Showing posts with label elevator machine room. Show all posts
Showing posts with label elevator machine room. Show all posts

Saturday, December 17, 2016

How to Wire Elevator Shunt Trip

Elevator Shunt Trip Wiring

We have created an easy to follow document for the proper wiring method with elevator shunt trip functions.  This document includes two methods both based on the supervision requirements of NFPA 72 2016 edition section A.21.4.4.

Below is a sample picture of the document that is available for download on our Facebook Group.

It is important to remember that the wiring between the FACP/FACU and the ECID (Emergency Control Interface Device) needs to be supervised.  In one method below, we are using an addressable relay module (FRM-1) to operate the shunt trip breaker directly.  With this wiring method, only the wire to the FRM-1 (SLC) needs to be supervised.  This is obviously achieved through the SLC and addressing of the device.


In the alternate method, we are showing you how to properly wire up the equipment when the load of the circuit exceeds the rating of the FRM-1.  In this case you would need to install a PR-1 interface relay (rated for 10 amps).  Now that you have a PR-1 switching the shunt trip circuit, this becomes your ECID (Emergency Control Interface Device) and the wiring up to this relay needs to be supervised.  To save the cost of an additional addressable monitor module (FMM-1) we can switch out the FRM-1 with a FCM-1 (addressable control module).  By doing this, we can achieve supervision as well as activation of the PR-1 interface relay through one device.


Elevator Shunt Trip Wiring Diagram


Make sure to download the document and let us know your thoughts.

Saturday, May 18, 2013

Elevator Recall Explanation and Programming

Elevator Recall Programming for Fire Alarm


Programming and designing elevator recall for fire alarm systems is a fairly simple process if you are familiar with the codes and standards in place.  Most fire alarm programmers and contractors understand the principle behind capturing passenger elevators but for those of you that don't, check this out!
Fire Alarm Elevator Recall

Per NFPA 72 2016 section 21.3.1, elevators are required by code to be connected and controlled by a Building Fire Alarm System (NFPA 72 2016 3.3.103.4.1) or an Elevator Recall System which falls under the NFPA 72 classification of Dedicated Function Fire Alarm System (NFPA 72 2016 3.3.103.4.2).

As required by NFPA 72 2016 21.3.5*, the spot type smoke detectors for the use of capturing the passenger elevator shall be mounted within 21' center line of the elevator door.  In addition to these detectors, you will have smoke detector(s) in the elevator machine (EMR) room and at the top of the elevator hoistway.   Keep in mind that smoke detection in the elevator shaft is only required if the elevator hoistway has automatic sprinklers.  Automatic sprinklers are only found in the elevator hoistway if the elevator is constructed of combustible material.  Consult NFPA 13 and the International Building Code for more details.  All of these spot type smoke detectors will be associated with your building fire alarm or dedicated function elevator system's elevator recall functions.

Regarding the elevator and the building fire alarm system relationship, we have additional functions that require the installation of thermal spot type heat detectors.  You will need these thermal spot type heat detectors in the elevator machine room (EMR) and elevator shaft (only if automatic sprinklers are present).  Note these heat detectors do not recall or capture the elevators.  These thermal heat detectors shunt the power to the elevator controller in the event of a fire.  Remember the thermal spot type detectors used for shunt trip are required to be set or programmed to a lower temperature point then the surrounding automatic sprinkler heads.  The intent is for the fire alarm system to sense the fire before the automatic sprinkler heads.  This way the fire alarm control unit (FACU) can disconnect the power to the elevator controls prior to the sprinkler head applying water to its electronics.  You can read more about fire alarm system elevator shunt trip in the following article: elevator shunt trip.

Designated Level Recall and Alternate Level Recall


NFPA 72 2016 21.3.13.1.  Designated Level Recall.  All smoke detectors associated with elevator recall that are not installed on the primary floor of egress including the top of the elevator shaft will activate the designated level elevator recall relay.  This function will send the elevator car to the main level of exit discharge.  (typically lobby floor or level #1 depending on the building layout).

NFPA 72 2016 21.3.13.2.  Alternate Level Recall.  All smoke detectors associated with elevator recall that are installed on the main level of exit discharge will activate the alternate level elevator recall relay.  This function will send the passenger elevator to the alternate floor of egress. (typically the basement or 2nd floor depending on the building layout).

Elevator Flashing Hat LightThe floor or level where the elevator equipment room is located will determine the recall relay to be activated in the event of an activated smoke detector.  Example:  If the elevator machine room (EMR) is located on the first floor, its associated smoke will activate the alternate elevator recall relay.  If the elevator machine room is located on the roof, its associated smoke detector will activate the designated elevator recall relay.

The heat detectors in the elevator machine room and elevator hoistway will activate the shunt trip relay killing power to the controller.  On top of this the heat detectors shall shut off any back-up power to the elevator.  Per NFPA 72 2016 section 21.3.13.3* The elevator hoistway and equipment machine room smoke detectors and or heat detectors shall activate a visual warning commonly known as the flashing Fireman's Hat Light near the elevator call buttons.  This allows the fire department to become aware if there is a fire in the hoistway or elevator machine room.

Now programming all of this might seem difficult but it is actually really simple.  Get basic instructions on how the programming breaks down in this article:  fire alarm system with elevator recall.

Make sure to join our Fire Alarms Online Facebook Group HERE.

Elevator Recall Programming for Fire Alarm

Are you up to speed with fire alarm systems in relation to elevator recall and elevator shunt trip? If not, check out this article titled Elevator Recall and Shunt Trip Basics.

Easy Way to Breakdown Elevator Recall and Shunt Trip Programming


Now that we know what elevator recall is all about, lets move on to programming basics for fire alarm systems.  The best way to start this process is to write down all of your fire alarm devices associated with the elevator recall functions.  Make a list running vertical (top to bottom) of all the smoke detectors and heat detectors used for these functions.  Example below:

1 - 1st floor elevator lobby smoke detector
2 - 1st floor elevator machine room smoke detector
3 - 1st floor elevator machine room heat detector
4 - 2nd floor elevator lobby smoke detector
5 - 3rd floor elevator lobby smoke detector
6 - 4th floor elevator lobby smoke detector
7 - Elevator hoistway smoke detector
8 - Elevator hoistway heat detector
9 - Designated elevator recall relay
10 - Alternate elevator recall relay
11 - Shunt trip relay
12 - Elevator battery back-up relay
13 - Elevator fireman's hat light relay

Now that we have all of our fire alarm devices associated with the elevator recall functions written down, it's time to place them in groups or zones.  This is the process that tells the fire alarm control panel what to do in the event one of these devices is activated.

As stated in one of our previous articles,  we know that the smoke detectors on all floors other than the first floor will send the elevator the the 1st floor.  We also know that the smoke detectors on the first floor will send the elevator to the second floor.  And last the heat detectors will activate the shunt trip and battery back-up and the elevator hoistway and elevator machine room smoke detectors will activate the fireman's hat light or visual warning per NFPA 72 2016 21.3.13.3.  To make this simple we are going to use 5 different zones (1 = general alarm, 2 = primary elevator recall, 3 = secondary elevator recall, 4 = shunt trip/battery back-up, and 5 = fire fighters hat light).

With that said, take your list above and write down the zones or groups for each point next to the device description.  Also make note of which devices are inputs and outputs.

Elevator Recall and Shunt Trip Programming Zones


1 - 1st floor elevator lobby smoke detector (input) -------- 1,3
2 - 1st floor elevator equipment room smoke detector (input) -------- 1,3,5
3 - 1st floor elevator machine room heat detector (input) -------- 1,4,5
4 - 2nd floor elevator lobby smoke detector (input) -------- 1,2
5 - 3rd floor elevator lobby smoke detector (input) -------- 1,2
6 - 4th floor elevator lobby smoke detector (input) -------- 1,2
7 - Elevator hoistway smoke detector (input) -------- 1,2,5
8 - Elevator hoistway or pit heat detector (input) -------- 1,4,5
9 - Designated elevator recall relay (output) -------- 2
10 - Alternate elevator recall relay (output) -------- 3
11 - Shunt trip relay (output) -------- 4
12 - Elevator battery back-up relay (output) -------- 4
13 - Elevator fireman's hat light relay (output) -------- 5



Elevator Recall Detail

Now that you have it all written out it makes it a lot easier to program.  Hope this helps.  If you have questions regarding elevator recall be sure to post a comment or email us.