Thursday, May 16, 2013

Wet Pipe Fire Sprinkler Systems | How They Work

Fire Alarms Online • Wet Pipe Sprinkler System Guide
Wet pipe sprinkler systems are the most straightforward automatic sprinkler systems you will encounter. This guide explains how they work, what happens when a sprinkler activates, and how waterflow and supervisory devices interface with the fire alarm system.

What Is a Wet Pipe Fire Sprinkler System?

A wet pipe fire sprinkler system is an automatic sprinkler system in which the sprinkler piping is normally filled with water under pressure.

Water is already present behind the automatic sprinklers, so when a sprinkler operates from sufficient heat, water can discharge immediately through that sprinkler.

This relatively simple operating principle is one reason wet pipe systems are so commonly encountered in commercial buildings.

Key Concept: A standard wet pipe sprinkler system does not wait for a smoke detector or fire alarm control unit to tell the sprinkler to open. The individual automatic sprinkler operates when its heat-responsive element reaches its operating condition.

How Does a Wet Pipe Sprinkler System Work?

Think of the basic sequence this way:

Heat from Fire → Sprinkler Operates → Water Discharges → Waterflow Occurs → Waterflow Alarm Initiates

The sprinkler piping is already filled with pressurized water. Each automatic sprinkler contains a heat-responsive operating element that keeps the sprinkler closed during normal conditions.

When sufficient heat reaches an individual sprinkler, its operating element releases and allows water to discharge through that sprinkler.

The resulting sustained movement of water through the sprinkler system can then operate the system's waterflow alarm-initiating device.

Does One Sprinkler Cause Every Sprinkler to Open?

No. This is one of the most common misconceptions about automatic fire sprinklers.

In a conventional wet pipe system using automatic sprinklers, each sprinkler operates individually in response to sufficient heat at that sprinkler.

If a fire produces enough heat to operate one sprinkler, that does not electrically or mechanically command every other sprinkler in the building to open.

Additional sprinklers can operate if the developing fire exposes them to sufficient heat.

Movie Myth: Pulling a fire alarm or activating one sprinkler does not normally cause every automatic sprinkler in the building to discharge. Hollywood has been flooding fictional hotels for decades.

What Temperature Activates a Fire Sprinkler?

Automatic sprinklers are available with different temperature ratings. The correct temperature classification is selected for the environment and application.

Do not assume every sprinkler operates at the same temperature. The sprinkler's listed temperature rating, expected maximum ceiling temperature, occupancy conditions and applicable NFPA 13 requirements all need to be considered during system design.

Also remember that the sprinkler's temperature rating is not necessarily the room temperature when a fire is first detected. The heat-responsive element itself must reach the conditions necessary for that particular sprinkler to operate.

Glass Bulb and Fusible-Link Sprinklers

Automatic sprinklers can use different heat-responsive operating elements.

One common design uses a glass bulb containing a liquid that expands as it is heated. When the sprinkler reaches its operating condition, the bulb breaks and releases the sealing assembly so water can discharge.

Other sprinkler designs use a fusible heat-responsive element that releases at its listed operating condition.

In either case, the fundamental concept is the same: heat operates the sprinkler.

Does Smoke Activate a Wet Pipe Sprinkler?

No, not under normal automatic sprinkler operation.

A smoke detector connected to the building fire alarm system does not normally open the individual sprinklers in a conventional wet pipe sprinkler system.

This distinction is especially important for fire alarm technicians because smoke detection and sprinkler operation are two different forms of fire protection.

A smoke detector may detect a developing fire before sprinkler operation occurs. The automatic sprinkler, however, operates because of heat at the sprinkler.

Main Components of a Wet Pipe Sprinkler System

The exact arrangement varies by system and building, but a wet pipe system commonly includes components such as:

  • Water supply
  • System control valve
  • Backflow prevention equipment where required
  • Riser and distribution piping
  • Automatic sprinklers
  • Waterflow alarm-initiating device
  • Control-valve supervisory switch where required
  • Pressure gauges
  • Main drain
  • Inspector's test connection
  • Other valves, drains and test equipment required by the particular installation

What Is a Fire Sprinkler Riser?

The sprinkler riser is a major portion of the sprinkler system where the water supply transitions into the building's sprinkler distribution system and where many important system components are commonly located.

For a fire alarm technician, the riser is particularly important because this is where you will commonly encounter equipment such as waterflow switches, valve supervisory switches, pressure switches, alarm/check valves and fire alarm monitor modules.

Understanding what each sprinkler component actually does makes troubleshooting its fire alarm interface much easier.

What Is a Waterflow Switch?

A waterflow switch is used to detect sustained water movement associated with operation of the sprinkler system.

On many wet pipe systems, you will encounter a vane- or paddle-type waterflow switch installed directly on the sprinkler piping.

A paddle extends into the pipe. When sufficient sustained waterflow occurs, movement of the paddle operates the switch mechanism. The electrical contacts associated with the device can then be monitored by the building fire alarm system.

Want to see what is actually happening inside one? We have a separate field article showing the internal paddle/flapper arrangement: See How a Fire Sprinkler Waterflow Switch Works →

Fire Alarm Technician Tip: Waterflow is generally an alarm function. A control-valve tamper condition is generally a supervisory function. They should not simply be treated as interchangeable sprinkler monitor points.

What Happens at the Fire Alarm Panel When Water Flows?

For a monitored sprinkler system, the sequence can be viewed from the fire alarm side like this:

Sprinkler Operates → Water Flows → Waterflow Device Operates → Fire Alarm Input Changes State → FACU Processes Waterflow Alarm

Depending on the building, system configuration and applicable requirements, operation of the automatic sprinkler system can initiate required building fire alarm functions and transmit the required signal to a supervising station.

For more information about the components a fire alarm technician encounters at the sprinkler riser, see: Waterflow, Backflow, OS&Y and Tamper Switch Basics →

Why Is There a Delay on a Waterflow Switch?

Many vane-type waterflow switches have an adjustable retard mechanism.

The purpose is to reduce unwanted alarms caused by brief water movement or pressure fluctuations while still allowing sustained sprinkler waterflow to initiate the required alarm.

However, there is an important misconception about the familiar 90-second rule.

90 Seconds Is a Maximum, Not a Target: NFPA 72 requirements limit how long the waterflow alarm-initiating device can take to initiate an alarm under the specified sustained-flow condition. That does not mean every waterflow switch should simply be adjusted for a 90-second delay.

The actual retard setting must comply with the applicable code requirements, device listing, system configuration and requirements of the authority having jurisdiction.

What Is a Tamper Switch?

A valve supervisory switch, commonly called a tamper switch, monitors the position of a sprinkler system control valve.

Its purpose is fundamentally different from a waterflow switch.

If a valve controlling the sprinkler water supply is moved away from its normal position, the supervisory switch can send a signal to the fire alarm system indicating that the sprinkler system may no longer be in its normal operating condition.

Device What It Monitors Typical Fire Alarm Signal
Waterflow Switch Water flowing in sprinkler system Alarm
Valve Supervisory / Tamper Switch Position of sprinkler control valve Supervisory

For a deeper look at both devices, see our Fire Sprinkler Waterflow, Backflow, OS&Y and Tamper Switch Guide →

What Does OS&Y Mean?

OS&Y stands for Outside Screw and Yoke.

An OS&Y valve is a type of control valve. Its exposed stem provides a readily visible indication of valve position.

This is important because OS&Y valves and backflow preventers are sometimes incorrectly described as though they are the same component.

They are not.

OS&Y describes a valve configuration. A backflow prevention assembly serves a different purpose involving protection of the water supply from reverse flow.

What Is a Backflow Preventer?

A backflow prevention assembly is used where required to prevent water from the fire sprinkler system from flowing backward into the potable water supply.

It should not be described simply as a device installed to prevent false fire alarms.

Depending on the assembly and installation, associated control valves can also require electrical supervision.

Alarm Check Valves and Wet Pipe Systems

Some wet pipe systems use an alarm check valve arrangement.

During sprinkler operation, sustained waterflow through the alarm valve can provide pressure to an alarm line used for sprinkler alarm equipment.

Traditional arrangements can include:

  • Water motor gongs
  • Pressure-operated alarm switches
  • Retard chambers
  • Associated alarm trim

A retard chamber can help prevent brief pressure surges from producing an unwanted alarm through the alarm trim.

This should not be confused with the retard mechanism built into certain vane-type waterflow switches. The two can address similar transient-flow concerns but are different components and operate differently.

Can Wet Pipe Systems Be Installed Where Pipes Might Freeze?

Water-filled sprinkler piping must be protected from freezing.

That is why areas subject to freezing can require another design approach, such as a dry pipe system, an appropriate preaction arrangement, listed dry sprinklers extending from protected piping, or another method permitted by the applicable sprinkler standard.

This is one of the major differences between wet and dry pipe sprinkler systems.

For the complete dry-system sequence, see: Dry Pipe Fire Sprinkler Systems | How They Work →

Wet Pipe vs Dry Pipe Fire Sprinkler Systems

Feature Wet Pipe Dry Pipe
Normal piping condition Water-filled Pressurized air or nitrogen in system piping
Typical application Areas protected from freezing Areas where water-filled piping could freeze
Sprinklers Automatic Automatic
Water in system piping during normal conditions Yes No
Additional valve operation before water enters system piping No dry pipe valve trip required Dry pipe valve must operate

Wet Pipe vs Preaction vs Deluge

Wet pipe, dry pipe, preaction and deluge systems should not be treated as interchangeable terms.

One of the most important differences is what must happen before water enters or discharges from the system.

  • Wet pipe: Water is already present in the sprinkler piping.
  • Dry pipe: Pressurized air or nitrogen occupies the system piping. Operation of an automatic sprinkler causes pressure loss that ultimately allows the dry pipe valve to operate and water to enter the piping.
  • Preaction: A supplemental detection/releasing arrangement is involved in controlling admission of water into the sprinkler piping according to the particular preaction system design.
  • Deluge: The system uses open sprinklers or nozzles. Operation of the releasing system allows water to enter the piping and discharge through the open outlets.

To see how dramatically the sequence changes when open sprinklers or nozzles and a releasing system are involved, read: Deluge Fire Sprinkler Systems | How They Work →

Waterflow vs Supervisory Signals

For fire alarm technicians, this is one of the most important lessons to take away from the sprinkler riser.

Waterflow generally indicates operation of the sprinkler system and is processed as an alarm signal.

A supervisory signal indicates an abnormal condition involving a monitored fire-protection system that can affect its readiness or operation.

Examples of sprinkler-related conditions requiring supervision can include control-valve position and critical air pressure where applicable.

Do not automatically program every sprinkler-related input as the same type of fire alarm event.

Testing a Wet Pipe Waterflow Switch

A proper functional waterflow test proves more than whether the electrical contacts inside the switch can change state.

The system should be tested through the appropriate test arrangement in accordance with the applicable inspection, testing and maintenance requirements and site procedures so that actual waterflow causes the initiating device to operate.

From the fire alarm side, the technician should verify that the required signal reaches the fire alarm control unit and that the required downstream functions occur.

Safety: Sprinkler valves, drains and test connections can release significant quantities of pressurized water. Testing should be performed by qualified personnel using approved procedures and with required parties properly notified.

Common Wet Pipe Sprinkler System Mistakes

  • Calling an OS&Y valve a backflow preventer.
  • Assuming every sprinkler opens when one sprinkler operates.
  • Believing smoke detectors normally activate wet pipe sprinklers.
  • Programming a waterflow switch as a supervisory condition.
  • Programming a control-valve tamper switch as a fire alarm condition.
  • Assuming the waterflow retard must always be set to 90 seconds.
  • Confusing an alarm-valve retard chamber with the retard mechanism in a vane-type waterflow switch.
  • Ignoring freezing exposure when evaluating water-filled piping.

Frequently Asked Questions

Why is it called a wet pipe sprinkler system?

Because the sprinkler piping is normally filled with water under pressure.

What activates a wet pipe sprinkler?

Heat at an individual automatic sprinkler causes its heat-responsive element to operate when the required operating conditions are reached.

Does pulling a fire alarm activate the sprinklers?

Not in a conventional wet pipe sprinkler system. Manual fire alarm boxes initiate the fire alarm system; they do not normally open automatic sprinklers.

Does a smoke detector activate a wet pipe sprinkler?

Normally, no. Automatic sprinklers operate in response to heat. Smoke detectors and automatic sprinklers perform different functions.

Does one sprinkler cause all the other sprinklers to open?

No. Automatic sprinklers operate individually when sufficient heat reaches their operating elements.

Is a sprinkler waterflow switch an alarm or supervisory signal?

Sprinkler waterflow is an alarm function. Valve-position and other specified abnormal sprinkler-system conditions are typically supervisory functions.

Why does a waterflow switch have a retard?

The retard helps prevent brief pressure fluctuations or transient water movement from unnecessarily initiating an alarm while still allowing sustained sprinkler waterflow to be detected within the required time.

Is 90 seconds the required waterflow delay setting?

No. The familiar 90-second requirement represents a maximum alarm-initiation period under the applicable sustained-flow criteria. It is not a universal instruction to set every waterflow switch for a 90-second delay.

Related Fire Sprinkler & Fire Alarm Guides

Understanding a wet pipe system makes the other sprinkler-system types and their fire alarm interfaces much easier to understand.

Fire Alarm Technician's Field Note: When troubleshooting a sprinkler point, identify the sprinkler component before touching the fire alarm programming. Ask what physical condition the device is supposed to detect. Water movement? Valve position? Low air? High air? Once you understand the mechanical function, the correct fire alarm signal type usually makes much more sense.

Studying for the NICET Fire Alarm Systems Exam?

Sprinkler waterflow, valve supervision, pressure switches, alarm versus supervisory signals and fire alarm interfaces are important concepts for fire alarm technicians to understand.

Fire Alarms Online offers a 550-question NICET Fire Alarm Systems practice collection covering Levels I through IV, along with a free 35-question sample for technicians who want to preview the material first.

NICET Fire Alarm Practice Exams • Levels I–IV

Practice fire alarm concepts, code navigation, system operation, supervision, testing and troubleshooting.

View NICET Practice Exams →

Working With Fire Alarm Plans in Bluebeam?

If you also design, estimate or perform takeoffs from electronic plans, Fire Alarms Online offers a purpose-built Bluebeam profile and toolkit for fire alarm layouts, symbols, markups and estimating workflows.

Bluebeam Toolkit for Fire Alarm Professionals

Built for fire alarm design, takeoffs, estimating and faster PDF markup workflows.

View the Bluebeam Toolkit →

Bottom Line

A wet pipe fire sprinkler system is straightforward because water is already present throughout the sprinkler piping.

When sufficient heat operates an individual automatic sprinkler, water immediately discharges through that sprinkler. Sustained waterflow can then operate a waterflow alarm-initiating device, allowing the fire alarm system to receive and process the sprinkler waterflow alarm.

For fire alarm technicians, understanding the difference between sprinkler operation, waterflow alarm and sprinkler supervisory conditions is the key to understanding how the wet pipe system interfaces with the fire alarm system.

1 comment: