of the visual appliance lens:
> or = to 24 inches = 110 Candela
< 24 inches = 177 Candela

This standard was put in place as smoke migrates to the ceiling in the event of a fire.  It is common sense that a more intense strobe flash would be required to shine thorough the thicker smoke found closer to the ceiling and still have the ability to awake a sleeping occupant.  This is why we are required to install a 177 candela strobe when located less than 24" from the ceiling.

Best installation method to accomplish ADA adaptability for Group R-2 occupancies.


Run a trunk run down the corridor with Notification Appliance Circuit (NAC) loops as well as a Signaling Line Circuit (SLC) pulled into a J-Box within the closet of each living unit.  It is best to pick the closet that contains the unit's breaker panel.  From this J-Box pull your notification circuit loop through all appliance locations.  In the event the room needed to become adaptable, simply splice your incoming/outgoing NAC loop through in the J-Box.  This way the notification field wiring loop within the living unit is separate from the rest of the existing building NAC circuits.  Install a single output remote power supply listed for fire within the closet and power up with a dedicated 120 AC circuit.  Use the SLC in the closet to install an addressable smoke detector and control module to protect and activate the power supply.  See the example layout below:


Group R-2 ADA Adaptability for Fire Alarm


Now keep in mind that these audible / visual notification appliances will need to activate via general alarm, floor alarm or an alarm from within the unit itself.  To activate the notification appliances from within the living unit, you could either install addressable system smoke detectors or connect addressable mini modules to the 120 VAC UBC smoke alarms.  The detectors or modules would activate the control module connected to the power supply as well as indicate a supervisory condition on the fire alarm control unit (FACU).

Tuesday, March 17, 2015

Are Low Frequency Sounders Required by Your AHJ

520Hz Low Frequency Sounders 

"Effective January 1st 2014, audible appliances provided for the sleeping areas to awaken occupants shall provide a low frequency alarm signal that complies with the following:  (1) The alarm signal shall be square wave or provide equivalent awakening ability.  (2) The wave shall have a fundamental frequency of 520 Hz +/- 10 percent."

We got a glimpse of the future requirement in the 2010 Version of NFPA 72 section 18.4.5.3 page 102.  Here we could see that come January 1st 2014, there would be a requirement for fire alarm designers to use a 520Hz square wave low frequency sounder within all sleeping areas.  There have been multiple studies performed that validate the belief that a 520 Hz low frequency audible tone will have a greater chance at awakening a sleeping occupant.  The lower frequency also has greater chances of awakening people whom are intoxicated or hard of hearing.

Lets fast forward to the 2016 edition of the standard.  NFPA 72 version 2016 notes the same requirement in section 18.4.5.3 page 112.

Click to listen to a 520Hz Low Frequency sound file.  Or a 3KHz tone typically used prior to 520Hz requirements.

Now, here we are in the year 2016 and yet not everyone is following this standard.  You may ask yourselves why is our AHJ or authority having jurisdiction not requiring our fire alarm installation company to install the new 520Hz low frequency sounders for sleeping areas.  Keep in mind that the particular state you install fire alarms in may have an older code adopted.  Click to learn the difference between fire alarm codes and standards.

How do you know if your state or region is requiring 520Hz low frequency sounders?


The International Fire Code or IFC 2018 edition chapter 80 as well as the International Building Code or IBC 2018 edition chapter 35 both reference NFPA 72 2019.  With this said, you will need to find out if your jurisdiction has adopted the 2012 or newer version of the IBC or IFC code.  Better yet, System Sensor has provided a detailed map of the States and Regions currently adopting this code.  See below:

Map for 520 Hz Low Frequency Sounders

Tuesday, April 22, 2014

Fire Alarm Requirements for Group R-4 Occupancy

Group R-4: (Residential)


Systems required to be monitored per the 2021 IFC section 907.6.6.

A manual fire alarm system (pull stations) and automatic smoke detection system that activates the occupant notification system (horns, strobes, sounders, speakers, chimes, mass notification, etc.)

Manual Fire Alarm Box Requirements:


Manual fire alarm boxes at all exits.

Travel distance to any manual fire alarm box cannot exceed 200 feet.

Exceptions:

Manual fire alarm boxes are not required if the facility is two stories or less in height and all individual sleeping units and contiguous attic and crawl spaces to the sleeping units are separated from one another and public/common spaces by a minimum of 1-hour partitions.  Each sleeping unit must also have a direct exit to a public way, egress court or yard.

Manual fire alarm boxes at exits in sleeping units shall not be required if manual pull boxes are located at all care providers’ stations or other approved staff locations.  Note: the pull stations must be visible/accessible and the travel distance to any pull box shall not exceed 200 feet.

manual fire alarm boxes are not required to be installed when ALL of the following conditions exist:

The Group R-2 facility is equipped with an automatic sprinkler system.

The occupant notification systems will activate upon sprinkler water flow.

A minimum of one manual fire alarm box shall be installed in an area approved by the local AHJ (Authority Having Jurisdiction).

UL 268 Automatic Smoke Detection Requirements:


Smoke detection shall be provided for corridors, waiting areas open to corridors and habitable spaces other than sleeping units and kitchens.

“Exceptions”

If the building is protected by an automatic sprinkler system, smoke detection is not required in habitable spaces.

Smoke detection is not required in buildings without interior corridors serving the sleeping units.  This is predicated on the sleeping units having a means of egress door opening that leads directly to an exit.

UL 217 Smoke Alarm Requirements:


Single or multiple station smoke alarms shall be installed in all of the following areas:

On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms.

In every room used for sleeping purposes.

On every level of the dwelling unit including the basement.  This does not include crawl spaces or uninhabitable attics.  If the dwelling unit has split levels without a separation door then a smoke alarm shall be installed on the upper level predicated on the distance between the split levels being less than one full story.

Notification Requirements:


520 Hz low frequency sounders shall be installed in all sleeping areas.  Horns can be provided in common areas including but not limited to corridors, public restrooms, elevator lobbies, etc.  Emergency voice/alarm communications systems shall be provided for high rise applications.  High rise buildings are classified by the International Building Code as a structure that has occupied floors located more than 75 feet above the lowest level of fire department vehicle access.

Using a sound pressure meter or dB Meter, verify you comply with the following:

Public Mode Audibility: You must have 15 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.

Private Mode Audibility: You must have 10 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.

Fire Alarm Requirements for Licensed R-2.1 Occupancy

Group R-2.1 “Licensed”: (Residential)


Systems required to be monitored per the 2021 IFC section 907.6.6.

If the “Licensed” R-2.1 facility houses more than six non-ambulatory, elderly clients shall be equipped with a manual and automatic fire alarm system.

Manual Fire Alarm Box Requirements:


Manual fire alarm boxes at all exits.

Travel distance to any manual fire alarm box cannot exceed 200 feet.

UL 268 Automatic Smoke Detection Requirements:


Smoke and/or heat detectors installed throughout

If ALL of the following conditions exist then the facility can be provided with the same requirements of a Group R-2 facility.

The facility is equipped with an approved automatic sprinkler system that activates the occupant notification system.

A manual fire alarm system.

Single or multiple station smoke alarms installed inside each sleeping unit as well as outside each sleeping unit within immediate vicinity of the bedrooms.

Fire Alarm Notification Requirements:


520 Hz low frequency sounders shall be installed in all sleeping areas.  Horns can be provided in common areas including but not limited to corridors, public restrooms, elevator lobbies, etc.  Emergency voice/alarm communications systems shall be provided for high rise applications.  High rise buildings are classified by the International Building Code as a structure that has occupied floors located more than 75 feet above the lowest level of fire department vehicle access.

Note:  “Licensed” R-2.1 occupancies are required to be pre-wired for future adaptability.  This means you need to install either a conduit raceway or the necessary cable for the possibility that any room may convert to an accessible unit in the future.

Using a sound pressure meter or dB Meter, verify you comply with the following:

Public Mode Audibility: You must have 15 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.

Private Mode Audibility: You must have 10 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.

Fire Alarm Requirements for Group R-2 and R-2.1 Occupancy

Group R-2 and R-2.1: (Residential)


Systems required to be monitored per the 2021 IFC section 907.6.6.

A manual fire alarm system (Manual fire alarm boxes) that activates the occupant notification system (horns, strobes, sounders, speakers, chimes, mass notification, etc.)

Group R-2 and R-2.1 Fire Alarm Requirements

Manual Fire Alarm Box Requirements:


Manual fire alarm boxes are required if the facility has:
  • Dwelling or sleeping units located three or more stories above the lowest level of exit discharge 
  • Dwelling or sleeping units more than one story below the highest level of exist discharge
  • The building contains more than 16 dwelling or sleeping units.

Exceptions: 
  • A fire alarm system is not required where the Group R-2 facility is not more than two stories in height where all dwelling or sleeping units and contiguous attic and crawl spaces are separated from each other and public or common areas by not less than 1-hour fire partitions and each dwelling unit or sleeping unit has an exit directly to a public way, egress court or yard.
  • Manual fire alarm boxes are not required where the building is equipped with an automatic sprinkler system that activates the occupant notification appliances.
  • A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units or sleeping units and are protected by an approved automatic sprinkler system.  This is provided that the dwelling units or sleeping units open directly to an exterior exit access that leads directly to the exits or a re served by open-ended corridors designed in accordance with section 1027.6 Exception #3.

2021 IFC section 907.2 - If the facility is provided with an approved automatic sprinkler system in which the Waterflow activates the occupant notification system a minimum of one (1) manual fire alarm box is required to be provided in an area approved by the local AHJ (Authority Having Jurisdiction).

Exceptions:
#1: The manual fire alarm box is not required for fire alarm systems dedicated to elevator recall control and supervisory service.
#2: The manual fire alarm box is not required for group R2 occupies unless required by the fire code official to provide a means for fire watch personnel to initiate an alarm during a sprinkler system impairment event. Where provided, the manual fire alarm box shall not be located in an area that is open to the public.

UL 268 Automatic Smoke Detection Requirements:


System smoke detectors shall be provided for all of the following applications:

Above control panels and power supplies
For the purpose of elevator capture
On all HVAC units over 2,000 CFM (Duct Detector)
For releasing service
Fire Smoke Dampers
Delayed egress locks

UL 217 Smoke Alarm Requirements:


Single or multiple station smoke alarms shall be installed in all of the following areas per section 907.2.11:

On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms.

In every room used for sleeping purposes.

On every level of the dwelling unit including the basement.  This does not include crawl spaces or uninhabitable attics.  If the dwelling unit has split levels without a separation door then a smoke alarm shall be installed on the upper level predicated on the distance between the split levels being less than one full story.

Important update to this edition of the model code: The UL 217 single and multiple station smoke alarms are now required to produce a 520Hz low frequency audible tone. Please note these units are not currently manufactured and or listed for this use. It is very important to get ahead of the project and discuss with the general contractor and electrical contractor the requirements for this change. If you would like more information on how this can be achieved as well as the code references, please visit this link. 520Hz audible tone for 120 VAC Smoke Alarms.

Fire Alarm Notification Requirements:


520 Hz low frequency sounders shall be installed in all sleeping areas.  Horns can be provided in common areas including but not limited to corridors, public restrooms, elevator lobbies, etc.  Emergency voice/alarm communications systems shall be provided for high rise applications.  High rise buildings are classified by the International Building Code as a structure that has occupied floors located more than 75 feet above the lowest level of fire department vehicle access.

Note:  R-2 occupancies are required to be pre-wired for future adaptability.  This means you need to install either a conduit raceway or the necessary cable for the possibility that any room may convert to an accessible unit in the future.  This is noted in Section 907.5.2.3.3

Using a sound pressure meter or dB Meter, verify you comply with the following:

Public Mode Audibility: You must have 15 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.

Private Mode Audibility: You must have 10 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.

Sleeping Area Audibility: You must have 15 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds or a minimum of 75 dB whichever is greater.

Group R-2: (College and University Buildings)


Systems required to be monitored per the 2021 IFC section 907.6.6.

An automatic smoke detection system that activates the occupant notification system (horns, strobes, sounders, speakers, chimes, mass notification, etc.)

Manual Fire Alarm Box Requirements:


2021 IFC section 907.2 - If the facility is provided with an approved automatic sprinkler system in which the Waterflow activates the occupant notification system a minimum of one (1) manual fire alarm box is required to be provided in an area approved by the local AHJ (Authority Having Jurisdiction).
Exceptions:
#1: The manual fire alarm box is not required for fire alarm systems dedicated to elevator recall control and supervisory service.
#2: The manual fire alarm box is not required for group R2 occupies unless required by the fire code official to provide a means for fire watch personnel to initiate an alarm during a sprinkler system impairment event. Where provided, the manual fire alarm box shall not be located in an area that is open to the public.

UL 217 Smoke Alarm Requirements:


Single or multiple station smoke alarms shall be installed in all of the following areas:

Sleeping areas.

Each room in the path of the means of egress from sleeping area to the door leading to the sleeping unit.

On each level within the sleeping unit.  This includes basements.  If the sleeping unit has split levels without a door separation, one smoke alarm on the upper level will suffice.  Note this is only for slip level where the distance between levels is less than one full story.

All smoke alarms in dwelling units and sleeping units shall be interconnected with the fire alarm system in accordance with NFPA 72. 

Important update to this edition of the model code: The UL 217 single and multiple station smoke alarms are now required to produce a 520Hz low frequency audible tone. Please note these units are not currently manufactured and or listed for this use. It is very important to get ahead of the project and discuss with the general contractor and electrical contractor the requirements for this change. If you would like more information on how this can be achieved as well as the code references, please visit this link. 520Hz audible tone for 120 VAC Smoke Alarms.

UL 268 Automatic Smoke Detection Requirements:


System smoke detectors shall be provided for all of the following applications:

Above control panels and power supplies
For the purpose of elevator capture
On all HVAC units over 2,000 CFM (Duct Detector)
For releasing service
Fire Smoke Dampers
Delayed egress locks

Automatic smoke detectors shall be provided in the following areas:

Common spaces outside of the dwelling/sleeping units.

Laundry rooms, mechanical equipment rooms and storage rooms.

Interior corridors serving dwelling/sleeping units
  
Exception

Smoke detection is not required in buildings without interior corridors serving the sleeping units.  This is predicated on the sleeping units having a means of egress door opening that leads directly to an exit.

Fire Alarm Notification Requirements:


520 Hz low frequency sounders shall be installed in all sleeping areas.  Horns can be provided in common areas including but not limited to corridors, public restrooms, elevator lobbies, etc.  Emergency voice/alarm communications systems shall be provided for high rise applications.  High rise buildings are classified by the International Building Code as a structure that has occupied floors located more than 75 feet above the lowest level of fire department vehicle access.

Note:  R-2 occupancies are required to be pre-wired for future adaptability.  This means you need to install either a conduit raceway or the necessary cable for the possibility that any room may convert to an accessible unit in the future.  This is noted in Section 907.5.2.3.3

Public Mode Audibility: You must have 15 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.

Private Mode Audibility: You must have 10 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.