"For fire smoke dampers, should I use an in-duct spot type smoke detector or a duct detector?"
Sampling tube style duct detectors are listed for a minimum air velocity of 100 fpm (feet per minute). If you are to ensure the rating of the wall at duct penetrations (dampers), you must provide coverage per The International Building Code IBC 2015 Edition Section 717.3.3.2.
717.3.3.2 Smoke damper actuation. The smoke fire damper shall close upon actuation of a listed smoke detector or detectors installed in accordance with Section 907.3 and one of the following methods, as applicable:
1. Where a smoke damper is installed within a duct, a smoke detector shall be installed in the duct within 5 feet (1524 mm) of the damper with no air outlets or inlets between the detector and the damper. The detector shall be listed for the air velocity, temperature and humidity anticipated at the point where it is installed. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate.
2. Where a smoke damper is installed above smoke barrier doors in a smoke barrier, a spot-type detector listed for releasing service shall be installed on either side of the smoke barrier door opening.
3. Where a smoke damper is installed within an air transfer opening in a wall, a spot-type detector listed for releasing service shall be installed within 5 feet (1524 mm) horizontally of the damper.
4. Where a smoke damper is installed in a corridor wall or ceiling, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor.
5. Where a total-coverage smoke detector system is provided within areas served by a heating, ventilation and air-conditioning (HVAC) system, smoke dampers shall be permitted to be controlled by the smoke detection system.
The 1st method above states that you must provide a smoke detector installed in the duct within 5’ of the fire smoke damper, and that the smoke detector shall be listed for the air velocity. If you shut down the fan, there will not be a minimum air velocity of 100 fpm to achieve the proper listing of a sampling tube style duct detector (System Sensor D4120 for example). Notice that this same paragraph states that “Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate”.
What if we decide to use sample tube duct smoke detectors?

What if we use spot type In-Duct Smoke Detectors?

Building owners really don’t like when their building heats up because they are servicing one of their fans, or one of the many fans in their building turns off due to a number of circumstances that are not necessarily indicative of a fire, and our fire alarm system shuts down all HVAC movement in the building. Mechanical contractors don’t like it when they are forced to interface with individual dampers to close upon fan shutdown. And finally, electrical/mechanical contractors really don’t like it when we force them to give us a true status of the fan via a Current or Differential Pressure switch when the fan is not a part of a smoke control system and it was not shown on their drawings or bid docs.
If you like what you see here then make sure to join our Facebook Group here.
It’s amazing in support of me to truly have a web site that is valuable meant for my knowledge.
ReplyDeleteMost furnaces own a filtration connected about the profit air inlet. Many are good enough to protect the oxygen and furnace conditioning evaporator coil from grime. heating services from laird and son
ReplyDelete