Monday, January 5, 2026

California OSFM Clarifies Emergency Power Requirement for Smoke Alarms with Integral Strobes

 

California OSFM Clarifies Emergency Power Requirement for 120V Smoke Alarms with Integral Strobes (R-1 & R-2 Only)

Overview

The California Office of the State Fire Marshal (OSFM) has issued Code Interpretation 25-12, providing critical clarification on power supply requirements for 120-volt smoke alarms with integral strobe lights under the 2022 California Fire Code (CFC).

This interpretation has immediate design and construction implications for new residential projects, particularly Group R-1 and R-2 occupancies, and resolves long-standing confusion about whether internal battery backup alone is acceptable.

Spoiler alert: it is not.


What Triggered This Clarification?

Designers, contractors, and AHJs have questioned whether smoke alarms that include integral visual notification (strobes) could rely solely on internal battery backup during a power outage.

The OSFM was formally asked to interpret CFC Section 907.2.11.6, and the response was unambiguous.


Official OSFM Interpretation (Code Interpretation 25-12)

According to the OSFM:

Smoke alarms with integral strobes must be connected to an emergency electrical system when the strobe portion cannot be powered by the internal battery.

The Office further clarified that:

  • There are currently no listed smoke alarms where the battery backup is capable of powering the strobe

  • Strobes have significantly higher power demands than audible-only smoke alarms

  • Battery backup is therefore insufficient for visual notification appliances

This requirement is clearly stated in OSFM Code Interpretation 25-12, issued December 26, 2025


Diagram showing a 120V smoke alarm with integral strobe connected to a building emergency power circuit as required by California OSFM for R-1 and R-2 occupancies
California OSFM Code Interpretation 25-12 requires smoke alarms with integral strobes in Group R-1 and R-2 occupancies to be powered by an emergency electrical system.



Which Occupancies Are Affected?

This requirement applies only to the following occupancy groups:

 Applies To:

  • Group R-1

    • Hotels

    • Motels

    • Boarding houses

  • Group R-2

    • Apartments

    • Condominiums

    • Dormitories

    • Assisted living (non-R-3.1)

Does NOT Apply To:

  • Group R-3 (single-family dwellings)

  • Commercial occupancies

  • Audible-only smoke alarms

  • Smoke alarms without integral strobes

Clarity here matters. This is not a blanket requirement across all residential buildings.


What “Emergency Power” Means in Practice

For applicable R-1 and R-2 projects:

  • The strobe portion of the smoke alarm must be supplied by emergency power

  • Acceptable sources include:

    • Legally required standby power systems

    • Emergency generators

    • Other code-compliant emergency electrical systems

  • Simply installing a 120VAC smoke alarm with battery backup is not compliant when a strobe is integrated

This has direct impact on:

  • Electrical design

  • Circuiting strategy

  • Panel schedules

  • Cost estimating

  • AHJ plan review approvals


Why the OSFM Took This Position

The OSFM explicitly stated that:

  • Battery technology cannot reliably support strobe operation

  • Visual notification is a life-safety feature, especially for the hearing-impaired

  • Emergency power ensures continuous visual alerting during outages

This interpretation reinforces accessibility and survivability objectives already embedded in the California Fire Code.


Key Takeaways for Designers & Contractors

  •  Treat smoke alarms with integral strobes like notification appliances, not basic household   alarms

  •  Plan emergency power early in design for R-1 and R-2 projects

  •  Expect AHJs to enforce this interpretation statewide

  •  Do not assume battery backup satisfies strobe power requirements

Failing to account for this can result in plan check corrections, failed inspections, or costly redesigns.


Reference Document

  • CAL FIRE – Office of the State Fire Marshal

  • Code Interpretation 25-12

  • Issued December 26, 2025

  • 2022 California Fire Code – Section 907.2.11.6 

Tuesday, December 13, 2016

Fire Alarm Requirements for Group R-1 Occupancy

Group R-1: (Residential)


Systems required to be monitored per the 2021 IFC section 907.6.6.

A manual fire alarm system (manual fire alarm boxes) that activates the occupant notification system (horns, strobes, sounders, speakers, chimes, mass notification, etc.)

Manual Fire Alarm Box Requirements:

Manual fire alarm boxes are not required if the facility is two stories or less in height and all individual sleeping units and contiguous attic and crawl spaces to the sleeping units are separated from one another and public/common spaces by a minimum of 1-hour partitions.  Each sleeping unit must also have a direct exit to a public way, egress court or yard.

Manual fire alarm boxes are not required to be installed when ALL of the following conditions exist:

#1: The Group R-1 facility is equipped with an automatic sprinkler system installed in accordance with section 903.3.1.1 or 903.3.1.2. 

#2: The occupant notification systems will activate upon sprinkler water flow.

#3: At minimum one manual fire alarm box is installed at an approved location.


2021 IFC section 907.2 - If the facility is provided with an approved automatic sprinkler system in which the Waterflow activates the occupant notification system a minimum of one (1) manual fire alarm box is required to be provided in an area approved by the local AHJ (Authority Having Jurisdiction).
Exceptions:
#1: The manual fire alarm box is not required for fire alarm systems dedicated to elevator recall control and supervisory service.
#2: The manual fire alarm box is not required for group R2 occupies unless required by the fire code official to provide a means for fire watch personnel to initiate an alarm during a sprinkler system impairment event. Where provided, the manual fire alarm box shall not be located in an area that is open to the public.

UL 268 Automatic Smoke Detection Requirements:

System smoke detectors shall be provided for all of the following applications:

Above control panels and power supplies
For the purpose of elevator capture
On all HVAC units over 2,000 CFM (Duct Detector)
For releasing service
Fire Smoke Dampers
Delayed egress locks

Automatic smoke detectors are required to be installed in all interior corridors serving the sleeping units.

Exception:

Automatic smoke detectors are not required to be installed in interior corridors if the building does not contain interior corridors serving the sleeping units where all sleeping units have a means of direct exit access to the exterior.

UL 217 Smoke Alarm Requirements:

Low frequency sounders for fire alarms in sleeping areas
Single or multiple station smoke alarms shall be installed in all of the following areas:

Sleeping areas.

Each room in the path of the means of egress from sleeping area to the door leading to the sleeping unit.

On each level within the sleeping unit.  This includes basements.  If the sleeping unit has split levels without a door separation, one smoke alarm on the upper level will suffice.  Note this is only for slip level where the distance between levels is less than one full story.

Fire Alarm Notification Requirements:

520 Hz low frequency sounders shall be installed in all sleeping areas.  Horns can be provided in common areas including but not limited to corridors, public restrooms, elevator lobbies, etc.  Emergency voice/alarm communications systems shall be provided for high rise applications.  High rise buildings are classified by the International Building Code as a structure that has occupied floors located more than 75 feet above the lowest level of fire department vehicle access.

Note:  R-1 occupancies have a required amount of handicap accessible rooms that need to be provided with visible appliances.  This requires sounder/strobes, horn/strobes or speaker/strobes in the sleeping rooms and living rooms as well as a strobe in the restrooms.  Keep in mind that the strobe located in sleeping areas shall be 110 candela if the top of the lens is greater than or equal to 24 inches from the ceiling.  If the top of the lens is 23 inches or closer to the ceiling you shall provide a setting of 177 candela. ** These visible alarms shall activate upon system smoke detectors or single or multiple station smoke alarms.

** Use the ADA Room tool found in the main menu of this application to determine the quantity of accessible rooms you need to include in your design.

ADA Room Fire Alarm Strobe Chart

Using a sound pressure meter or dB Meter, verify you comply with the following:

Public Mode Audibility: You must have 15 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.

Private Mode Audibility: You must have 10 dB above average ambient sound level or 5 dB above the maximum sound level for at least 60 seconds whichever is greater.