Does California require Duct Smoke Detectors on the Return Side?
Since this question comes up so often, I felt it would be beneficial to put an article together with the answers and applicable code/standard references. Please note that the below information is pertinent to CA and may be altered by individual jurisdictions if they have formally adopted a local ordinance to supersede the state level requirements.
- In California, are we
required to install the duct smoke detector on the supply or return side
of HVAC units GREATER than 2,000 cfm?
- In California, are we required to install a duct smoke detector on both the supply and return side of and HVAC unit GREATER than 15,000 cfm?
Before we can answer these questions, we need to know what codes and standards California has adopted.
Chapter 35 of the California Building Code 2022 edition is
dedicated to clarifying which codes and standards are adopted by the State Fire
Marshal. The code/standard
references are on the left with vertical columns signifying which agencies have
adopted them. The third column from the left with the “Xs” is for the State
Fire Marshal. From here we can tell that based on the 2022 CBC, the applicable
standard for Fire Alarm is the 2022 edition of NFPA 72. Please also note that the IMC or International Mechanical Code is not found within this document. This
lets us know this code not valid in California and therefore its individual
language does not apply.
![]() |
| 2022 CBC MATRIX ADOPTION TABLE - CHAPTER 35 |
Duct Smoke Detectors based on NPFA 72 2022 Edition
NFPA 72 2022 Section 17.7.5.3.1 States “To prevent the recirculation of dangerous quantities of smoke, a detector approved for air duct use shall be installed on the supply side of air handing systems as required by NFPA 90A and 17.7.5.4.2.1”
Duct Smoke Detectors based on NFPA 90A
- Downstream of the air
filters and ahead of any ranch connections in air supply systems
having a capacity greater than 2000 cfm.
- At each story prior to
the connection to a common return and prior to any recirculation or fresh
air inlet connection in air return systems having a capacity greater
than 15,000 cfm and serving more than one story.”
Duct Smoke Detectors based on the International Mechanical Code (IMC)
NO Duct Smoke Detector on Return for units greater than 2,000 cfm in California
Summary
- NFPA 72 2022 17.7.5.3.1
- In California we are required to provide a duct smoke detector on the SUPPLY
side of HVAC units per NFPA 90A.
- NFPA 90A 6.4.2.1 - In
California we are required to provide a duct smoke detector on the SUPPLY
side of HVAC units greater than 2,000 cfm
- NFPA 90A 6.4.2.1 – In
California we are required to provide a duct smoke detector on each return
inlet prior to a common return for HVAC units greater than 15,000 which
serve more than one floor (below is a simple
diagram showing this setup.)
- IMC 2021 606.2.1 –
Requires a duct smoke detector in the return of HVAC units greater than
2,000 cfm. THIS DOES
NOT APPLY IN CALIFORNIA


No comments:
Post a Comment