| 22.5° | 22.5° | 30° | 30° | |
| OFFSET | DISTANCE BETWEEN BENDS | SHRINK | DISTANCE BETWEEN BENDS | SHRINK |
| 2" | 5-1/4" | 3/8" | ||
| 3" | 7-3/4" | 9/16" | 6" | 3/4" |
| 4" | 10-1/2" | 3/4" | 8" | 1" |
| 5" | 13" | 15/16" | 10" | 1-1/4" |
| 6" | 15-1/2" | 1-1/8" | 12" | 1-1/2" |
| 7" | 18-1/4" | 1-5/16" | 14" | 1-3/4" |
| 8" | 20-3/4" | 1-1/2" | 16" | 2" |
| 9" | 23-1/2" | 1-3/4" | 18" | 2-1/4" |
| 10" | 26" | 1-7/8" | 20" | 2-1/2" |
| 45° | 45° | 60° | 60° | |
| OFFSET | DISTANCE BETWEEN BENDS | SHRINK | DISTANCE BETWEEN BENDS | SHRINK |
| 2" | ||||
| 3" | ||||
| 4" | ||||
| 5" | 7" | 1-7/8" | ||
| 6" | 8-1/2" | 2-1/4" | 7-1-4" | 3" |
| 7" | 9-3/4" | 2-5/8" | 8-3/8" | 3-1/2" |
| 8" | 11-1/4" | 3" | 9-5/8" | 4" |
| 9" | 12-1/2" | 3-3/8" | 10-7/8" | 4-1/2" |
| 10" | 14" | 3-3/4" | 12" | 5" |
Thursday, February 27, 2014
Conduit Bender Offset Reference Table
This is a chart to help you better understand the the shrink amount and the distance between conduit bends when performing a saddle with EMT, Rigid electrical conduit or any other type of electrical conduit. You will want to use the arrow mark on the conduit bender and refer to the degree markers along the side of the conduit bender head. Make sure the electrical conduit is always in line with the pipe bender to insure nice straight bends.